Dz260_05a_oi_e.doc / Dez-16
Page 18 / 40
No.
Display
Key action
Comment
00
001024
The actual value 1024 is displayed, with
the last digit blinking
01
4 x
Change last digit to 0
02
001020
Shift cursor to left
03
001020
2 x
Change highlighted digit to 0
04
001000
2 x
Shift curser to left by 2 positions
05
001000
Change highlighted digit to 0
06
000000
Shift cursor to left
07
000000
5 x
Change highlighted digit to 5
08
050000
Shift cursor to left
09
050000
2 x
Change highlighted digit to 2
10
250000
Save new setting and return to
Parameter Level
6.5.
Return from the Menu, Time-Out Function
At any time the PROG key changes the Menu by one level backwards or fully back to the normal
operation mode. The menu also switches automatically one level backwards, every time when for
10 seconds no key has been touched (Time-Out-Function).
6.6.
Reset all Parameters to Factory Default Values
If applicable, the whole set of parameters can be reset to factory default values (e.g. because a
code for the keypad interlocking has been forgotten, or because the unit does no more work
correctly for reasons of bad settings). All default values are indicated in the following parameter
tables.
To execute this Reset procedure, you have to take the following steps:
Power the unit down
Press
and
simultaneously
Switch power on with both keys held down
When execute this action, please be aware that all parameter settings
will be lost and the whole setup procedure must be repeated!