17 

Altitude & Short Circuit Protection

-20°C (-4°F) to 50°C (122°F). Above 50°C (122°F) de-rate linearly by 4 % of VMX-
Synergy Plus Ie per °C to a maximum of 60°C (140°F).

Altitude above sea level 1000m (3281ft). Above 1000m (3281ft) de rate by 
1% of VMX-Synergy Plus Ie per 100m (328ft) to a maximum altitude of 
2000m (6562ft). Please note for higher temperatures and altitudes contact 
your supplier. 

Short circuit protection 

VMX-Synergy Plus models bearing the UL listing mark are UL 60947-4-2 and CSA C22.2 
No.14 listed to US and Canadian safety standards respectively. 

Size 1 

Type designation (eg. VMX-SGY-I-

…)

 

17 

22 

29 

35 

41 

55 

66 

80 

100 

Rated operational 
currents  

I

e

 

17 

22 

29 

35 

41 

55 

66 

80 

100 

Rated conditional 
short circuit current 

I

q

 

kA 

10 

10 

10 

10 

10 

10 

10 

10 

10 

Class J time-delay 
fuse 

#1

 

Maximum 
rating Z

1

 

25 

30 

40 

45 

60 

70 

90 

100 

125 

UL Listed inverse-
time delay circuit 
breaker 

#1

 

Maximum 
rating Z

2

 

Semiconductor fuse 
(class aR) 

#2

 

Type 

Mersen 6,9 URD 30 _ 

Bussmann 170M30__ 
Bussmann 170M31__ 
Bussmann 170M32__ 

SIBA 20 61___ 

Mersen 6,9 URD 31__ 

Bussmann 170M40__ 
Bussmann 170M41__ 
Bussmann 170M42__ 

SIBA 20 61___ 

Fuse rating  A 

100 

100 

160 

160 

200 

200 

200 

315 

315 

Size 2 and 3 

Type designation (eg. VMX-SGY-I-

…)

 

132 

160 

195 

242 

302 

361 

430 

500 

Rated operational 
currents  

I

e

 

132 

160 

195 

242 

302 

361 

430 

500 

Rated conditional 
short circuit current 

I

q

 

kA 

10 

10 

10 

18 

18 

18 

30 

30 

Class J time-delay 
fuse 

#1

 

Maximum 
rating Z

1

 

175 

200 

250 

350 

400 

450 

600 

600 

UL Listed inverse-
time delay circuit 
breaker 

#1

 

Maximum 
rating Z

2

 

400 

500 

600 

700 

800 

Semiconductor fuse 
(class aR) 

#2

 

Type 

Mersen 6,9 URD 31__ 

Bussmann 170M40__ 
Bussmann 170M41__ 
Bussmann 170M42__ 

SIBA 20 61___ 

Mersen 6,9 URD 33__ 

Bussmann 170M60__ 
Bussmann 170M61__ 
Bussmann 170M62__ 

SIBA 20 63___

 

Fuse rating  A 

400 

550 

550 

900 

900 

900 

1000 

1000 

# 1. Suitable for Use On A Circuit Capable Of Delivering Not More Than ___I

q

___ rms Symmetrical Amperes, 600 

Volts Maximum, When Protected by Class L time delay Fuses with a Maximum Rating of ___Z

1

___ or by a 

Circuit Breaker with a Maximum Rating of ___Z

2

___. 

# 2. Correctly selected semiconductor fuses can provide additional protection against damage to the Synergy Plus 

unit (This is sometimes referred to as type 2 co-ordination). These semiconductor fuses are recommended to 
provide this increased protection. 

Summary of Contents for VMX-Synergy Plus VMX-SGY-I-100

Page 1: ......

Page 2: ...rreur progressif doit tre int gralement v rifi par un agent de maintenance agr Important information Installers should read and understand the instructions in this guide prior to installing operating...

Page 3: ...ce de protection minimal It is the responsibility of the installer to provide suitable grounding and branch circuit protection in accordance with local electrical safety codes Il appartient l installe...

Page 4: ...act Com Port Future use USB Port Motor Connections Status LED Modbus RTU Port Expansion Port Supply Connections Control Terminals Under cover Ground Connection Keypad release point Keypad release poin...

Page 5: ...e 1 VMX SGY I 132 to VMX SGY I 195 Size 2 Dimensions Dimensions VMX SGY I 17 to VMX SGY I 29 Weight 3 9 kg 8 6 lbs VMX SGY I 35 to VMX SGY I 100 Weight 4 2 kg 9 26 lbs VMX SGY I 132 Weight 6 7 kg 14 7...

Page 6: ...stallation VMX SGY I 242 to VMX SGY I 361 Size 3 VMX SGY I 430 to VMX SGY I 500 Size 3 Dimensions Dimensions VMX SGY I 242 to VMX SGY I 361 Weight 17 0 kg 37 5 lbs VMX SGY I 430 to VMX SGY I 500 Weigh...

Page 7: ...m2 10AWG 8 71 VMX SGY I 55 to VMX SGY I 80 10mm2 8AWG VMX SGY I 100 16mm2 6AWG M8 stud VMX SGY I 132 to VMX SGY I 160 16mm2 6AWG 12 106 VMX SGY I 195 25mm2 4AWG VMX SGY I 242 35mm2 3AWG VMX SGY I 302...

Page 8: ...s x number of starts per hour 1200 iERs Disabled Watts VMX Synergy Plus VMX Synergy Plus current rating x 0 6 iERs Enabled The maximum power dissipation occurs when energy saving and the iERS is turne...

Page 9: ...9 Terminal Designations and Wiring Connection...

Page 10: ...30Vac or 24Vdc 230Vac factory default 230Vac d faut d usine 4 The system can have either a 110 230Vac mains or 24Vdc input NOT both Le syst me peut avoir soit une alimentation principale de 110 230Vac...

Page 11: ...re le court circuit dans la section Informations techniques normes du pr sent guide For wire size and torque requirements see Technical Information standards section of this guide Pour les dimensions...

Page 12: ...utes les configurations de c blage doivent galement tre en conformit avec les codes et les r glements locaux et nationaux en vigueur 2 Power factor correction capacitors must NOT be positioned between...

Page 13: ...13 Programming OL 0 0A P 0 1a 1b 2 3 4 5 6 7 8 9 Screen 1a on 1st Power On only Subsequent use will show 1b...

Page 14: ...5 100 VMX SGY I 132 6 01 132 37 75 90 125 40 40 40 100 125 VMX SGY I 160 6 01 160 45 90 110 156 50 50 60 125 150 VMX SGY I 195 6 01 195 55 110 132 192 60 60 75 150 200 VMX SGY I 242 6 01 242 75 132 16...

Page 15: ...Motor overload cold trip curves 20 C ambient Class10 Class20 Class30 Technical Information Fig 1 Trip curves Note When the overload has tripped there is a forced cooling time to allow the overload to...

Page 16: ...10VAC or 230VAC 50 60Hz 5Hz Protect with 4A UL 248 Listed fuse Rated control supply voltage Us See Rating Table 2 Amp supply cont Relay specification 11 12 24 and 33 34 44 AC 15 230VAC 1A DC 13 30VDC...

Page 17: ...40__ Bussmann 170M41__ Bussmann 170M42__ SIBA 20 61___ Fuse rating A 100 100 160 160 200 200 200 315 315 Size 2 and 3 Type designation eg VMX SGY I 132 160 195 242 302 361 430 500 Rated operational cu...

Page 18: ...0 30 55 55 99 30 30 30 75 100 SGY I 100 SGY I 132 SGY I 160 132 37 75 90 125 40 40 40 100 125 SGY I 132 SGY I 160 SGY I 195 160 45 90 110 156 50 50 60 125 150 SGY I 160 SGY I 195 See Size 3 195 55 110...

Page 19: ...ize 3 338 90 185 220 312 100 100 125 250 300 SGY I 195 See Size 3 See Size 3 Size 3 Ie 1 kW FLA 1 Hp Trip Class 10 Trip Class 20 Trip Class 30 A 230V 400V 500V A 200V 208V 220 240V 440 480V 550 600V I...

Page 20: ...ostrokovnjaki in elektrotehni no pou ene osebe Nebezpe enstvo ohrozenia ivota elektrick m pr dom Pr ce ktor s ni ie op san sm vykon vat iba elektroodborn ci a osoby s elektrotechnick m vzdelan m Perig...

Page 21: ...21 Notes...

Page 22: ...22 Notes...

Page 23: ...23 Notes...

Page 24: ......

Reviews: