Environment - Installation
Enclosure Internal Clearances
Conductor size and torque requirements
Terminal
Models
Conductor Size
Torque
Metric
Imperial
Nm Ib-in
Main
Terminals
Cu STR 75
o
C
only
Terminal
VMX-SGY-I-17 to
VMX-SGY-I-100
2.5 - 70mm
2
12- 2/0AWG
9
80
VMX-SGY-I-132 to VMX-SGY-I-195
4 - 185mm
2
12
–
350MCM
14
124
M10 bolt
VMX-SGY-I-242 to VMX-SGY-I-361
2 x 95mm
2
2 x 4/0AWG
28
248
VMX-SGY-I-430 to VMX-SGY-I-500
2 x 150mm
2
2 x 350MCM
Control terminals
All models
0.2
–
1.5mm
2
24-16AWG
0.5
4.5
Protective
Earth
1)
Cu only
M6 stud
VMX-SGY-I-17 to VMX-SGY-I-41
≥
6mm
2
≥
10AWG
8
71
VMX-SGY-I-55 to VMX-SGY-I-80
≥
10mm
2
≥
8AWG
VMX-SGY-I-100
≥
16mm
2
≥
6AWG
M8 stud
VMX-SGY-I-132 to VMX-SGY-I-160
≥ 16
mm
2
≥
6AWG
12
106
VMX-SGY-I-195
≥ 25
mm
2
≥
4AWG
VMX-SGY-I-242
≥ 35
mm
2
≥
3AWG
VMX-SGY-I-302
≥ 35
mm
2
≥
2AWG
VMX-SGY-I-361
≥
50mm
2
≥
1AWG
VMX-SGY-I-430 to VMX-SGY-I-500
≥
70mm
2
≥
1/0AWG
1)
Protective Earth wire size based on bonding conductor requirements of UL508 Table 7.4 and UL508A Table
15.1, with suitable equivalent metric conductor sizes as per IEC 60947-1 Table 7a.
2)
The actual conductor used must comply with local wiring regulations.
Model
A
B
C
mm
inch
mm
inch
mm
inch
VMX-SGY-I-17 to VMX-SGY-I-100
25
0.98
75
2.95
25
0.98
VMX-SGY-I-132 to VMX-SGY-I-195
40
1.57
100
3.93
25
0.98
VMX-SGY-I-242 to VMX-SGY-I-500
60
2.36
125
4.92
25
0,98
A
A
B
B
C
Air Flow