background image

MORTEX

 

PRODUCTS

 

INC

 

501

 

TERMINAL

 

RD

 

FORT

 

WORTH,

 

TX

 

76106

 

Page

 

2

 

SPECIFIC SAFETY RULES AND PRECAUTIONS 

1.

 

Only Natural gas or Propane (LP) gases are approved for 

use with this furnace. Refer to the furnace rating plate or 
SECTION IV of these instructions. 
2.

 

Install this furnace only in a location and position as 

specified in SECTION II of these instructions. 
3.

 

A gas fired furnace for installation in a residential garage 

must be installed as specified in SECTION I of these 
instructions. 
4.

 

Provide adequate combustion and ventilation air to the 

furnace space as specified in SECTION VI of these instructions. 
5.

 

Combustion products must be discharged outdoors. 

Connect this furnace to an approved vent system only, as 
specified in SECTION VI of these instructions. 

 

 

 
 
 
 
 
 
 
 
 
 

 

6.

 

Tests for gas leaks as specified in section IX of these 

instructions. Never test for gas leaks with an open flame. 
7.

 

Always install furnace to operate within the furnaces 

intended rise range with a duct system that has an external static 
pressure within the allowable range, as specified in these 
instructions. See furnace rating plate. 
8.

 

When a furnace is installed so that the supply duct(s) carry 

the air circulated by the furnace to areas outside the space 
containing the furnace, the return air shall also be handled by 
duct(s) sealed to the furnace casing and terminating outside the 
space containing the furnace.  
9.

 

The return air duct system is not required by the 

manufacturer provided the combustion air and vent system have 
been installed  as a Two Pipe Sealed Combustion System and 
provided a return air duct system is not required by state, local 
or regional codes. Refer to sealed combustion systems section in 
ANSI 223.1 (NFPA 54) – latest edition. 
10.

 

It is permitted to use the furnace for heating of buildings or 

structures under construction. Installation must comply with all 
of the manufacturer’s instructions including: 

 

Proper vent installation. 

 

Furnace must be operating under thermostatic control. 

 

Return air duct must be sealed to the furnace. 

 

Air filters must be in place. 

 

Set furnace input rate and temperature rise per the 
rating plate marking. 

 

Means for providing outdoor air required for 
combustion. 

 

Return air maintained between 55°F (13°C) and 80°F 
(27°C). 

 

The air filter must be replaced upon substantial 
completion of the construction process. 

 

Clean furnace supply and return air duct work making 
sure the duct system is free of saw dust, dirt, dust and 
debris. Clean all of the furnace components upon 
substantial completion of the of the construction 
process.  

 

Verify furnace operating conditions including: 

 

 Ignition 

 

Input rate 

 

Temperature rise 

 

Venting system 

 

Verify the furnace is operating according to the 
manufacturer’s instructions.  

11.

 

When installed in a Manufactured (Mobile) Home:

 The 

combustion air shall not be supplied from occupied spaces. 
12.

 

 The size of the furnace shall be based on an acceptable heat 

loss calculation for the structure. ACCA Manual “J” or other 
approved methods may be used. 
13.

 

Gas fired heating equipment must be vented - do not 

operate unvented 
14.

 

If you are replacing an existing furnace, it may be necessary 

to replace the roof jack venting system. Improperly sized or the 
wrong roof jack venting system can result in vent gas leakage or 
the formation of condensate. Refer to the National Fuel Gas 
Code ANSI Z223.1 or CAN/CGA B149.1 or .2 latest editions. 
Failure to follow these instructions can result in injury or death. 
15.

 

To reduce the opportunity for condensation, the minimum 

sea level input to the appliance, as indicated on the rating plate, 
must not be less than 8% below the rated input. 
16.

 

Ensure that the supply voltage to the appliance, as indicated 

on the rating plate, is not 5% greater than the rated voltage.  
17.

 

Manufactured (Mobile) Home Installation:

 This 

appliance must be installed and maintained as a Two Pipe 
Sealed Combustion Configuration. The combustion air pipe 
must terminate in the same atmospheric zone as the vent pipe 
and they must terminate external to the building. 
18.

 

Roof Jack Sizes

 

Mortex is a   4” Vent Pipe with a 7” Combustion Air Pipe. 

 

Coleman is a 5” Vent Pipe with a 8” Combustion Air Pipe. 

 

Nordyne is a  5” Vent Pipe with a 8” Combustion Air Pipe. 

If you replace a Coleman or Nordyne furnace with a Mortex and 
do not change the vent the furnace will fire up for around 5 
seconds to a minute and the flame will extinguish, 
19.

 

Modular Homes:

 This appliance can be installed in one of 

the following configurations: 

a.

 

A Two Pipe Sealed Combustion Configuration. This 
configuration has a combustion air pipe and a vent pipe that 
terminates in the same atmospheric zone and is external to 
the building. Refer to Figures 19 – 25.  

b.

 

A One Pipe Vent with Ambient Combustion Air 
Configuration. This configuration has no combustion air 
pipe connected to the burner box. The vent pipe terminates 
external to the building. 

c.

 

A One Pipe Ventilated Combustion Air Configuration: This 
configuration has the combustion air pipe connected to the 
burner box and terminating in the attic or a crawl space. 
The vent pipe terminates external to the building. The vent 

FIRE OR EXPLOSION HAZARD

 

Failure to follow the safety warnings exactly could result in 
serious injury, death or property damage. A fire or 
explosion may result causing property damage, personal 
injury or loss of life. 
Never test for gas leaks with an open flame. Check all gas 
piping connections with a commercially available soap

 

solution

 

made

 

specifically

 

for

 

detection

 

of

 

leaks.

 

Summary of Contents for G18D SERIES

Page 1: ...30 Reading the Inlet Supply Gas Pressure INP 29 14 Separate T stat furnace Cooling Unit Trans W D 17 31 Reading the Outlet Manifold Gas Pressure 29 15 Same T stat Separate Furnace Cooling Unit Trans W...

Page 2: ...enting system Verify the furnace is operating according to the manufacturer s instructions 11 When installed in a Manufactured Mobile Home The combustion air shall not be supplied from occupied spaces...

Page 3: ...he voltage exceeds 132 VAC This furnace must be installed so the components are protected from water Installing and servicing heating equipment can be hazardous due to the electrical and gas fired com...

Page 4: ...btain the model and serial numbers so the correct parts can be ordered The furnace supply air blower is designed for correct performance with this furnace Do not attempt alter or use a different type...

Page 5: ...rom gas supply line should be performed as described in ANSI Z223 1 latest edition National Fuel Gas Code or in Canada in CAN CGA B149 1 or B149 2 codes 5 Do not attempt to reuse any mechanical or ele...

Page 6: ...OR ACCESS Ample clearances should be provided to permit easy access to the appliance The following minimum clearances are recommended 1 Twenty four 24 inches 61 cm between the front of the furnace and...

Page 7: ...hat the requirements of this subdivision cannot be met at the time of completion of the installation the owner shall have thirty 30 days to comply with the above 48 requirements provided that during t...

Page 8: ...mper is full heating or full cooling position Figure 2 Duct Connector Dimensions Floor Base Installation and Duct Connection Downflow combustible floor base is used for installations on combustible ma...

Page 9: ...g the furnace be sure you have enough clearance to install the furnace and clearance for the return air Refer to Table 1 CLEARANCES 2 Remove the top shipping cover and corner posts 3 Remove the upper...

Page 10: ...d velocity of 300 feet per minute 91 44 m minute cannot be used on the furnace return air louvered door because the air velocity is too high and will destroy the filter The filter velocity with this f...

Page 11: ...2 1 27 cm Table 4 allows for a 0 3 W C 0 075 kPa pressure drop in the ON OFF Pressure Convertable OUT P IN P VENT Manifold Pressure Tap Electrical Terminals Gas Supply Line Pressure Tap GAS FLOW Switc...

Page 12: ...natural gas orifice into the bag and hang it on the gas valve 11 Place the gas valve mounting bracket on the burner mounting plate and secure with the screws you removed in step 5 12 Reconnect the el...

Page 13: ...48 72AG 081 0 081 46 72AG 082 0 082 45 72AG 089 0 089 43 10 000 72AG 073 0 073 49 72AG 078 0 078 47 72AG 081 0 082 46 72AG 089 0 089 43 60 00 BTU FURNACE 70 00 BTU FURNACE 77 00 BTU FURNACE 90 00 BTU...

Page 14: ...ized Proper methods for field installing electrical wiring i Between the furnace and devices not attached to the furnace ii Between the separate devices that are field installed and located iii Exteri...

Page 15: ...Current 60 HZ 0 49 0 49 0 49 0 49 Total Unit Amps 2 54 2 54 2 54 2 54 Model G18D060CA3BA G18D070CA3BA G18D077CA3BA G18D090CA3BA Blower Motor HP 1 3 1 3 1 3 1 3 Blower Mortor SPD 5 5 5 5 Blower Motor...

Page 16: ...e routed through side of furnace and connect to the pig tail wires located above the control box The thermostat wires should also be no smaller than 22 gauges Refer to Table 9 for recommended wire gau...

Page 17: ...use located on the left side of the control board that protects the 24 VAC circuit Replace the fuse only with the equivalent 3 Amp Automotive type fuse Separate Heating and Cooling Thermostats If the...

Page 18: ...ypical Single Stage Heating Cooling Digital Thermostat with Two Stage Furnace Figure 19 Typical Two Stage Heating Cooling Digital Thermostat Connections Typical Heat Pump Heating Cooling Thermostat Wi...

Page 19: ...not less than 17 percent The combustion system is fan assisted This Category I direct vent furnace is designed for Manufactured Home and Modular Home applications It may be installed without modifica...

Page 20: ...rews or rivets Figure 20 Roof Jack Mounting Collars Top of Furnace VENTING INTO AN EXISTING ROOF JACK The furnace shall not be connected to another manufacturers factory built roof jack vent system If...

Page 21: ...per installation of the roof jack requires that openings in the roof and ceiling be on the same vertical center line as the furnace flue collar 2 Once the hole has been cut into the roof insert the ro...

Page 22: ...1000 BTU hr The calculation would be the 50 cubic ft per 1000 BTU hr by the 80 000 BTU Input of all appliances 50 x 80 4000 ft 7 Determine ratio of the available volume to the required volume 2400 ft...

Page 23: ...ply with local codes and requirements NOTE The Roof Jack venting system is considered a special venting system Important Consideration must be given for degradation of building materials by flue gases...

Page 24: ...window or door that may be opened 12 inches 30 cm for models 100 000 BTUH 30 kW 36 inches 91 cm for models 100 000 BTUH 30 kW 4 Feet 1 22 m C Clearance to permanently closed window 12 inches 30 cm 12...

Page 25: ...enting systems are permitted and must be installed in accordance with the National Fuel Gas Code ANSI Z223 1 NFPA 54 and or the CSA B149 1 Natural Gas and Propane Installation Codes local codes and th...

Page 26: ...T C ADJUSTIBLE HEIGHT 90 RJF1729 AL 17 29 FLAT 73 85 94 5 106 5 90 RJF2551 AL 25 51 FLAT 81 107 102 5 128 5 90 RJS1729 AL 17 29 3 12 73 85 94 5 106 5 90 RJS2551 AL 25 51 3 12 81 107 102 5 128 5 90 RJS...

Page 27: ...liance connected to the venting system being placed into operation while all other appliances connected to the venting system are not in operation 1 Seal any unused openings in the venting system 2 In...

Page 28: ...for a CU FT Gas Meter The formula for the input calculation of the appliance if you re heating value is in Mj m you using a cubic meter gas meter Example calculating the input for an appliance operati...

Page 29: ...the gas valve Follow the procedure to shut off the furnace located in the Users Information Manual 5 Turn the switch on the gas valve to the OFF position 6 Turn off the gas supply at the ball valve o...

Page 30: ...als HEAT 120 VAC Blower speed tap connection for heating speed COOL 120 VAC Blower speed tap connection for cooling speed XFMR 120 VAC connection to the transformer L1 120 VAC incoming power supply to...

Page 31: ...try If flame is not established on the first trial for ignition period the gas valve is de energized and the inducer remains energized for an inter purge period of 25 seconds The ignitor is then re e...

Page 32: ...ndoor blower motor on heat speed the other outputs will be kept off and the control will display a LED fault code of 5 When flame is no longer sensed the induced draft motor will run through post purg...

Page 33: ...t be per the following A National Electrical Code NEC and or B Canadian Electrical Code CEC and or C State County Local Regional or City Codes 2 If any origional Factory wire must be replaced then rep...

Page 34: ...ys are integrated into the control board Notes 1 All field wiring must be per the following A National Electrical Code NEC and or B Canadian Electrical Code CEC and or C State County Local Regional or...

Reviews: