The Interface Solution Experts 19
SPA
2
Programmable Current/Voltage
Limit Alarm Trips
Configuring the Analog Output
(-AO Option)
Figure 11 gives an overview of the Analog Output
Configuration menu.
If your unit is equipped with the -AO option, use this
menu for configuration.
1.
Press
SELECT at the “CONFG AOUT” display.
This sends you to the “SEL AOUT” section.
Press
SELECT and use the UP and DOWN
buttons to toggle between current and voltage.
When the selction you desire is displayed,
press
SELECT.
2.
Once you reach the “SET DAMP” field, you
may skip the damping parameter, by using the
Down button to reach the next field. To set
damping, proceed to Step 3.
Damping–
Output Damping allows you to
introduce a delay (0-30sec) into the response
of your unit in order to stop momentary input
variations from setting off alarms.
3.
To set damping, press
SELECT at the “SET
DAMP” display. Use the
UP and DOWN
buttons to enter a value between 0 and 30
seconds; press
SELECT.
4.
Press
SELECT at “FAIL MODE” to program
the setting. Choose “FAIL HIGH” or FAIL
LOW”. This sends you to “EXIT AOUT”.
HIGH/LOW–
Choosing either of these options
will send the output to a High (23.6mA for
current; 11.0V for voltage) or Low (3.6mA for
current; -0.5V for voltage), respectively.
Figure 11.
CONFG AOUT Menu
CONFG
AOUT
D
D
D
U
U
U
SEL
AOUT
SET
DAMP
FAIL
MODE
EXIT
AOUT
SEL
U
TOGGLE
VOLT/
CURRENT
SEL
SEL
D
SCALE AOUT menu
SEL
XX
SEC
(XX = 0-30)
SEL
U
D
SEL
FAIL LOW
FAIL HIGH
SEL
U/D
SEL