Faults
ISA 1
14
Rev. -, April 2019
9
Faults
The faults listed below mainly occur during commissioning.
A reference run must be performed after having rectified the fault.
Value**
Fault
Cause
Rectification
K
The system stops and
reverses briefly
The error text "internal
Error" is displayed
Control is blocked for
5 seconds
Obstacle within the
travelling path
The system resets
automatically or has to be
reset manually by
pressing any button
N
The system stops, the
error text "internal
Error" is displayed
Error counter logging
CAN error
Trigger a manual system
restart by pressing any
button.
Connect SMI and read
error out with GOSUB???
K
The system stops, the
error text "internal
Error" is displayed
Drive is missing or
wrong address
Check error LED of all
drives.
Trigger a manual system
restart by pressing any
button.
Connect SMI and read
error out with GOSUB???
W
Error LED is flashing
Sensor failure
Check flash code.
Trigger a manual system
restart by pressing any
button.
Connect SMI and read
error out with GOSUB???