6.4 More about Run and Shutdown
RUN
– the system measures the heat gain of every zone and automatically holds back the
faster (probe) zones to the same rise rate as the slowest rising zone. This ensures that you
get a homogenous rise across the whole tool.
SHUTDOWN
– the system operates in a similar but reverse method to startup. It switches off
the slowest zone and sets the set temperature of all others to be 30° lower. This ensures that
you get a smooth uniform cool down across the whole tool.
6.5 Control Modes for All Zones
WARNING
Choosing Stop mode does not remove voltage from the heaters.
Do not try to change fuses or disconnect units while in this mod
e.
1. Choose a control mode.
2.
Choose [OK] to confirm the change to the new mode.
Table 6-1 Control Modes for All Zones
Operation
Available By
Description
BOOST
Mode Button Temporarily raises the temperature of all zones that have any
Boost temperature configured. When the Boost period expires,
zone temperatures return to their normal set levels.
RUN
Mode Button System is started in a homogenous heat rise, in which all zones
follow the slowest rising zone. It will switch to RUN when working
temperature has been reached.
SHUTDOWN
Mode Button System is shutdown in a homogenous heat reduction. It will switch
to STOP when temperatures are less than 90°C.
STANDBY
Mode Button Reduces temperatures of all zones that have Standby
Temperatures configured. Temperature remains reduced until
RUN command is given.
STOP
Mode Button Set all power levels to zero. Tool cools down to room temperature
at its own rate.
6-2
© 2020 Mold-Masters (2007) Limited. All Rights Reserved.
OPERATION
Me6 & Me12 Controller User Manual