Basic Connections
(4)
SUPER LINK ADAPTER (SC-AD-E)
(a) Functions
1)
Transmits the settings from the Super link option to the indoor units.
2)
Returns the priority indoor unit data in response to a data request from the Super link option.
3)
Inspects the error status of connected indoor units and transmits the inspection codes to the Super link option.
4)
A maximum of 16 units can be controlled (if in the same operation mode).
(b) Wiring connection diagram
SC-AD-E
A
B
X
Y
Z
X
Y
Z
Blue
Blue
Red
White
Black
Master/Slave address
Network address [00] ~ [47]
Connection to super link
(total length of wires: 1000 m maximum)
0.75 ~ 2.0 mm
2
2-core
Connection to the terminal block for remote control (polar)
(total length of wires: 600 m maximum)
No.
Name ot the recommended signal wire
1
Shielding wire
2
Vinylcabtire round cord
3
Vinyl cabtire round cable
4
Control vinyl insulated, vinyl sheath cable
Master/Slave Address
SW 3-1
ON
Master
OFF
Slave
Shielding wires:
100 ~ 200 m ................. 0.5 mm
2
×
3-core wires
~ 300 m ................. 0.75 mm
2
×
3-core wires
~ 400 m ................. 1.25 mm
2
×
3-core wires
~ 600 m ................. 2.0 mm
2
×
3-core wires
●
Make sure to ground one side only of the shielding wire.
1)
Set the super link network address with SW1 (10-position) and SW2 (1-position).
2)
Without a remote control (no wired remote control and no wireless remote control), set SC-AD-E SW3-1 to ON
(Master).
!
!
Summary of Contents for SRK63ZEA-S1
Page 2: ...TECHNICAL MANUAL...
Page 59: ...57 Service data record form 0 1 2 3 4 5 6 7...
Page 84: ...PARTS LIST SRK63ZEA S1 SRK71ZEA S1 SRC63ZEA S1 SRC71ZEA S1...
Page 88: ...MEMO 86...
Page 94: ...MEMO 92...
Page 105: ...MEMO...
Page 106: ...Manual No 06 SRK T 053 ROOM AIR CONDITIONING TECHNICAL MANUAL PARTS LIST...