22
-
(d)
Fan operation
2
(e)
Standby operation
1) Operation content
1) Operation content
Inverter command speed
0 rps
Indoor fan motor
OFF
Outdoor fan motor
2nd speed
Flap and louver
Fully closed/ Center
4.15 ECONOMY operation
(ECONO button on remote control: ON)
(1)
The set temperature is raised by 1.5°C (0.5°C every one hour) at cooling operation and lowered by 2.5°C (Steps of 1°C, 1°C and
0.5°C every one hour) at heating operation to continue the operation with the following contents.
(2)
Detail of operation
CnT Input
A Unit
B Unit
OFF
OFF
*ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
Note (1) The ON with the * mark indicates an
ON operation using the remote control
unit switch, etc.
*ON
4.16 External control (remote display)/control of input signal
Make sure to connect the wired remote control unit. Control of input signal is not available without the wired remote control unit.
(1)
External control (remote display) output
Following output connectors (CNT) are provided on the printed circuit board of indoor unit.
(a)
Operation output:
Power to engage DC 12V relay (provided by the customer) is outputted during operation.
(b)
Heating output:
Power to engage DC 12V relay (provided by the customer) is outputted during the heating operation.
(c)
Compressor ON output:
Power to engage DC 12V relay (provided by the customer) is outputted while the compressor is
operating.
(d)
Error output:
When any error occurs, the power to engage DC 12V relay (provided by the customer) is outputted.
(2)
Control of input signal
Control of input signal (switch input, timer input) connectors (CNT) are provided on the control circuit board of the indoor unit.
However, when the operation of air conditioner is under the Center Mode, the remote control by CnT is invalid.
(a)
If the factory settings (Jumper wire J1 EXTERNAL INPUT on the PCB) are set, or “LEVEL INPUT” is selected in the wired
remote control’s indoor unit settings.
1) Input signal to CnT OFF
→
ON Air conditioner ON
2) Input signal to CnT ON
→
OFF Air conditioner OFF
Inverter command speed
0 rps
Indoor fan motor
OFF
Outdoor fan motor
Determined by stop mode
Flap and louver
Fully closed/ Center
(b)
When Jumper wire J1 on the PCB of indoor unit is cut at the field or “PULSE INPUT” is selected in the wired remote
control’s indoor unit settings.
Input signal to CnT becomes valid at OFF
→
ON only and the motion of air conditioner [ON/OFF] is inverted.
CnT Input
A Unit
B Unit
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
OFF
Model
SRK63ZEA-S1
SRK71ZEA-S1
Item
Operation mode
Cooling
Heating
Cooling
Heating
Inverter command speed
12~46 rps
12~60 rps
12~52 rps
12~66 rps
Indoor fan motor
2nd, 4th speed
3rd, 5th speed
2nd, 4th speed
3rd, 5th speed
Outdoor fan motor
3rd~5th speed
Summary of Contents for SRK63ZEA-S1
Page 2: ...TECHNICAL MANUAL...
Page 59: ...57 Service data record form 0 1 2 3 4 5 6 7...
Page 84: ...PARTS LIST SRK63ZEA S1 SRK71ZEA S1 SRC63ZEA S1 SRC71ZEA S1...
Page 88: ...MEMO 86...
Page 94: ...MEMO 92...
Page 105: ...MEMO...
Page 106: ...Manual No 06 SRK T 053 ROOM AIR CONDITIONING TECHNICAL MANUAL PARTS LIST...