59
-
Current cut
[Open phase on compressor output
terminal, compressor lock]
YES
YES
NO
NO
YES
NO
¡
Check compressor wiring visually.
¡
Check insulation resistance. (1 M
Ω
or over)
¡
Check coil wire resistance. (Few
Ω
)
Does current cut operate when
operating inverter with compressor
wire disconnected?
Is output voltage applied to all 3
phases of power transistor?
Is there any shortcircuit?
Inspect compressor.
Defective inverter
Defective inverter
Secure space for suction
and blow out.
If check results are normal,
compressor is locked.
Abnormality of outdoor unit
[Compressor malfunction of
insufficient gas (refrigerant)]
Does compressor operation?
Is capacitor for compressor normal?
Replace compressor.
Replace heat exchanger sensor
Insufficient gas
Is refrigerant amount normal?
Is heat exchanger sensor resistance
value good?
Is connector for compressor connection
good?
Does trouble persist after charging gas?
Clogged capillary tube or strainer,
defective EEV, etc.
Replace capacitor for compressor.
Correct connection
Check if there are any places where
gas is leaking
YES
YES
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
Current safe stop
[Overload operation, compressor
lock, overcharge]
Secure space for inlet and outlet.
Discharge refrigerant.
Is refrigerant charge quantity adequate?
Is outdoor ventilation condition good?
Inspect compressor.
Defective inverter
YES
YES
NO
NO
YES
Summary of Contents for SRK63ZEA-S1
Page 2: ...TECHNICAL MANUAL...
Page 59: ...57 Service data record form 0 1 2 3 4 5 6 7...
Page 84: ...PARTS LIST SRK63ZEA S1 SRK71ZEA S1 SRC63ZEA S1 SRC71ZEA S1...
Page 88: ...MEMO 86...
Page 94: ...MEMO 92...
Page 105: ...MEMO...
Page 106: ...Manual No 06 SRK T 053 ROOM AIR CONDITIONING TECHNICAL MANUAL PARTS LIST...