15
-
(4)
Defrosting operation
(a)
Starting conditions (Defrosting operation can be started only when all of the following conditions are met.)
1)
1
After start of heating operation
→
When it elapsed 45 minutes.(Accumulated compressor operation time)
2
After end of defrosting operation
→
When it elapsed 45 minutes.(Accumulated compressor operation time)
3
Outdoor unit heat exchanger sensor (Th4) temperature
→
When the temperature has been below –5°C for 3 minutes
continuously.
4
¡
The outdoor air temperature => –17°C
The difference between the outdoor air temperature sensor temperature and the outdoor heat exchanger temperature
sensor temperature is => 7°C.
¡
The outdoor air temperature < –17°C
The difference between the outdoor air temperature sensor temperature and the outdoor heat exchanger temperature
sensor temperature is => –5°C.
5
During continuous compressor operation (Defrost operations shall not be performed from 10 minutes after the compressor
begins running.)
2) In addition, when the inverter command speed from the indoor controller of the indoor unit during heating operation has
counted 0 rps 10 times or more and all conditions of
1
,
2
,
3
and
5
above and when the outdoor air temperature is 3°C
or less are satisfied (note that when the temperature for Th4 is -5°C or less: 30 rps or more, -4°C or less: less than 30 rps),
After running at an inverter command speed of 40rps for 7 minutes, defrost operations will start.
3)
1
After start of heating operation
→
Less than 45 minutes.(Accumulated compressor operation time)
2
After end of defrosting operation
→
Less than 45 minutes.(Accumulated compressor operation time)
3
Outdoor unit heat exchanger sensor (Th4) temperature
→
When the temperature has been below –5°C for 3 minutes
continuously.
4
¡
The outdoor air temperature => –17°C
The difference between the outdoor air temperature sensor temperature and the outdoor heat exchanger temperature
sensor temperature is => 20°C.
¡
The outdoor air temperature < –17°C
The difference between the outdoor air temperature sensor temperature and the outdoor heat exchanger temperature
sensor temperature is => 15°C.
5
During continuous compressor operation (Defrost operations shall not be performed from 10 minutes after the compressor
begins running.)
(c)
Hot keep operation
If the hot keep operation is selected during the heating operation, the indoor blower is controlled based on the temperature of
the indoor unit heat exchanger (detected with Th2, indoor unit heat exchanger sensor) to prevent blowing of cool wind.
Note (1) Refer to the table shown above right for the values A and B.
¡
Hot keep N mode (Air flow: HI, MED, LO, ULO)
Indoor heat exchanger temp. (˚C)
¡
Values of A, B
A
B
At 0 rps command
22
25
Other than 0 rps
10
15
command
Notes (1) Refer to the table shown above right for the values A and B.
¡
Hot keep M mode (Air flow: AUTO, HIGH POWER, ECONOMY)
Indoor heat exchanger temp. (˚C)
¡
Values of A, B
A
B
At 0 rps command
22
25
Other than 0 rps
10
15
command
Indoor f
an speed
A B 26 27
28
29.5 31.5
33
35.5 38
40.5
43
45.5
48
OFF
!0
o
i
u
y
t
r
e
w
q
Indoor f
an speed
A B 26 27
28
29.5 31.5
33
34.5 36
37.5
39
40.5
42
OFF
!0
o
i
u
y
t
r
e
w
q
Summary of Contents for SRK63ZEA-S1
Page 2: ...TECHNICAL MANUAL...
Page 59: ...57 Service data record form 0 1 2 3 4 5 6 7...
Page 84: ...PARTS LIST SRK63ZEA S1 SRK71ZEA S1 SRC63ZEA S1 SRC71ZEA S1...
Page 88: ...MEMO 86...
Page 94: ...MEMO 92...
Page 105: ...MEMO...
Page 106: ...Manual No 06 SRK T 053 ROOM AIR CONDITIONING TECHNICAL MANUAL PARTS LIST...