background image

-

 106 

-

 '16 • SCM-T-199

Check before installation work

1

1

2

2

1

Q’ty

Standard accessories (installation kit)

Accessories for indoor unit

Wireless remote control

Remote control holder

Battery [R03 (AAA, Micro) 1.5V]

Joint (for drain hose)

2

8

2

4

Washer (for suspension bolt M10)

2

Flat head machine screw (for remote control signal receiver M3.5x10)

1

Plate (display)

Clamp (for drain hose) (big:1, small:1)

Wood screws (for remote control holder ø3.5 X 16mm)

• Model name and power source • Refrigerant piping length • Piping, wiring and miscellaneous small parts

10

9

8

Band

Pipe cover (big:1, small:1)

13

12

7

6

5

2

1

Remote control signal receiver

3

1

Installation frame (for remote control signal receiver)

4

1

Necessary tools for the installation work

1

2

3

4

5

6

7

8

9

Plus headed driver

Knife

Saw

Tape measure

Hammer

Spanner wrench

Torque wrench [14.0-62.0N·m (1.4-6.2kgf·m)]

Hole core drill (65mm in diameter)

W

rench key (Hexagon) [4m/m]

10

Flaring tool set (Designed specifically for R410A)

11

Gas leak detector (Designed specifically for R410A)

12

Gauge for projection adjustment (Used when flare is  made by using conventional flare tool)

13

Pipe bender

1

Q’ty

Option parts (Separately sold parts)

Bottom air inlet kit    25, 35 models : UT-BAT1EF   50, 60 models : UT-BAT2EF

Q’ty

Locally procured parts

1

4

8

4

Drain hose (VP25)

Suspension bolts (M10)

Nuts (M10)

Spring lock washers (M10)

H

G

F

E

1

1

1

1

Sealing plate

Sleeve

Inclination plate

Putty

D

C

B

A

11

When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use pipe hole sleeve sold separately.

Drilling of hole and fixture of sleeve (Locally procured parts)

Top

Sleeve

Thickness of the  wall + 1.5cm

Indoor side

Outdoor side

5

ø65

Indoor side

Outdoor side

Installed state

Turn to tighten

B

C

* Sleeve is for use in refrigerant piping work. Please install another pipe separately for drain piping work.

 

In case of rear piping draw out, cut off the lower  and the right side portions of the sleeve collar.

 

Drill a hole with whole core drill.

Dimensions of the opening on the ceiling after removing inspection opening (1)

Model

25, 35

50, 60

A

750

950

B

770

970

C

100(80) or more

D

150(50) or more

E

270

or more

F

150(0) or more

D

Dedicated inspection opening must be provided.

Inspection opening (1)

Inspection opening (2)

Indoor Unit

Ceilin

g plate

Air intake direction

E

F

unit : mm

1000 or more

unit : mm

Obstacle

1000 or more

Obstacle

Pipe locations

All models

Suspension Bolt Location

A

B

Model 25, 35 50, 60

A 790 990

B 457 457

○ 

Adhere

 to the measurements given 

below for the length of the suspension  bolts.

Unit

Suspension

 bolt (M10)

Under 60 mm

Remove bracket in this direction. 

Inspection opening (1)

Service

Inspection opening (2)

Clamping of the flare of required and  gas refrigerant pipe

Use

Not Use

Drain pipe connection

Use

Not Use

Installation and removal of blower

Not Use

Use

Control box

Connecting wire (between indoor and  outdoor)

Use

Not Use

Unit display section (Wireless remote   control signal receiver)

Use

Not Use

Replace drain pump

Use

Not Use

Replace heat exch sensor

Use

Not Use

Replace air filter

Not Use

Use

Refrigerant gas pipe

Refrigerant liquid pipe

Drain Pipe connection VP25 (I.D. 25, O.D. 32)

500

413

370

326

380

200

168

105

55

30

30

Gravity drainage

The minimum dimensions when used Bottom  air inlet kit (Option parts) are shown in  parentheses.

 Wireless remote control

 Remote control holder

 Wood screws

Sleeve

(Locally procured 

parts)

3

 Remote control  signal

 receiver

450

○ 

Remove bracket from the unit after 

unpacking according to process as shown 

belo

w

.

(1)

 Loosen 2 screws.

(2)

 Remove bracket.

(3)

 T

ighten the screws.

Sleeve

Inclination plate

A

Sealing plate

B

Drain pipe, refrigerant gas pipe and refrigerant liquid pipe

A

200

C

200

Air blowout direction

Air outlet

100

450

B

F

E

Screw

CAUTION

Completely seal the hole on  the wall with putty. Otherwise,  furniture, or other, may be  wetted by leaked water or  dewing.

putty

putty

Indoor side

Outdoor side

D

D

Grill (Prepare on site)

37

SELECTION OF INSTALLATION LOC

ATION

INSTALLATION OF INDOOR UNIT

Indoor unit

(Install at location that meets the following conditions, after getting approval from the customer)

○ Where there is no obstructions to the air flow and where the 

cooled and heated air can be evenly distributed.

○ A firm location that may sustain the weight of the unit, and 

do not cause the unit or the ceiling to vibrate.

○ A place where there will be enough space for servicing. (Wher

e space mentioned below can be secured)

○ Where wiring and the piping work will be easy to conduct. ○ The place where receiving part is not exposed to the direct r

ays of the sun or the strong rays of the street lighting.

○ A place where it can be easily drained. ○ A place separated at least 1m away from the television or the

 radio. (To prevent interference to images and sounds.)

○ Places where this unit is not affected by the high frequency 

equipment or electric equipment.

○ Avoid installing this unit in place where there is much oil m

ist.

○ Places where there is no electric equipment or household unde

r the installing unit.

Wireless remote control

Space for installation and service

○ A place where the air-conditioner can be received the signal 

surely during operating the wireless remote control.

○ Places where there is no affected by the TV and radio etc. ○ Do not place where exposed to direct sunlight or near heat de

vices such as a stove.

○ Where the suction inlet of the unit is located far from the a

ir inlet on the ceiling, the 

entire inside of ceiling acts as an 

air suction duct so that the capacity is reduced at the startup.

○ 

Areas where dew point is lower than around 28°C and relative humidity is lower than 80%. This indoor unit is tested under the condition of JIS (Japan Industrial Standard) high

 humidity condition and 

confirmed there is no problem. However, there is some risk of condensation drop if

 the air-conditioner is operated 

under the severer condition than mentioned above. If there is a possibility to use it under such a condition, attach additional insulation o

f 10 to 20mm thick for entire 

surface of indoor unit, refrigeration pipe and drain pipe.

Inspection opening for services

R410

A REFRIGERAN

T USED

FOR MODE

L SRR SERIES

INSTALLATION MANUAL FOR INDOOR UNIT

RJJ012A002

W

ARNIN

G

• 

Installation must be carried out by the qualified installe

r.

 

If you install the system by yourself, it may cause serious trouble such as  water leaks, electric shocks, fire and personal injur

y, as a result of a 

system malfunction. Do not carry out the installation and maintenance  work except the by qualified installe

r.

• 

Install the system in full accordance with the installation manual.

 

Incorrect installation may cause bursts, personal injur

y, water leaks, 

electric shocks and fire.

• 

Be sure to use only for household and residence. 

 

If this appliance is installed in inferior environment such as machine shop  and etc., it can cause malfunction. 

• 

Use the original accessories and the specified components for  installation.

 

If parts other than those prescribed by us are used, It may cause water  leaks, electric shocks, fire and personal injur

y.

• 

Install the unit in a location with good support.

 

Unsuitable installation locations can cause the unit to fall resulting in  material damage and personal injur

y.

• 

Ventilate the working area well in the event of refrigerant leakage  during installation.

 

If the refrigerant comes into contact with naked flames, poisonous gas is  produced.

• 

When installing in small rooms, take prevention measures not to  exceed the density limit of refrigerant in the event of leakage,  referred by the formula (accordance with ISO5149). 

 

If the density of refrigerant exceeds the limit, consult the dealer and  install the ventilation system, otherwise lack of oxygen can occu

r, which 

can cause serious accident. 

• 

After completing installation, check that no refrigerant leaks from  the system.

 

If refrigerant leaks into the room and comes into contact with an oven or  other hot surface, poisonous gas is produced.

• 

Use the prescribed pipes, flare nuts and tools for R410A.

 

Using existing parts (for R22 or R407C) can cause the unit failure and  serious accidents due to burst of the refrigerant circuit.

• 

Tighten the flare nut by torque wrench with specified method.

 

If the flare nuts were tightened with excess torque, this may cause burst  and refrigerant leakage after a long period.

• 

The electrical installation must be carried out by the qualified  electrician in accordance with “the norm for electrical work” and  “national wiring regulation”, and the system must be connected to  the dedicated circuit.

 

Power source with insu

fficient capacity and incorrect function done by 

improper work can cause electric shocks and fire.

• 

Be sure to shut off the power before starting electrical work.

 

Failure to shut o

ff the power can cause electric shocks, unit failure or 

incorrect function of equipment.

• 

Be sure to use the cables conformed to safety standard and cable  ampacity for power distribution work. 

 

Unconformable cables can cause electric leak, anomalous heat  production or fire.

• 

This appliance must be connected to main power source by means  of a circuit breaker or switch (fuse:16A) with a contact separation of  at least 3mm. 

• 

When plugging this appliance, a plug conforming to the norm  IEC60884-1 must be used.

• 

Use the prescribed cables for electrical connection, tighten the  cables securely in terminal block and relieve the cables correctly to  prevent overloading the terminal blocks.

 

Loose connections or cable mountings can cause anomalous heat  production or fire.

• 

Arrange the wiring in the control box so that it cannot be pushed up  further into the box. Install the service panel correctl

y.

 

Incorrect installation may result in overheating and fire.

• 

Be sure to switch off the power source in the event of installation,  inspection or servicing.

 

If the power source is not shut o

ff, there is a risk of electric shocks, unit 

failure or personal injury due to the unexpected start of fan.

• 

Be sure to wear protective goggles and gloves while at work.

• 

Earth leakage breaker must be installed.

 

If the earth leakage breaker is not installed, it can cause electric shocks.

CAUTION

• 

Use the circuit breaker of correct capacity. Circuit breaker should  be able to disconnect all poles under over current.

 

Using the incorrect one could cause the system failure and fire.

• 

Install isolator or disconnect switch on the power source wiring in  accordance with the local codes and regulations.

 

The isolator should be locked in OFF state in accordance with  EN60204-1.

• 

Be sure to install indoor unit properly according to instruction  manual so that drainage can run off smoothly.

 

Improper installation of indoor unit can cause dropping water into the  room and damaging personal property.

• 

Install the drainage pipe to run off drainage securely according to  the installation manual.

 

Incorrect installation of the drainage pipe can cause dropping water into  the room and damaging personal property.

• 

Be sure to install the drainage pipe with descending slope of 1/100  or more, and not to make traps and air-bleedings.

 

Check if the drainage runs off securely during commissioning and ensure  the space for inspection and maintenance. 

• 

After maintenance, all wiring, wiring ties and the like, should be  returned to their original state and wiring route, and the necessary  clearance from all metal parts should be secured.

• 

Secure a space for installation, inspection and maintenance  specified in the manual.

 

Insufficient space can result in accident such as personal injury due to  falling from the installation place.

• 

Take care when carrying the unit by hand.

If the unit weights more than 20kg, it must be carried by two or more  persons. Do not carry by the plastic straps, always use the carry handle 

when carrying the unit by hand. Use gloves to minimize the risk of cuts  by the aluminum fins.

• 

Dispose of any packing materials correctly.

 

Any remaining packing materials can cause personal injury as it contains  nails and wood. And to avoid danger of suffocation, be sure to keep the  plastic wrapper away from children and to dispose after tear it up.

• 

For installation work, be careful not to get injured with the heat  exchanger, piping flare portion or screws etc.

• 

Be sure to insulate the refrigerant pipes so as not to condense the  ambient air moisture on them.

 

Insufficient insulation can cause condensation, which can lead to  moisture damage on the ceiling, floor, furniture and any other valuables.

• 

When perform the air-conditioner operation (cooling or drying  operation) in which ventilator is installed in the room. In this case,  using the air-conditioner in parallel with the ventilator, there is the  possibility that drain water may backflow in accordance with the  room lapse into the negative pressure status. Therefore, set up the  opening port such as incorporate the air into the room that may  appropriate to ventilation (For example; Open the door a little). In  addition, just as above, so set up the opening port if the room lapse  into negative pressure status due to register of the wind for the high  rise apartment etc.

• 

Be sure to perform air tightness test by pressurizing with nitrogen  gas after completed refrigerant piping work.

 

If the density of refrigerant exceeds the limit in the event of refrigerant  leakage in the small room, lack of oxygen can occur,  which can cause  serious accidents.

• 

Do not install the unit in the locations listed belo

w

.

 

• 

Locations where carbon fibe

r, metal powder or any powder is floating.

 

• 

Locations where any substances that can a

ffect the unit such as sulphide 

gas, chloride gas, acid and alkaline can occu

r. 

 

• 

Vehicles and ships.

 

• 

Locations where cosmetic or special sprays are often used.

 

• 

Locations with direct exposure of oil mist and steam such as kitchen and  machine plant.

 

• 

Locations where any machines which generate high frequency harmonics  are used.

 

• 

Locations with salty atmospheres such as coastlines. 

 

• 

Locations with heavy snow (If installed, be sure to provide base flame and  snow hood mentioned in the manual).

 

• 

Locations where the unit is exposed to chimney smoke.

 

• 

Locations at high altitude (more than 1000m high).

• 

Locations with ammonic atmospheres (e.g. organic fertilizer).

• 

Locations with calcium chloride (e.g. snow melting agent).

 

• 

Locations where heat radiation from other heat source can a

ffect the unit.

 

• 

Locations without good air circulation.

 

• 

Loca

tions

 wi

th

 any

 obs

tacles

 which

 can

 pre

ven

t inle

t and

 ou

tle

t air

 o

f t

he

 uni

t.

 

• 

Locations where short circuit of air can occur (in case of multiple units  installation).

 

• 

Locations where strong air blows against the air outlet of outdoor unit.

 

• 

Locations where something located above the unit could fall.

 

It can cause remarkable decrease in performance, corrosion and damage of  components, malfunction and fire.

• 

Do not install the indoor unit in the locations listed below (Be sure to  install the indoor unit according to the installation manual fo

r each 

model because each indoor unit has each limitation).

 

• 

Locations with any obstacles which can prevent inlet and outlet air of the  unit.

 

• 

Locations where vibration can be amplified due to insu

fficient strength of 

structure.

 

• 

Locations where the infrared receiver is exposed to the direct sunlight or  the strong light beam (in case of the infrared specification unit).

 

• 

Locations where an equipment a

ffected by high harmonics is placed (TV 

set or radio receiver is placed within 1m).

 

• 

Locations where drainage cannot run o

ff safel

y.

 

It can a

ffect performance or function and etc. 

• 

Do not install the unit near the location where leakage of combustible 

gases can occu

r.

 

If leaked gases accumulate around the unit, it can cause fire.

• 

Do not install the unit where corrosive gas (such as sulfurous acid  gas etc.) or combustible gas (such as thinner and petroleum gas

es) 

can accumulate or collect, or where volatile combustible substa

nces 

are handled.

 

Corrosive gas can cause corrosion of heat exchange

r, breakage of plastic 

parts and etc.

 And combustible gas can cause fire.

• 

Do not use the indoor unit at the place where water splashes may  occur such as in laundries.

 

Since

 the

 indoor

 uni

t i

no

t wa

terproo

f, 

it 

can

 c

au

se

 ele

ct

ric

 shoc

ks

 and

 fire

• 

Do not install nor use the system close to the equipment that  generates electromagnetic fields or high frequency harmonics.

 

Equipment such as inverters, standby generators, medical high frequency  equipments and telecommunication equipments can a

ffect the system, and 

cause malfunctions and breakdowns.

 The system can also a

ffect medical 

equipment and telecommunication equipment, and obstruct its function or  cause jamming.

• 

Do not place any variables which will be damaged by getting wet  under the indoor unit.

 

When the relative humidity is higher than 80% or drainage pipe is clogged,  condensation or drainage water can drop and it can cause the damage of  valuables.

• 

Do not install the remote control at the direct sunlight.

 

It can cause malfunction or deformation of the remote control.

• 

Do not use the unit for special purposes such as storing foods,  cooling precision instruments and preservation of animals, plan

ts or 

art.

 

It can cause the damage of the items.

• 

Do not use any materials other than a fuse with the correct rating in  the location where fuses are to be used.

 

Connecting the circuit with copper wire or other metal thread can cause unit  failure and fire.

• 

Do not touch any buttons with wet hands.

 

It can cause electric shocks.

• 

Do not touch any refrigerant pipes with your hands when the system  is in operation.

 

During operation the refrigerant pipes become extremely hot or extremely  cold depending the operating condition, and it can cause burn injury or frost  injur

y.

• Do not wash the inside of the air-conditione

r.

 

W

ater leakage and permanent damage may result.

 

Electrical hazard exists.

• 

Carry out the electrical work for ground lead with care.

 

Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line

’s ground lead. Incorrect grounding can cause unit 

faults such as electric shocks due to short-circuiting.

• 

Do not put the drainage pipe directly into drainage channels where  poisonous gases such as sulphide gas can occu

r.

 

Poisonous gases will flow into the room through drainage pipe and  seriously a

ffect the use

r’s health and safet

y.

 This can also cause the 

corrosion of the indoor unit and a resultant unit failure or refrigerant leak.

• 

Ensure that no air enters in the refrigerant circuit when the unit is  installed and removed.

 

If air enters in the refrigerant circuit, the pressure in the refrigerant circuit  becomes too high, which can cause burst and personal injur

y.

• 

Do not process or splice the power cord, or share the socket with  other power plugs.

 

This may cause fire or electric shock due to defecting contact, defecting  insulation and over-current etc.

• 

Do not bundle or wind or process the power cord. Do not deform  the power cord by treading it.

 

This may cause fire or heating.

• 

Do not vent R410

A into the atmosphere : R410

A is a fluorinated 

greenhouse gas, covered by the Kyoto Protocol with Groval  W

arming Potential (GWP)=1975.

• 

Do not run the unit with removed panels or protections.

 

Touching rotating equipments, hot surfaces or high voltage parts can  cause personal injury due to entrapment, burn or electric shocks.

• 

Do not perform any change of protective device itself or its setup  condition.

 

The forced operation by short-circuiting protective device of pressure  switch and temperature controller or the use of non specified component  can cause fire or burst.

SAFET

Y PRECAUTION

S

• 

Before installation, read the “SAFETY PRECAUTIONS” carefully and strictly  follow it during the installation work in order to protect yourself.

• 

The precautionary items mentioned below are distinguished into two levels,

                           and                        .                            : 

W

rong installation would cause serious consequences such 

as injuries or death.

                           : 

W

rong installation might cause serious consequences 

depending on circumstances.

 

Both mention the important items to protect your health and safety so strictly  follow them by any means.

• 

Be

 sure

 to

 confirm

 no

 anomaly

 on

 the

 equipment

 by

 commissioning

 after

 completed 

installation

 and

 explain

 the

 operating

 methods

 as

 well

 as

 the

 maintenance

 methods 

of this equipment to the user according to the owne

r’s manual. 

• 

Keep the installation manual together with owne

r’s manual at a place where 

any user can read at any time. Moreover if necessar

y, ask to hand them to a 

new use

r.

• 

Before starting the installation work, proper precautions (using suitable  protective clothing, groves etc.) should be taken by qualified installer.

• 

Pay attention not to fall down the tools, etc. when installing the unit at the  high position.

• 

If unusual noise can be heard during operation, consult the deale

r.

• 

The meanings of “Marks” used here are shown as follows:

Never do it under any  circumstances.

Always do it according to the  instruction.

CAUTION

W

ARNING

CAUTION

W

ARNING

• 

This installation manual illustrates the method of installing an indoor unit.

• 

For electrical wiring work, see instructions set out on the backside.

• 

For outdoor unit installation and refrigerant piping, refer to page 18. 

• 

While installing the unit, be sure to check the selection of installation place,  power source specifications, usage limitation (piping length, height  differences between indoor and outdoor units, power source voltage etc.)  and installation spaces. 

• 

A wired remote control unit is supplied separately as an option part.

Summary of Contents for SCM40ZS-S

Page 1: ...ZS S 50ZS S INDOOR UNIT Wall mounted type SRK20ZMX S 25ZMX S 35ZMX S 50ZMX S SRK20ZS S 25ZS S 35ZS S 50ZS S SKM20ZSP S 25ZSP S 35ZSP S Floor standing type SRF25ZMX S 35ZMX S 50ZMX S 4way ceiling casse...

Page 2: ...ressure type FDUM 52 5 Ceiling suspended type FDE 62 6 Duct connected Low Middle static pressure type FDUM 63 2 Floor standing type SRF 47 2 2 Exterior dimensions 44 44 1 2 Exterior dimensions 12 1 3...

Page 3: ...sette type FDTC 3 PIPING SYSTEMS 124 4 RANGE OF USAGE LIMITATIONS 126 7 1 SRK20 50ZMX S SRF and SRR series 135 7 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER 135 138 7 1 1 Operation control function...

Page 4: ...ntrol 3 Installing two air conditioners in the same room 151 2 Auto restart function 1 Unit ON OFF button 151 150 7 2 2 Operation control function by indoor control 151 152 6 High power operation 152...

Page 5: ...nction by the indoor control 7 4 2 Operation control function by the wired remote control 170 7 4 1 Remote control Option parts 167 8 Determining the operating mode 164 9 Outline of dehumidifying DRY...

Page 6: ...rature thermistor return air indoor heat exchanger wire short circuit detection 186 23 Selection of cooling heating external input function 187 25 Return air temperature compensation 24 Room temperatu...

Page 7: ...ll 199 5 Self diagnosis table 200 6 Service mode Trouble mode access function 201 209 7 Inspection procedures corresponding to detail of trouble 9 Checking the indoor electrical equipment 215 8 Phenom...

Page 8: ...ooting flow 232 233 2 Troubleshooting 1 List of troubles 232 6 Inverter checker for diagnosis of inverter output 231 4 Outdoor unit inspection points 228 1 FDTC series RCN TC 24W ER 292 2 FDE series R...

Page 9: ...l mounted type SRK ZMX S Wall mounted type SRK ZS S Wall mounted type SKM ZSP S Duct connected Low Middle static pressure type FDUM 4way ceiling cassette type FDTC Ceiling suspended type FDE Example I...

Page 10: ...tion Frost protection Serial signal error protection Outdoor fan motor error protection Heating Cooling overload protection Installation data Refrigerant piping size O D mm Liquid line 6 35 1 4 2 Gas...

Page 11: ...tion Serial signal error protection Outdoor fan motor error protection Heating Cooling overload protection Installation data Refrigerant piping size O D mm Liquid line 6 35 1 4 2 Gas line 9 52 3 8 2 C...

Page 12: ...ction Outdoor fan motor error protection Heating Cooling overload protection Installation data Refrigerant piping size O D mm Liquid line 6 35 1 4 3 Gas line 9 52 3 8 3 Connecting method Flare connect...

Page 13: ...ischarge hole Symbol B A Service valve connection gas side M10 12 4 places 20 2 places Service valve connection liquid side 6 35 1 4 Flare 280 136 253 16 4 20 14 6 Notes 1 The unit must not be surroun...

Page 14: ...321 7 42 7 20 20 290 476 203 1 510 850 14 6 2 12x16 17 9 65 274 290 Slot hole 155 21 10 Minimum installation space Center of gravity Terminal block Center of gravity Notes 1 The unit must not be surr...

Page 15: ...L 250V F3 CNFAN YG YG RD BR EEV B M RD EEV A EEV B L Compressor motor Electric expansion valve coil Reactor Tho A Tho D Heat exchanger sensor Outdoor air temp sensor Discharge pipe temp sensor CM Tho...

Page 16: ...YG C 2 RD C 1 CN20V CN20V G1 YG G YG CNEEV1 CNEEV3 CNA CNB CNC N L EEV EEV YG WH BK UNIT A UNIT B UNIT C M POWER SOURCE WH RD BL 20S HEATER WH RD CNHEAT BK WH RD BK WH BR BK WH BL Tho D Tho A Tho R 2...

Page 17: ...10 5 Pa 10 20 30 40 50 60 70 N50 N30 N40 N60 N70 N20 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Mid octave band frequency Hz Sound pressure level dB Standard 2 10 5 Pa 10 20 30 40 50 60 7...

Page 18: ...ating 51 dB A Cooling Heating Condition ISO T1 JIS C 9612 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Mid octave band frequency Hz Sound pressure level dB Standard 2 10 5 Pa 10 20 30 40 50...

Page 19: ...ers can cause electric shock personal injury or property damage Be sure to switch off the power source in the event of installation mainte nance or service If the power source is not switched off ther...

Page 20: ...2 Location of snow accumulation Install the unit on the base so that the bottom is higher than snow cover surface Install the unit under eaves or provide the roof on site 3 Installation space There mu...

Page 21: ...rise even if the system is left for 15 minutes or more Vacuum gauge indicator will rise if the system has moisture left inside or has a leakage point Check the system for the leakage point If leakage...

Page 22: ...prevent it from heating and dew condensation Use the heat insulating material which can withstand 120 C or higher temperature Make sure that insulation is wrapped tightly around the pipes and no gap i...

Page 23: ...re control Microcomputer thermostat Operation display RUN Green TIMER Yellow HI POWER Green 3D AUTO Green ECONO Blue Safety equipments Frost protection Serial signal error protection Indoor fan motor...

Page 24: ...display RUN Green TIMER Yellow HI POWER Green 3D AUTO Green ECONO Blue Safety equipments Frost protection Serial signal error protection Indoor fan motor error protection Installation data Refrigeran...

Page 25: ...display RUN Green TIMER Yellow HI POWER Green 3D AUTO Green ECONO Blue Safety equipments Frost protection Serial signal error protection Indoor fan motor error protection Installation data Refrigeran...

Page 26: ...n display RUN Green TIMER Yellow HI POWER Green 3D AUTO Green ECONO Blue Safety equipments Frost protection Serial signal error protection Indoor fan motor error protection Installation data Refrigera...

Page 27: ...ow Safety equipments Frost protection Serial signal error protection Indoor fan motor error protection Installation data Refrigerant piping size O D mm Liquid line 6 35 1 4 Gas line 9 52 3 8 Connectin...

Page 28: ...isplay RUN Green TIMER Yellow Safety equipments Frost protection Serial signal error protection Indoor fan motor error protection Installation data Refrigerant piping size O D mm Liquid line 6 35 1 4...

Page 29: ...reen TIMER Yellow Safety equipments Frost protection Serial signal error protection Indoor fan motor error protection Installation data Refrigerant piping size O D mm Liquid line 6 35 1 4 Gas line 9 5...

Page 30: ...isplay RUN Green TIMER Yellow Safety equipments Frost protection Serial signal error protection Indoor fan motor error protection Installation data Refrigerant piping size O D mm Liquid line 6 35 1 4...

Page 31: ...om temperature control Microcomputer thermostat Operation display RUN Green TIMER Yellow Safety equipments Frost protection Serial signal error protection Indoor fan motor error protection Installatio...

Page 32: ...om temperature control Microcomputer thermostat Operation display RUN Green TIMER Yellow Safety equipments Frost protection Serial signal error protection Indoor fan motor error protection Installatio...

Page 33: ...om temperature control Microcomputer thermostat Operation display RUN Green TIMER Yellow Safety equipments Frost protection Serial signal error protection Indoor fan motor error protection Installatio...

Page 34: ...ER Yellow HI POWER Green Air outlet selection Green ECONO Green Safety equipments Frost protection Serial signal error protection Indoor fan motor error protection Installation data Refrigerant piping...

Page 35: ...RUN Green TIMER Yellow HI POWER Green Air outlet selection Green ECONO Green Safety equipments Frost protection Serial signal error protection Indoor fan motor error protection Installation data Refri...

Page 36: ...RUN Green TIMER Yellow HI POWER Green Air outlet selection Green ECONO Green Safety equipments Frost protection Serial signal error protection Indoor fan motor error protection Installation data Refr...

Page 37: ...r error protection Installation data Refrigerant piping size O D mm Liquid line 6 35 1 4 Gas line 9 52 3 8 Connecting method Flare connection Insulation for piping Necessary Both sides independent Dra...

Page 38: ...tion Installation data Refrigerant piping size O D mm Liquid line 6 35 1 4 Gas line 9 52 3 8 Connecting method Flare connection Insulation for piping Necessary Both sides independent Drain hose Hose c...

Page 39: ...tion Installation data Refrigerant piping size O D mm Liquid line 6 35 1 4 Gas line 12 7 1 2 Connecting method Flare connection Insulation for piping Necessary Both sides independent Drain hose Hose c...

Page 40: ...on Noise heat Polyurethane form Remote control Wired RC E5 RC EX1A option Wireless RCN TC 24W ER option Room temperature control Thermostat by electronics Safety equipment Overload protection for fan...

Page 41: ...ol Wired RC E5 RC EX1A option Wireless RCN TC 24W ER option Room temperature control Thermostat by electronics Safety equipment Overload protection for fan motor Frost protection thermostat Installati...

Page 42: ...yurethane form Remote control Wired RC E5 RC EX1A option Wireless RCN TC 24W ER option Room temperature control Thermostat by electronics Safety equipment Overload protection for fan motor Frost prote...

Page 43: ...control Thermostat by electronics Safety equipment Internal thermostat for fan motor Frost protection thermostat Installation data Refrigerant piping size mm Liquid line 6 35 1 4 Gas line 12 7 1 2 Co...

Page 44: ...on thermostat Installation data Refrigerant piping size mm Liquid line I U 6 35 1 4 Gas line 12 7 1 2 Connecting method Flare piping Drain pump Built in drain pump Drain Hose connectable with VP25 Ins...

Page 45: ...pace for installation and service when viewing from the front Unit 15 Service space Service space Service space Terminal block Wired remote control Option Notes 1 The model name label is attached on t...

Page 46: ...ont Unit mm Notes 1 The model name label is attached on the right side of the unit 2 To connect the wired remote control the interface kit SC BIKN E is required 120 19 60 24 167 45 45 870 290 Outlet f...

Page 47: ...Symbol A 65 VP16 6 35 1 4 Flare Content 65 9 52 3 8 Flare Outlet for piping on both side G Note 1 The model name label is attached on the underside of the indoor unit 60 150 17 3 190 40 1 47 130 5 508...

Page 48: ...ng from the front Option Wired remote control Wireless remote control G Screw point fasten the indoor unit 5 860 238 15 60 60 100 60 55 157 2 76 3 85 3 22 7 185 25 5 30 5 198 804 65 65 45 585 30 5 103...

Page 49: ...ing D Hole for wiring E Suspension bolts M10 Symbol Content 6 35 1 4 Flare 9 52 3 8 Flare Drain piping C2 Gravity drainage VP25 I D 25 O D 32 Used with attached connector VP25 I D 25 O D 32 Used with...

Page 50: ...1 4 Flare 12 7 1 2 Flare Drain piping C2 Gravity drainage VP25 I D 25 O D 32 Used with attached connector VP25 I D 25 O D 32 Used with attached connector 25 x 2 Control box Connector Accessory Instal...

Page 51: ...for installation and service Option Make a space of 4000 or more between the units when installing more than one Ducting for air outlet 6 4 Holes for Hole tapping screws Hanger plate for suspension bo...

Page 52: ...side cutout Piping can be connected from 3 different direction Remove the cutout using side cutter or similar tool Obstacle Space for installation and service or more Air return grille Air supply Dra...

Page 53: ...ravity drainage 6 35 1 4 Flare H Inspection hole 450X450 170 124 170 tapping screws Holes for Space for installation and service or more or more or more or more Case 1 From side of unit Select either...

Page 54: ...e control a Wireless remote control Models SRK SRF SRR Typical example Model SKM 60 17 150 Unit mm 60 The wireiess remote controller in the following figure shows for the SRK ZJ S type 17 3 150 60 26...

Page 55: ...thickness 100 to 200m 0 5mm2 2 cores 0 75mm2 2 cores 1 25mm2 2 cores 2 0mm2 2 cores Under 300m Under 400m Under 600m Upper part Lower part Lower case Sheath Upper cace Board Wiring Upper Lower X Y She...

Page 56: ...e Adapted to RoHS directive Exterior appearance Munsell color Pearl white N8 5 near equivalent Model RC EX1A A PJZ000Z297 Installation space R C cable 0 3mm2 2 core Adapted to RoHS directive Exterior...

Page 57: ...Z RORU 0DUN t Th2 1 Th2 2 Th3 LM 1 LM 2 SM FM I HDW H FKDQJHU VHQVRU XPLGLW VHQVRU RQO DQ PRWRU 5RRP WHPS VHQVRU ODS PRWRU 7K 7K 7K LRGH VWDFN 6 XVH 0 7HUPLQDO EORFN 7 RXYHU PRWRU 0 60 DS LPLW VZLWFK...

Page 58: ...GER 2 N 3 Y G HD ONLY t o 2 t o R AMP 2 HEAT EXCHANGER 5 FM I SM I LM 1 LM 2 F Va Th I Th 2 Th 3 T DS RORU PDUNV 0HDQLQJ RI PDUNV OXH ODFN 5HG 5 KLWH HOORZ UHHQ RORU 0DUN HDW H FKDQJHU VHQVRU DQ PRWRU...

Page 59: ...3 15A U F Va DS CNG CNE R AMP WIRELESS DISPLAY BACK UP SW CNU CNM 5 M M Blue Black BK Red BL RD White WH Yellow Green YG Color Color marks Meaning of marks Mark Heat exchanger sensor Fan motor Room t...

Page 60: ...1 Th2 2 Th3 DM 1 DM 2 SM 1 SM 2 FM I DS t t TO OUTDOOR UNIT HEAT EXCHANGER 1 2 N 3 POWER WIRES SIGNAL WIRE 1 2 N 3 Power source 1 Phase AC220 240V 50Hz T AIR SELECTION SW Color marks Blue Black BK Re...

Page 61: ...L 250V F 2 F 3 15A L 250V Y BK RD CNS t t t 5 1 8 2 RD TB CNY Color marks Meaning of marks Blue Black BK Red BL RD White WH Yellow Y Color Mark Heat exchanger sensor Fan motor Room temp sensor Th1 Th2...

Page 62: ...ine between BL 1 Y GN Y GN Y GN 6 7 8 9 BK BK BK BK 10 BK 11 BK 12 BK 13 BK 14 BK 15 BK 16 BK 17 BK BK 18 BK 19 BK 20 BK 1 2 3 4 5 BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK BK 1 2 3...

Page 63: ...3 4 5 6 t 1 2 CNH BK Thi A t t t Thi R1 Thi R2 Thi R3 BK BK BK BK BK BK CNTA BL 1 2 YE GN 3 BL WH 1 3 CNW3 WH F2 3 15A SW2 SW6 SW5 SW7 LED 2 LED 3 CNZ FOR HA WH 12 BK BK Connecting line between indoor...

Page 64: ...rol PCB Power PCB RD YE t YE BK t BK 1 2 3 4 5 6 BK t BK 1 2 XR1 XR2 XR3 XR4 XR5 Remote operation Remote operation input volt free contact Prepare on site 1 2 3 4 5 6 12 SW2 SW6 SW5 SW7 LED E2 LED E3...

Page 65: ...ont side 1m Mike position 0 8m 1m Unit Mike position Front low points Noise Level Cooling 41 dB A Heating 41 dB A Cooling Heating 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 Mid octave ban...

Page 66: ...ion as mentioned below Distance from front side 1m Mike position 0 8m 1m Unit Mike position Front low points Mike position at highest noise level in position as mentioned belo Distance from front side...

Page 67: ...el dB Cooling Heating Cooling Heating Mike position at highest noise level in position as mentioned below Distance from front side 1m Mike position 0 8m 1m Unit Mike position Center low points 09 SRK...

Page 68: ...ling Heating Cooling Heating Model SRK35ZS S Mike position at highest noise level in position as mentioned below Distance from front side 1m Mike position 0 8m 1m Unit Mike position Center low points...

Page 69: ...oling Heating Condition ISO5151 T1 H1 Mike position at highest noise level in position as mentioned be Distance from front side 1m Mike position 0 8m 1m Unit Mike position Front low points 10 20 30 40...

Page 70: ...position at highest noise level in position as mentioned belo Distance from front side 1m Mike position 0 8m 1m Unit Mike position Front low points 10 20 30 40 50 60 70 10 20 30 40 50 60 70 Sound pre...

Page 71: ...ng 41 dB A Heating 41 dB A Cooling Heating Condition ISO T1 JIS C 9612 10 20 30 40 50 60 70 10 20 30 40 50 60 70 Sound pressure level dB Standard 2 10 5 Pa 63 125 250 500 1000 2000 4000 8000 Mid octav...

Page 72: ...6 dB A Heating 47 dB A Condition ISO T1 JIS C 9612 10 20 30 40 50 60 70 10 20 30 40 50 60 70 Sound pressure level dB Standard 2 10 5 Pa 63 125 250 500 1000 2000 4000 8000 Mid octave band frequency Hz...

Page 73: ...50 500 1000 2000 4000 8000 Mid octave band frequency Hz N50 N30 N40 N60 N70 N20 10 20 30 40 50 60 70 10 20 30 40 50 60 70 Sound pressure level dB Standard 2 10 5 Pa 63 125 250 500 1000 2000 4000 8000...

Page 74: ...octave band frequency Hz N50 N30 N40 N60 N70 N20 Noise Level Cooling 33 dB A Heating 34 dB A Cooling Heating Condition ISO5151 T1 JIS C 9612 Model SRR35ZM S Sound pressure level Sound pressure level...

Page 75: ...000 Mid octave band frequency Hz N50 N30 N40 N60 N70 N20 Noise Level Cooling 41 dB A Heating 43 dB A Cooling Heating Condition ISO5151 T1 JIS C 9612 Sound pressure level 1m Unit Supply duct Return duc...

Page 76: ...8000 Mid octave band frequency Hz N50 N30 N40 N60 N70 N20 Noise Level Cooling 41 dB A Heating 46 dB A Cooling Heating Condition ISO5151 T1 JIS C 9612 Sound pressure level Sound pressure level 1m Unit...

Page 77: ...z N50 N30 N40 N60 N70 N20 4 4way ceiling cassette type FDTC Model FDTC25VF 1 5m Mike position Center below unit Mike position Noise Level Cooling 41 dB A Heating 43 dB A Cooling Heating N50 N30 N40 N6...

Page 78: ...ing Heating N50 N30 N40 N60 N70 N20 10 20 30 40 50 60 70 63 125 250 500 1000 2000 4000 8000 10 20 30 40 50 60 70 Mid octave band frequency Hz Sound pressure level dB Standard 2 10 5 Pa Condition ISO T...

Page 79: ...70 63 125 250 500 1000 2000 4000 8000 10 20 30 40 50 60 70 Mid octave band frequency Hz Sound pressure level dB Standard 2 10 5 Pa Condition ISO T1 JIS B 8616 6 Duct connected Low Middle static pressu...

Page 80: ...re Pa 13 15 40 50 60 30 20 10 0 5 7 9 11 Air flow m3 min External static pressure Pa 13 15 40 50 60 30 20 10 0 5 7 9 11 Air flow m3 min External static pressure Pa 13 15 40 30 20 10 0 4 6 8 Air flow m...

Page 81: ...m i t o f E S P Setting 10Pa P Hi P Hi P Hi 0 10 20 30 40 50 60 70 80 90 100 110 11 12 13 14 15 Air flow m3 min External static pressure Pa 100Pa Max 90Pa 80Pa 70Pa 60Pa 50Pa 40Pa 30Pa 20Pa 10Pa Min...

Page 82: ...alkaline can occur Vehicles and ships Locations where cosmetic or special sprays are often used Locations with direct exposure of oil mist and steam such as kitchen and machine plant Locations where...

Page 83: ...ote Be careful that If it is not inserted securely water leakage may occur Adjustment of the installation board in the horizontal direction is to be conducted with four screws in a temporary tightened...

Page 84: ...that you can keep measurement B to a correct value Clutch type flare tool for R410A Conventional R22 flare tool 6 35 9 52 12 7 0 0 0 5 0 0 0 5 0 0 0 5 1 0 1 5 1 0 1 5 1 0 1 5 1 5 2 0 1 5 2 0 2 0 2 5...

Page 85: ...r conditioners are installed in the same room use this setting when the two air conditioners are not operated with one wireless remote control Set the wireless remote control and indoor unit INSTALLIN...

Page 86: ...bed pipes flare nuts and tools for R410A U sing existing parts for R22 or R407C can cause refrigerant circuit burst resulting in unit failure and personal injury B e sure to connect both liquid and ga...

Page 87: ...generate or accumulate D rain water can not be discharged properly T V set or radio receiver is placed within 1m H eight above sea level is more than 1000m It can cause performance degradation corrosi...

Page 88: ...gnal surely during operating the wireless remote control A place where it is not affected by the TV and radio etc Do not place where it is exposed to direct sunlight or near heat devices such as a sto...

Page 89: ...5 IEC57 CENELEC H05RN F 1 Earth wire is included Yellow Green 2 Arrange each wire length as shown below Make sure that each wire is stripped 10mm from the end Connecting cable Wire end 40mm or more Ea...

Page 90: ...e Avoid the following drain piping Higher than specified Wavy The drain hose tip is in water The gap to the ground is 5 cm or less The drain hose tip is in the gutter Odor from the gutter Pour water t...

Page 91: ...ion prevention 1 D ress the connecting pipes both liquid and gas pipes with insulation to prevent it from heating and dew condensation U se the heat insulating material which can withstand 120 C or hi...

Page 92: ...the front panel and fix 4 upper latches 2 Secure the front panel with the 2 screws 3 Install the bottom panel the air inlet panel and the air filters Front panel Bottom panel Screw in the cap Screw L...

Page 93: ...button continuously for at least 5 seconds Then operation will start For the detail of pump down refer to the instal lation manual of outdoor unit Unit ON OFF button 16 INSTALLATION CHECK AND TEST RUN...

Page 94: ...al injury B e sure to use the prescribed pipes flare nuts and tools for R410A U sing existing parts for R22 or R407C can cause refrigerant circuit burst resulting in unit failure and personal injury B...

Page 95: ...w melting agent and acid sulfurous acid etc which can harm the unit will generate or accumulate D rain water can not be discharged properly T V set or radio receiver is placed within 1m H eight above...

Page 96: ...air conditioner can receive the signal surely during operating the wireless remote control A place where it is not affected by the TV and radio etc Do not place where it is exposed to direct sunlight...

Page 97: ...5 IEC57 CENELEC H05RN F 1 Earth wire is included Yellow Green 2 Arrange each wire length as shown below Make sure that each wire is stripped 10mm from the end Connecting cable Wire end 40mm or more Ea...

Page 98: ...e gap to the ground is 5 cm or less The drain hose tip is in the gutter Odor from the gutter Pour water to the drain pan located under the heat exchanger and ensure that the water is discharged outdoo...

Page 99: ...ng pipes both liquid and gas pipes with insulation to prevent it from heating and dew condensation U se the heat insulating material which can withstand 120 C or higher temperature Make sure that insu...

Page 100: ...t can be operated with only one wireless remote control Setting one wireless remote control 1 Slide and take out the cover and batteries 2 Cut the switching line next to the battery with wire cutters...

Page 101: ...alves are fully open No gas leaks from the joints of the service valves Indoor and outdoor side pipe joints have been insulated Hole on the wall is completely sealed with putty Drain hose and cap are...

Page 102: ...of multiple units installation Locations where strong air blows against the air outlet of outdoor unit Locations where something located above the unit could fall It can cause remarkable decrease in p...

Page 103: ...at location that meets the following conditions after getting approval from the customer Wireless remote control In case of piping in the right rear direction When drilling the wall that contains a me...

Page 104: ...ver the exterior portion with outer tape and shape the piping so it will match the contours of the route that the piping to take Also fix the wiring and pipings to the wall with clamps ELECTRICAL WIRI...

Page 105: ...to the outdoor unit when the pipes are removed from the unit Uncover the wireless remote control and mount the batteries R03 AAA Micro 2 pieces in the body regularly Fit the poles with the indication...

Page 106: ...e status due to register of the wind for the high rise apartment etc Be sure to perform air tightness test by pressurizing with nitrogen gas after completed refrigerant piping work If the density of r...

Page 107: ...ributed A firm location that may sustain the weight of the unit and do not cause the unit or the ceiling to vibrate A place where there will be enough space for servicing Where space mentioned below c...

Page 108: ...pipe after installation Insulating material to be removed Joint Rubber stopper to be removed Standard hard polyvinyl chloride pipe Connecting port of bottom drain pipes Outside diameter 25mm Connectin...

Page 109: ...ry 6 Pull out the cover and mount the batteries R03 AAA Micro 2 pieces in the body regularly Fit the poles with the indication marks without fail Do not use new and old batteries together Disconnect W...

Page 110: ...the earth leakage breaker is not installed it can cause electric shocks Use the circuit breaker of correct capacity Circuit breaker should be the one that disconnect all poles under over current Usin...

Page 111: ...resistant brace to the bolt In case the unit is hanged directly from the slab and is installed on the ceiling plane which has enough strength When suspension bolt length is over 1000mm apply the eart...

Page 112: ...the pipe as close place to the unit as possible when connecting the drain pipe Do not set up air vent Supporting metal No bump No trap Not touching the water Trapped air will generate noises Air vent...

Page 113: ...nit PCB is turned ON the Connector CNB is disconnected and then the power supply 220 240VAC on the terminal block and or and is turned ON Make sure to turn OFF SW7 1 and reconnect the Connector CNB af...

Page 114: ...113 16 SCM T 199 source PJA012D783...

Page 115: ...5 7 5 7 Note This function is not able to be set with wireless remote controls or simple remote control RCH H3 5 7 5 7 For setting the swing range of other louvers return to 1 and proceed same proced...

Page 116: ...ught in the machine to get burned or electric shock Shut off the power before electrical wiring work It could cause electric shock unit failure and improper running Perform earth wiring surely Do not...

Page 117: ...is no obstruction of airflow on both air return grille and air supply port Areas where fire alarm will not be accidentally activated by the air conditioner Areas where the supply air does not short ci...

Page 118: ...to make the up down bending and trap in the mid way while assum ing that the drain pipes is downhill more than 1 100 Never set up air vent 5 Insulate the drain pipe Insulate the drain hose clamp with...

Page 119: ...is fixed at that position auto swing does not funtion ATTENTION If you press RESET button during settings the display will return to previous display If you press button during settings the mode will...

Page 120: ...nerated or accumulated or volatile flammable substances are handled It could cause the corrosion of heat exchanger breakage of plastic parts etc And inflammable gas could cause fire Secure a space for...

Page 121: ...to unit falling Space for installation and service Make installation altitude over 2 5m Indoor Unit Select either of two cases to keep space for installation and services Notes a There must not be obs...

Page 122: ...to t Caution Refrigerating machine is because even if the force on the threads an by the stress corrosion Refrigerating machine Be sure to use new pipes for the refrigerant pipes Use the flare nut at...

Page 123: ...g machine oil may be applied to the internal surface of flare only Descending slope greater than 1 100 As wide as possible about100mm Supporting metal Descending slope greater than 1 100 Please confir...

Page 124: ...ecurely and handled with care not to drop when it is necessary toreplace Notes 2 For the maintenance space refer to page 120 i Remove the control box and the side panel and remove the screws marked in...

Page 125: ...at exchanger Heat exchanger Liquid line Gas line 6 35 6 35 9 52 9 52 Strainer Humidity sensor 1 Compressor 4 way valve Service valve Liquid Capillary tube Capillary tube Electric expansion valve EEVA...

Page 126: ...ccumulator Sensor Tho S Service valve Liquid Electronic expansion valve Compressor 4 way valve Discharge Suction Sensor Tho R Heat exchanger Cooling cycle Heating cycle 9 52 or 12 7 9 52 or 12 7 9 52...

Page 127: ...ltage Within 15 of rated voltage Within 10 of rated voltage 3 min or more 10 min or more from stop to stop or from start to start Max 25m Max 15m Max 15m Outdoor air temperature Upper lower limits Num...

Page 128: ...Indoor unit combination Heating capacity kW Power consumption W Standard current A Indoor unit capacity kW Total capacity kW Min Standard Max 220V 230V 240V A B Min Standard Max 1 unit 20 3 0 1 3 3 0...

Page 129: ...0 900 1070 4 4 4 2 4 0 25 3 4 1 3 3 4 4 0 520 1070 1210 5 2 5 0 4 8 35 4 5 1 3 4 5 4 8 520 1340 1450 6 5 6 3 6 0 2 units 20 20 2 25 2 25 2 0 4 5 6 1 550 930 1700 4 5 4 3 4 2 20 25 2 36 2 94 2 0 5 3 6...

Page 130: ...25 25 3 00 3 00 2 0 6 0 6 3 550 1600 1900 7 3 7 0 6 7 25 35 2 50 3 35 2 0 6 0 6 3 550 1600 1900 7 3 7 0 6 7 35 35 3 00 3 00 2 0 6 0 6 3 550 1600 1900 7 3 7 0 6 7 Heating Indoor unit combination Coolin...

Page 131: ...7 1 6 8 6 5 35 35 3 00 3 00 2 0 6 0 6 3 550 1550 1900 7 1 6 8 6 5 Heating c Indoor unit except SRK ZMX S and SKM ZSP S models Cooling Heating Indoor unit combination Cooling capacity kW Power consump...

Page 132: ...6 8 25 25 35 2 06 2 06 2 88 3 0 7 0 7 5 600 1690 2580 7 8 7 5 7 2 Heating 3 Model SCM50ZS S a Indoor unit SRK ZMX S models only Cooling Heating Indoor unit combination Cooling capacity kW Power consum...

Page 133: ...7 6 7 3 7 0 25 25 35 2 06 2 06 2 88 3 0 7 0 7 3 600 1750 2580 8 1 7 7 7 4 Heating b Indoor unit SKM ZSP S models only Cooling Heating Indoor unit combination Cooling capacity kW Power consumption W S...

Page 134: ...6 9 25 25 35 2 06 2 06 2 88 3 0 7 0 7 3 600 1730 2580 8 0 7 7 7 3 Heating Indoor unit combination Cooling capacity kW Power consumption W Standard current A Indoor unit capacity kW Total capacity kW...

Page 135: ...y piping length between the indoor and outdoor units 3 Correction relative to frosting on outdoor heat exchanger during heating In additions to the foregoing corrections 1 2 the heating capacity needs...

Page 136: ...0 5 sec 0 5 sec Operation mode invalid OPERATION MODE select button ALLERGEN CLEAR button ON OFF luminous button TEMPERATURE button AIR FLOW UP DOWN button TIME SET UP switch SLEEP button CLEAN switc...

Page 137: ...ops due to the HOT KEEP and CLEAN operation ON OFF 1 5 sec 0 5 sec HOT KEEP 3 sec 1 sec ON OFF CLEAN operation ON OFF 0 5 sec 0 5 sec Operation mode invalid OPERATION MODE select button ON OFF luminou...

Page 138: ...OT KEEP and CLEAN operation 1 Unit ON OFF button When the wireless remote control batteries become weak or if the wireless remote control is lost or malfunctioning this button may be used to turn the...

Page 139: ...trol Since the signal is sent in about 6 seconds after the ACL switch is pressed point the wireless remote control at the indoor unit for some time iii Check that the reception buzzer sound Pip is emi...

Page 140: ...air temperature Model A SRR25 35 50ZM S 17 SRF25 35 50ZMX S 7 SRK20 25 35 50ZMX S 10 5 High power operation Pressing the HI POWER ECONOMY button intensifies the operating power and initiates powerful...

Page 141: ...ioner is OFF d The setting temperature is adjusted according to the following table Temperature adjustment Cooling Heating Mode Item at the start of operation one hour after the start of operation two...

Page 142: ...n on the wireless remote control a Flap Each time when you press the AIR FLOW UP DOWN button the mode changes as follows COOL DRY FAN Wireless remote control display HEAT Approx 60 Approx 44 Approx 50...

Page 143: ...to reaching the setting point And then the air outlet will change to both outlets in order to spread comfort air to every corner ii HEAT operation 1 In case both lower and upper outlets operation with...

Page 144: ...low direction contorol 2 C Setting temp Room temp 5 C 2 C Room temp Setting temp 5 C Room temp Setting temp 5 C Setting temp Room temp 5 C The control in 4 continues Control returns to the control in...

Page 145: ...end installation Center installation Right end installation iv Press the ON OFF button The air conditioner s installation location is set Press within 60 seconds of setting the installation location...

Page 146: ...t checks the float switch If it is normal the unit is stopped under the normal mode or if there is any anomalous condition displayed by the flashing of display lights and the drain motor is turned ON...

Page 147: ...n and prohibition by releasing the jumper wire J3 on the indoor PCB When the jumper wire J3 is short circuited Normal operation is enable when shipping When CnT input is set to ON the operation starts...

Page 148: ...output connector CnT is located on the circuit board of the interface kit Operation output Power to engage DC12V relay provided by the customer is outputted during operation Heating output Power to e...

Page 149: ...r this control is not executed 20 Frost prevention control a Operating conditions b Detail of anti frost operation c Reset condition Indoor heat exchanger temperature C 2 5 8 Operation mode Item Prote...

Page 150: ...ndition Tho A Tho A Fan speed Model Upper limit SRK20 35ZMX S 8th SRK50ZMX S SRF25 50ZMX S SRR25 50ZM S 9th 12 Current cut a Purpose b Detail of operation 13 Outdoor unit failure 23 Indoor fan motor p...

Page 151: ...witch This switch selects the CLEAN operation display brightness adjustment and PRESET operation ON TIMER button This button selects ON TIMER operation TIMER button This button is used for setting the...

Page 152: ...less remote control Set the wireless remote control and indoor unit a Setting the wireless remote control i Pull out the cover and take out batteries ii Disconnect the switching line next to the batte...

Page 153: ...nuously The wireless remote control displays HIGH POWER mark and the FAN SPEED display disappears a During the HIGH POWER operation the room temperature is not controlled When it causes an excessive c...

Page 154: ...a soft operation with the power suppressed in order to avoid an excessive cooling or heating The unit operate 1 5 higher than the setting temperature during cooling or 2 5 lower than that during heati...

Page 155: ...87D 9 3D auto operation a i ii Cooling Air flow selection Operation mode AUTO HI MED LO Heating Room temp Setting temp 5 C Room temp Setting temp 5 C Setting temp Room temp 5 C Setting temp Room temp...

Page 156: ...tion mode Room temp Setting temp 2 C Setting temp Room temp 2 C Heating Cooling Air flow direction contorol 2 C Setting temp Room temp 5 C 2 C Room temp Setting temp 5 C Room temp Setting temp 5 C Set...

Page 157: ...1 2 Remote control display COOL HEAT Operation COOL HEAT Selected mode Heating Cooling Remote control display HEAT COOL Different mode is only fan operation Operation FAN 1 FAN Note 1 If the display...

Page 158: ...ately c When the unit is started again within one hour after the stop of automatic operation or when the automatic operation is selected during heating cooling or dehumidifying operation the unit is o...

Page 159: ...s released Permission Prohibition mode When CnT input is set to ON the operation mode is changed to permission and if input is set to OFF the operation is prohibited When the jumper wire J1 is short c...

Page 160: ...selected in the wired remote control s indoor unit settings Input signal to CnT becomes valid at OFF ON only and the motion of air conditioner ON OFF is inverted CnT input Unit Case A Unit Case B OFF...

Page 161: ...me lower than the release temperature Item Room temperature Th1 Release temperature Start temperature Th1 24 C 48 5 C 62 C 24 C Th1 27 C 47 5 C 61 C 27 C Th1 46 5 C 60 C 22 Heating overload protective...

Page 162: ...CANCEL button Unit display section Name of each part and its function This button can be used for turning on off the unit when wireless remote control is not available Wireless remote control signal r...

Page 163: ...with your dealer if this function needs to be switched off 2 When power failure ocurrs the timer setting is cancelled Once power is resumed reset the timer 3 If the jumper wire J1 AUTO RESTART is cut...

Page 164: ...When the HI POWER ECONOMY button is pressed again When the operation mode is changed When it has been 15 minutes since HIGH POWER operation has started e Not operable while the air conditioner is OFF...

Page 165: ...continuously S In HEAT operation S In COOL DRY operation Approx 35 Approx 65 Approx 20 Approx 59 c Memory flap When you press the AIR FLOW UP DOWN button once while the flap is operating it stops swin...

Page 166: ...d then begins in the automatic operation Heating Dehumidifying Cooling Indoor air temperature C Outdoor air temperature C A b The unit checks the temperature every hour after the start of operation an...

Page 167: ...ion mode 8 2 5 i ii 13 Heating high pressure control a Starting condition When the indoor heat exchanger temperature Th2 has become higher than the start temperature for 1 minute continuously b Conten...

Page 168: ...ontrol CHECK button This button is used at servicing TEST button This button is used during test operation Weekly timer display Displays the settings of the weekly timer Operation setting display area...

Page 169: ...ent time and the name of R C Change set temp button Displays the temperature which is set currently Tap this button to change the set temperature Change operation mode button Displays the operation mo...

Page 170: ...once again it stops operating Used to swing the louver Every time this button is pressed displays switch as below Sets room temperature by pressing or button Sets time when setting the time Used to ca...

Page 171: ...ting Louver auto swing stop However the stop position 4 position is cancelled so that it returns to Position 1 Remote control function items which have been set with the remote control function settin...

Page 172: ...nu screen 1 Menu screen 3 Service password input Tap the Menu button on the TOP screen Main menu screen is displayed Tap the Service Maintenance on the menu screen Display the service password input s...

Page 173: ...r failure compensation are as follows Note 1 Items f and g are memorized regardless whether the power failure compensation is effective or not while the setting of silent mode is cancelled regardless...

Page 174: ...rature shown at right 59 56 Heating operation stopped cooling Heating OK Indoor heat exchanger temperature C b The following automatic controls are performed other than a above i Cooling or heating op...

Page 175: ...ing Fan Operation Functional item Thermostat ON Thermostat ON Thermostat OFF Thermostat OFF Hot start Defrost Compressor 4 way valve Outdoor unit fan Indoor unit fan Drain pump 3 2 2 Thermostat ON The...

Page 176: ...ekly timer Set the ON or OFF timer for a week Up to 8 patterns can be set for a day The day off setting is provided for holidays and non business days Note 1 It is necessary to set the clock to use th...

Page 177: ...Thi R1 or R2 whichever higher detects 35 C or higher the fan operates with the set airflow volume c If the fan control at heating thermostat OFF is set at the Set airflow volume from the remote contro...

Page 178: ...conditioner is operating SWING is displayed for 3 seconds and then the swing louver moves up and down continuously 2 To fix the swing louver at a position press one time the LOUVER button while the sw...

Page 179: ...e indoor unit fan motor stops 2 Indoor fan OFF is fixed for 5 minutes After the 5 minutes the indoor fan is operated at ULo for 2 minutes In the meantime the louver is controlled at level 3 After oper...

Page 180: ...indoor unit of which the thermostat has been turned OFF is turned OFF The same occurs also when the remote control sensor is effective 10 Filter sign As the operation time Total ON time of ON OFF swi...

Page 181: ...the drain pump forcibly 3 Turning the drain detection switch OFF releases the forced drain pump ON condition Normal state 1 2 Normal state Drain detection switch ON Stop 1 Indoor unit operation mode...

Page 182: ...return air detection temperature detected with Thi A is 23 C or higher and the indoor heat exchanger temperature detected with Thi R detects the compressor frequency drop start temperature A C 1 C of...

Page 183: ...e control Pressing AIR CON No button on the remote control displays the indoor unit address If button is pressed at the next it is displayed orderly starting from the unit of youngest No iv In case of...

Page 184: ...come independent functions each other 4 In case of CnT Number CnTA Number the CnT Number and the CnTA Number become competing functions each other 5 In case of CnT Number CnTA Number the function of C...

Page 185: ...nal control set is changed from Individual Factory default to For all units all units connected in one wired remote control system can be controlled by external operation input Individual operation Fa...

Page 186: ...ation permission start stop operation of the unit from the wired remote control becomes available When card key switch is OFF CnT 6 or CnTA OFF Operation prohibition the unit stops operation in conjun...

Page 187: ...the indoor unit function If the external input is changed OPEN CLOSE operation modes are inverted Cooling Heating or Heating Cooling Operation Operation Operation Stop Stop Stop Stop Operation prohibi...

Page 188: ...n the thermostat is likely to turn OFF earlier because the unit is installed at the ceiling where warm air tends to accumulate the setting can be changed with the wired remote control indoor unit func...

Page 189: ...C unit goes thermo OFF 33 Auto fan speed control RC EX1A only In order to reach the room temperature to the set temperature as quickly as possible the airflow rate is increased when the set temperatur...

Page 190: ...t SKM ZSP S models only Model Capacity SCM40ZS S SCM45ZS S SCM50ZS S SCM45ZS S 1 3 6 3 kW SCM50ZS S 1 4 7 3kW Model Capacity SCM40ZS S 1 3 6 1 kW Functional components Operation Compressor speed Indoo...

Page 191: ...tes Hot keep operation 20 20 15 10 5 0 5 10 15 10 5 0 Outdoor air temperature Outdoor heat exchanger temperature Defrost operation start Defrost operation start temperature a Capacity control i Indoor...

Page 192: ...pressor speed control 7 5 3 Protective control function 1 Cooling overload protective control a Operating conditions Item SCM40 45 50ZS S Outdoor air temperature Lower limit speed Model Outdoor air te...

Page 193: ...compressor speed is set to 35 or 45 rps and even if the speed becomes lower than 35 or 45 rps the speed is kept to 35 or 45 rps However when the thermostat OFF the speed is reduced to 0 rps ii The up...

Page 194: ...35 60 55 55 ON2 65 65 ON3 Unit rps Indoor unit 1 unit Indoor unit 2 units or more Indoor unit 1 unit Indoor unit 2 units 8 6 4 Outdoor air temperature C 6 ON2 ON1 12 10 ON3 8 10 11 13 16 17 OFF Upper...

Page 195: ...have satisfied the following condition even on one unit b Contents of control i Stop the compressor and delay the start and then restarts ii Compressor stops by the abnormal stop when the compressor s...

Page 196: ...Heating 10 0 12 0 10 0 10 0 7 5 7 5 Unit A 14 Discharge pipe sensor disconnection protection control a When the compressor speed is other than 0 rps i Tho D 10 Tho D 0 8 C and Tho D 10 Tho A 10 5 C Th...

Page 197: ...ess 5th speed 4th speed Less than 30 48 or more 6th speed More than 30 but 48 or less 5th speed 4th speed 16 Serial signal transmission error protection a Purpose b Detail of operation 17 Rotor lock 1...

Page 198: ...C for 30 seconds continuously while the compressor is operating ii Contents of control The outdoor fan is stepped up by 3 speed Upper limit 6th speed iii Reset condition When the compressor is turned...

Page 199: ...Troubleshooting procedure If the air conditioner does not run at all Important YES YES YES NO NO NO NO YES AC source source satisfied 1 Cautions 2 Items to check before troubleshooting 3 Troubleshooti...

Page 200: ...199 16 SCM T 199 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 200 201 207 201 207...

Page 201: ...tarts The air conditioner stops Defective compressor Open phase on compressor Defective outdoor PCB Service valve is closed Refrigerant is insuf Outdoor sub PCB communication error Outdoor sub PCB fau...

Page 202: ...t Data are recorded for up to 5 previous occurrences Data which are older than the 5th previous occurrence are erased In addition data on the temperature of each sensor room temperature indoor heat ex...

Page 203: ...n speed mode 21 C 22 C 23 C 24 C 25 C 1 time previous previous time 2 times previous 3 times previous 4 times previous 5 times previous Only for indoor heat exchanger sensor 2 Indicates the number of...

Page 204: ...the stop stop code 2 times previous when the air conditioner was stopped by protective stop control Displays the reason for the stop stop code 3 times previous when the air conditioner was stopped by...

Page 205: ...ror content Cause Occurrence conditions Error display Auto recovery OFF 3 time flash 5 time flash 6 time flash 8 time flash 4 time flash 2 times 2 times 3 times 3 times 3 times When high pressure cont...

Page 206: ...EAT TIMER light 1 s digit Display pattern when in service mode Fan speed mode when there is an abnormal stop 2 time flash 3 time flash 4 time flash AUTO HI MED LO 5 time flash ULO 6 time flash 7 time...

Page 207: ...84 94 55 45 35 25 15 5 5 15 25 35 45 55 65 75 85 95 56 46 36 26 16 6 6 16 26 36 46 56 66 76 86 96 57 47 37 27 17 7 7 17 27 37 47 57 67 77 87 97 58 48 38 28 18 8 8 18 28 38 48 58 68 78 88 98 59 49 39 2...

Page 208: ...126 146 48 28 8 8 28 48 68 88 108 128 148 50 30 10 10 30 50 70 90 110 130 150 52 32 12 12 32 52 72 92 112 132 54 34 14 14 34 54 74 94 114 134 56 36 16 16 36 56 76 96 116 136 58 38 18 18 38 58 78 98 1...

Page 209: ...208 16 SCM T 199 09 SRK DB 087D Service data record form 202 Operation mode Fan speed mode Wireless r Wireless r Wireless r Wireless r Wireless r wireless Wireless r Refer...

Page 210: ...0 Discharge pipe and power transistor sensor temperature characteristics Indoor fan motor error Broken sensor wire connector poor connection 0 0 20 40 60 80 100 120 135 20 40 60 80 100 120 140 160 180...

Page 211: ...0 C sub main main main Limit switch anomaly SRK20 25 35 50ZMX S only Defective limit switch defective indoor control PCB Defective air inlet panel set Is the air inlet panel set correctly Are limit sw...

Page 212: ...SCM T 199 Over heat of compressor Gas shortage defective discharge pipe sensor Error of signal transmission Wiring error including power cable defective indoor outdoor PCB 209 main indoor indoor outd...

Page 213: ...outdoor PCB Power source reset Is it normalized Malfunction by temporary noise Replace fan motor If the error persists after replacing the fan motor replace the outdoor main PCB the fan motor and out...

Page 214: ...ain motor driver Is the drain piping clogged or at the wrong gradient Drain motor is defective Inspect wiring Drain abnormality SRR only Drain piping defective pump defect float switch indoor PCB Serv...

Page 215: ...ks and oscillating between DC 0 and 20V Inspect power source for outdoor unit Replace fuse Replace indoor PCB Is the fuse burnt out 3 15 A YES YES YES NO NO NO b Indoor unit fan motor check procedure...

Page 216: ...YES YES YES NO NO NO b Indoor fan motor check procedure i Indoor PCB output check ii Fan motor resistance check FMI DC15V Indoor PCB DC280V DC several V 4 6V CNU GND Blue Yellow White Black Red Senso...

Page 217: ...Check then the operation Faulty part other than fan motor YES Fan motor is faulty YES YES YES NO NO NO Replace the faulty part and the fuse Test run then the unit for checking Is there any damage on...

Page 218: ...A BK WH WH S 1 CNMAIN SIN RIN BK WH SO RO 250V 15A FUSE RD C 1 CN20V 3 2 G1 Y G G2 Y G CNEEV1 CNA CNB TB1 N L EEV B Y G WH BK UNIT A UNIT B M M Power source 1 Phase AC220 240V 50Hz WH RD PCB 2 SUB PC...

Page 219: ...G CNEEV1 CNEEV3 CNTH TB2 CNA CNB CNC TB1 N L EEV B EEV C Y G WH BK M M M WH RD BL PCB 2 SUB PCB 1 MAIN 20S HEATER WH RD CNHEAT 250V 20A 3 2 1 BK WH RD 3 2 1 3 2 1 BK WH BR BK WH BL t 2 Tho S Color ma...

Page 220: ...0V DC15V Outdoor main PCB GND DC280V Red Black 20 M or higher Measuring point Resistance when normal Red Blue 20 M or higher White Black 20 k or higher 20 k or higher Brown Blue CNFAN Red Black White...

Page 221: ...ature thermistor input circuit Replacement of PCB 1 time flash Keeps flashing Stays OFF Indoor return air temperature thermistor Defective indoor return air temperature thermistor defective element br...

Page 222: ...re sensor 264 Outdoor main PCB Defective outdoor main PCB Defective temperature sensor input circuit Replacement of PCB Stays OFF Keeps flashing 1 time flash Outdoor main PCB compressor Current cut An...

Page 223: ...one remote control Whenever excessively connected indoor units is detected after power ON Return air temperature thermistor anomaly 50 C or lower is detected for 5 seconds continuously within 60 minut...

Page 224: ...ontrol and fuse Note 1 With regard to parts of high voltage circuits and refrigeration cycle judge it according to ordinary inspection methods b Instruction of how to replace indoor control PCB Read t...

Page 225: ...wirings d Control PCB Parts mounting are different by the kind of PCB Part number SW2 Blue Address setting SW7 Function setting CNT Blue External switch CNJ White Louver motor CNN Yellow Thermistor H...

Page 226: ...to the PCB Wiring connector color should match with the color of connector of the PCB Note 2 vi Let the wiring red and blue pass beneath the yellow green wiring and bind together with band vii Screw b...

Page 227: ...to the PCB Match the wiring connector to the connector color on the PCB and connect it d Control PCB Parts mounting are different by the kind of PCB Item Switch Address SW2 OFF ON Content of control P...

Page 228: ...d to the connector are removed iii Fix the board such that it will not pinch any of the wires iv Reconnect the wirings to the PCB Wiring connector color should match with the color of connector of the...

Page 229: ...id Normal SW8 1 OFF SW8 2 OFF SW8 3 OFF SW8 4 OFF Keep OFF Reserved Reserved Reserved Keep OFF Keep OFF Keep OFF Reserved Model selection As per model See table 1 Remarks Address No setting at plural...

Page 230: ...ferent indoor unit press the button which allows you to go back to the indoor unit selection screen Pressing the button will stop displaying data Pressing the RESET button during remote control unit o...

Page 231: ...e display returns to the last precious screen Note 1 When two remote controls are used to control indoor units the check of anomaly operation data can be made on the master remote control only It cann...

Page 232: ...tively b Operation for judgment i Power ON and start check operation on cooling or heating mode ii Check ON OFF status of 6 LED s on the checker iii Judge the PCB by ON OFF status of 6 LED s on the ch...

Page 233: ...maly 250 E8 Heating overload operation 251 E9 Drain trouble FDTC and FDUM only 252 E10 Excessive number of connected indoor units more than 17 units by controlling with one remote control 253 E11 Addr...

Page 234: ...pective parts NO YES YES NO YES YES YES NO NO Is the compressor operating NO YES NO Note 1 Outdoor 35 C Indoor 27 C 1 WAIT It is normal This unit is designed to start in the soft start mode by detecti...

Page 235: ...ssor operating NO YES NO Note 1 Outdoor 7 C Indoor 20 C 1 WAIT It is normal This unit is designed to start in the soft start mode by detecting the under dome temperature of compressor when it restart...

Page 236: ...M because of refrigerant migrated in the compressor When the earth breaker is activated at lower insulation resistance check the following points 6 hours after power ON check if the insulation resist...

Page 237: ...ransmitting to wall and etc by fixing pipes on the wall or wrapping rubber cushion around the pipe which goes through the hole in the wall or applying other appropriate means Strength of ceiling wall...

Page 238: ...particularly during cooling or defrosting in the heating mode It is normal The noise vibration occurs when the refrigerant starts or stops flowing It is normal When the defrost operation starts or st...

Page 239: ...essary to recover refrigerant vacuum dry and recharge refrigerant Since there could be many causes of noise vibration the above do not cover all In such case check the conditions when where how the no...

Page 240: ...M louver motor Is the louver operable with the remote control YES NO Does the louver operate at the power on YES NO YES NO Operate after waiting for more than 1 minute Repair wiring Defective indoor c...

Page 241: ...erminal block of outdoor unit YES YES NO 2 1 Note 2 for GND Note 1 FDE FDUM F1 F2 Is DC5Vdetected between of CNW1 FDTC CNW2 NO YES YES Is JX1 open YES Defective outdoor sub PCB Noise filter Misconnect...

Page 242: ...NO Is DC15V or higher detected between X Y of indoor unit terminal block YES YES YES NO Is DC180V between of CNW1 FDTC CNW2 YES NO NO Correct Replace wires Replace remote control Defective indoor powe...

Page 243: ...Power source reset NO YES YES NO NO NO NO NO YES YES YES Set one remote control for Master and the other for Slave Set SW1 on remote control PCB at Master Set address again SW2 on indoor control PCB...

Page 244: ...d Same as above 4 Presumable cause Improper setting Surrounding environment Defective remote control communication circuit Faulty indoor control or power PCB Faulty outdoor sub PCB Note If any error i...

Page 245: ...WAIT YES YES YES YES To next page Normal Defective outdoor sub PCB Replace Defective indoor control PCB Replace Replace indoor control PCB Correct connection wires between indoor and outdoor units Def...

Page 246: ...e power source fuse Diagnosis Countermeasure Replace the outdoor sub PCB YES YES NO YES Replace the outdoor main PCB Replace the reactor Isn t there a short circuit between phases of outdoor sub PCB A...

Page 247: ...e control side after disconnecting the remote control Are wires connected properly between the indoor and the outdoor units Is approx DC20V detected between on the outdoor unit terminal block NO Is ap...

Page 248: ...ion by noise Check peripheral environment Defective indoor control PCB Replace Defective remote control Replace 2 Error detection method When normal communication between the remote control and the in...

Page 249: ...ource reset Note 2 Check for faulty connection or breakage of signal wires between indoor outdoor units YES NO YES NO Repair signal wires Repair signal wires Defective outdoor sub PCB Defective networ...

Page 250: ...fective indoor control PCB Replace Defective indoor unit heat exchanger temperature thermistor input circuit 2 Error detection method Anomalously low temperature or high temperature resistance is dete...

Page 251: ...thermistor Replace Defective indoor control PCB Replace Defective return air temperature thermistor input circuit 2 Error detection method Anomalously low temperature or high temperature resistance is...

Page 252: ...ay E6 YES NO YES NO Error stop Reset Indoor heat exchanger temperature C 56 63 For the characteristics of indoor heat exchanger temperature refer to E6 Wash Defective indoor heat exchanger temperature...

Page 253: ...t switch Defective indoor control PCB Replace Defective indoor control PCB Replace Check optional equipment Correct setting to Humidifier drain motor interlock Defective indoor power PCB Replace FDUM...

Page 254: ...asure Aren t more than 17 indoor units connected to one remote control NO YES Defective remote control Replace Reduce to 16 or less units 2 Error detection method When it detects more than 17 of indoo...

Page 255: ...Return address No to IU using or button 2 Error detection method IU address has been set using the Master IU address set function of remote control 3 Condition of error displayed Same as above 4 Presu...

Page 256: ...er source Note 1 Set dip switches SW5 1 and SW5 2 as shown in the following table Factory default setting Master Master Slave a Slave b SW5 1 OFF OFF ON SW5 2 OFF ON OFF Dip switch Indoor unit YES NO...

Page 257: ...PCB Replace fan motor If the error persists after replacing the fan motor replace the indoor control PCB Malfunction by temporary noise 2 Error detection method Detected by rotation speed of indoor f...

Page 258: ...efective indoor control PCB Defective SW7 Replace Turn SW7 1 on the indoor control PCB OFF and reset the power 2 Error detection method After indoor operation check when the communication between indo...

Page 259: ...l Replace the fan motor Check power source voltage Replace faulty fan motor and power PCB Replace fan motor If the error persists after replacing the fan motor replace the indoor control PCB Malfuncti...

Page 260: ...er 3 minutes delay the compressor starts again automatically but if this error occurs again within 60 minutes after the initial detection 4 Presumable cause Faulty connection of remote control tempera...

Page 261: ...re any fouling or clogging on heater exchanger Control operation check Defective outdoor main PCB Replace Excessive refrigerant amount Recharge refrigerant by weighing proper amount on a scale 2 Error...

Page 262: ...ufficient refrigerant amount Recharge refrigerant by weighing proper amount on a scale Control operation check Defective outdoor main PCB Replace Check unit side Isn t filter clogged Are adequate indo...

Page 263: ...mperature sensor Replace Defective outdoor main PCB Replace Defective outdoor heat exchanger temperature sensor input circuit 2 Error detection method Detection of anomalously low temperature resistan...

Page 264: ...N the compressor stops After 3 minutes delay the compressor starts again automatically but if this anomalous temperature is detected 3 times within 40 minutes When 55 C or lower is detected for within...

Page 265: ...ective discharge pipe temperature sensor Replace Defective outdoor main PCB Replace Defective temperature sensor input circuit 2 Error detection method Detection of anomalously low temperature resista...

Page 266: ...ce Open the valves Check refrigerant amount and refregerant circuit In case of transitional increase of high pressure and or test run several times restarting may recover it because liquid refrigerant...

Page 267: ...fully opened Is the filter clogged At heating does the indoor fan motor run Are the service valves fully opened Is the filter clogged Is there any liquid flooding Is the superheat within normal range...

Page 268: ...nnector Check why power is not supplied to outdoor sub PCB Connect communication wire securely Defective outdoor sub PCB Replace Malfunction by temporary noise 2 Error detection method Detected commun...

Page 269: ...or foreign matter like dust fouling etc YES Is voltage within the specified range NO Restore normal condition Restore normal condition Remove foreign matter like dust fouling etc Defective outdoor sub...

Page 270: ...ction by temporary noise 2 Error detection method Detected by rotation speed of outdoor fan motor 3 Condition of error displayed When actual rotation speed of outdoor fan motor drops to 75min 1 or low...

Page 271: ...untermeasure 2 Error detection method 3 Condition of error displayed 4 Presumable cause Note If the power transistor primary current exceeds the setting value for 3 seconds the compressor stops Power...

Page 272: ...Replace Defective outdoor sub PCB Replace Defective suction pipe temperature sensor input circuit 2 Error detection method Detection of anomalously low temperature resistance on suction pipe temperatu...

Page 273: ...0 40 20 50 Temperature thermistor resistance k Temperature C 5k at 25 C Broken wire Short circuit Open fully Correct indoor heat exchanger return air temperature thermistor connector connections Defec...

Page 274: ...under Same as above Excessive refrigerant amount Indoor outdoor unit installation spaces Faulty compressor Defective outdor air temp sensor Defective outdoor main PCB Diagnosis Countermeasure 2 Error...

Page 275: ...Check refrigerant amount and refrigerant circuit Repalce compressor Defective outdoor main PCB Replace Defective outdoor main PCB Replace Repalce compressor 2 Error detection method If it fails to ch...

Page 276: ...resistance Replace compressor if necessary Defective outdoor main PCB Replace 2 Error detection method Compressor rotor position 3 Condition of error displayed If it fails again to detect the rotor po...

Page 277: ...Forced operation of drain pump Forced operation of drain pump is sent to the indoor unit 20 Setting of compressor frequency Fixing compressor frequency 21 Quiet mode On timer in order to start quiet m...

Page 278: ...check signal is received RAC unit does not have this function Display of check Display of checking in case of signal of error code address from remote control RAC unit does not have this function Disp...

Page 279: ...case with a nipper or knife and grind burrs with a file etc Install the lower case to the flat wall with attached two wooden screws Connect the remote control cord to the terminal block Connect the t...

Page 280: ...emote control cord art or center upper part h a nipper or knife oden screws Connect the remote control cord to the terminal block Connect the terminal of remote control X Y with the terminal of indoo...

Page 281: ...button once and change to the TEMP RANGE indication 3 Press SET button and enter the temperature range setting mode 4 Select UPPER LIMIT or LOWER LIMIT by using button 5 Press SET button to fix 6 When...

Page 282: ...ordingly You can select the louver stop position in the four The louver can stop at any position In normal working indication indoor unit temperature is indicated instead of airflow Only the master re...

Page 283: ...5 C increase in return air temperature of indoor unit To be reset producing 1 0 C increase in return air temperature of indoor unit To be reset producing 1 0 C increase in return air temperature of i...

Page 284: ...nty minutes OFF or heating thermostat is OFF the fan perform intermittent operation for five minutes e minutes OFF g type indoor unit and is automatically defined e split series the indoor fan tap is...

Page 285: ...284 16 SCM T 199 B PJZ012D077 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL...

Page 286: ...the Installation Manual should be given to a new owner WARNING Ask a professional contractor to carry out installation work according to the installation manual Improper installation work may result...

Page 287: ...ontrol to medical or communication equipment could disrupt medical activities video broadcasting or cause noise interference CAUTION Do not install the remote control at following places It could caus...

Page 288: ...m 2 0 mm2 x 2 core 3 Remote control installation procedure Determine where to install the remote control Installation Using a switch box Installed directly on a wall Wiring direction Backward Upper ce...

Page 289: ...procedure Dimensions Viewed from front Take care to protect the removed upper case from moisture or dust PCB side Viewed from rear To remove the upper case from the bottom cases of R C Insert the tip...

Page 290: ...om case In case of exposing wiring When the wiring is taken out from the upper center or upper left of R C Cut out the thin wall sections on the cases for the size of wire Upper center Upper left Uppe...

Page 291: ...two or more R C Up to two units of R C can be used at the maximum for 1 indoor unit or 1 group One is main R C and the other is sub R C Operating range is different depending on the main or sub R C R...

Page 292: ...USB simultaneously with other USB devices It could cause malfunction or breakdown of R C or personal computer USB port Cover Note Initializing of password Administrator password for daily setting ite...

Page 293: ...located on the refrigerant pipes side Remove two screws and detach the lid from the control box of the air conditioner Setting on site PCB on the receiver has the following switches to set the functio...

Page 294: ...he receiver is pressed If the backup button on the receiver is pressed during a test run it will end the test run If you cannot operate the unit properly during a test run please check by consulting w...

Page 295: ...t 4 Places where the receiver is influenced by the fluorescent lamp or sunlight 2 Places near heat devices 5 Places where the receiver is affected by infrared rays of any other communication devices 3...

Page 296: ...the back ATTENTION DO NOT remove the clamp fixed the wiring Installation of the receiver Check direction of the receiver and fix to the panel CAUTION Connect the connectors before installing the rece...

Page 297: ...in connecting a plural number of indoor units Condition Illuminance at the receiver area 360 lux Top view 60 5m 5m 60 5m Receivable range Receivable range Wireless remote control unit 1m 2 4m 60 5m Re...

Page 298: ...se check wiring by consulting with inspection guides Backup switch 7 segment indicator Light receiving section TIMER CHECK RUN Receiver continued Backup button Cooling test run operation How to read t...

Page 299: ...indoor unit series are not able to be set with this wireless remote control RCN KIT3 E 1 4 fan speed setting PHi Hi Me Lo 3 fan speed setting Hi Me Lo 3 FDUM series RCN KIT3 E 88 A Direct installation...

Page 300: ...the unit properly during a test run please check by consulting with inspection guides on the wiring diagram of outdoor units Cut off the thin section on the side of the upper case with a pair of nipp...

Page 301: ...tioner FAN SPEED button Button to set the fan speed AIR CON No button Indicates the No of air conditioner which is connected MODE button Use to select the mode TEMP button Use to raise the setting tem...

Page 302: ...tion 2 Maximum prolongation of remote control wiring is 600m If the prolongation is over 100m change to the size below But the wiring in the remote control case should be 0 3mm2 recommended to 0 5mm2...

Page 303: ...se of the remote control is mounted to a flat wall with two accessory wood screws Connect the remote control cord to the terminal block Connect the terminals X and Y of the remote control and the term...

Page 304: ...removed screw e remote control cord to the wall surface with a ntrol cord 2 core wires or cables on site configuration is 600 m size below d be 0 3mm2 recommended to 0 5mm2 ing to wire connecting Wat...

Page 305: ...or enabled offset temperature at 1 0 C 06 Remote control thermistor 2 0 C At the time of heating in the case of remote control thermistor enabled offset temperature at 2 0 C 07 Remote control thermist...

Page 306: ...seconds Setting number 01 lighting for 3 to 20 seconds Then the screen goes back to the function number blinking indication if the setting is sequentially conducted continue with the same procedures...

Page 307: ...se instruction Safety precautions Before use please read these Safety Precautions thoroughly before installation All the cautionary items mentioned below are important safety related items to be taken...

Page 308: ...unit approximately 1 3m Be sure not to extend the connection cable on site If the connection cable is extended malfunction may occur Fix the interface on the wall pillar or the like Cut out the punch...

Page 309: ...ct a external remote control unit procured locally to CnT terminal In case of the pulse input switch OFF the DIP switch SW2 1 on the interface PCB When setting operation permission prohibition mode sw...

Page 310: ...l the wired remote control with reference to the attached instruction manual of wired remote control B 0 3mm2 x 2 core cable should be used for the wiring of wired remote control C Maximum length of w...

Page 311: ...310 16 SCM T 199 4 10 5 Superlink E board SC ADNA E F SL2NA E and SL4 AE BE to control...

Page 312: ...311 16 SCM T 199...

Page 313: ...nstalling the unit 1 Place the unit as shown below 2 Remove the bottom plate and duct flange plate of rear from the unit Keep the removed tapping screws to reuse later The number of tapping screws to...

Page 314: ...surface etc Run the sensor cable in a place where the power cable or electrical noise will not cause any abnormal operation 3 Installation procedure a Insert the tip of slotted screwdriver to the gap...

Page 315: ...Connect the cable from remote sensor box and the cut wiring procedure 6 of CNG connector No polarity Be sure to connect the wirings by solder separately Then wirings should prevent a short circuit sep...

Page 316: ...o overturn of the unit Turn off the power source during servicing or inspection work If the power is supplied during servicing or inspection work it could cause electric shock and injury by the operat...

Page 317: ...ions of intake outdoor air do not meet process the outdoor air before intaking 2 Intake outdoor air volume Intake outdoor air volume is 2 6 m3 min at the maximum when two sets of duct joints are used...

Page 318: ...e figure For the height position of hanging the indoor unit refer to Section 5 Fix the brackets 3 and 4 2 pieces each with bolts Install OA spacer i Install it in the way that the recess of OA spacer...

Page 319: ...e put on distant place Conrm there is no backlash between the hanger plate for suspension bolt and the lower nut and washer Use the level gauge only when OA spacer has been installed before hanging 1...

Page 320: ...ed by assembling on the spacer TC OAS E Con rm the following parts are included 1 Before installation Fix the product on the spacer TC OAS E as shown below For the installation method refer to the ins...

Page 321: ...del 5pcs 1pc 1pc Installation Points and Operating Instructions for the Filter Kit CAUTION PJZ012D076 This manual contains installation points and operating instructions for the filter kit manufacture...

Page 322: ...pper side 2 Install the rail on both inner sides of the duct with the screw 3 Install the air filter on the rails Installation procesure 4 Install the bracket on the rail with the screw PJZ012D076 Whe...

Page 323: ...icient of performance Warmer season at indoor temperature 20 0 2 e r u t a r e p m e t j T e r u t a r e p m e t r o o d t u o d n a and outdoor temperature Tj Tj 2 Pdh kW Tj 2 COPd Tj 7 Pdh kW Tj 7 C...

Page 324: ...mer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 0 2 e r u t a r e p m e t j T e r u t a r e p m e t r o o d t u o d n a and outdoor temperature Tj Tj 2...

Page 325: ...g Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 0 2 e r u t a r e p m e t j T e r u t a r e p m e t r o o d t u o d n a and outdoor temperature Tj...

Page 326: ...clared coefficient of performance Warmer season at indoor temperature 20 0 2 e r u t a r e p m e t j T e r u t a r e p m e t r o o d t u o d n a and outdoor temperature Tj Tj 2 Pdh kW Tj 2 COPd Tj 7 P...

Page 327: ...indoor Declared coefficient of performance Warmer season at indoor temperature 20 0 2 e r u t a r e p m e t j T e r u t a r e p m e t r o o d t u o d n a and outdoor temperature Tj Tj 2 Pdh kW Tj 2 C...

Page 328: ...indoor Declared coefficient of performance Warmer season at indoor temperature 20 0 2 e r u t a r e p m e t j T e r u t a r e p m e t r o o d t u o d n a and outdoor temperature Tj Tj 2 Pdh kW Tj 2 CO...

Page 329: ...eason at indoor Declared coefficient of performance Warmer season at indoor temperature 20 0 2 e r u t a r e p m e t j T e r u t a r e p m e t r o o d t u o d n a and outdoor temperature Tj Tj 2 Pdh k...

Page 330: ...Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 0 2 e r u t a r e p m e t j T e r u t a r e p m e t r o o d t u o d n a and outdoor temperature Tj T...

Page 331: ...Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 0 2 e r u t a r e p m e t j T e r u t a r e p m e t r o o d t u o d n a and outdoor temperature Tj Tj...

Page 332: ...Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 0 2 e r u t a r e p m e t j T e r u t a r e p m e t r o o d t u o d n a and outdoor temperature Tj Tj...

Page 333: ...Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 0 2 e r u t a r e p m e t j T e r u t a r e p m e t r o o d t u o d n a and outdoor temperature Tj T...

Page 334: ...g Warmer season at indoor Declared coefficient of performance Warmer season at indoor temperature 20 0 2 e r u t a r e p m e t j T e r u t a r e p m e t r o o d t u o d n a and outdoor temperature Tj...

Page 335: ...o 108 8215 Japan http www mhi mth co jp en INVERTER MULTI SPLIT SYSTEM RESIDENTIAL AIR CONDITIONERS Because of our policy of continuous improvement we reserve the right to make changes in all specific...

Reviews: