(15) Regulation of outdoor air flow
◆
Model SCM50
◆
Models SCM40, 45
Cooling
Heating
Compressor speed (rps)
Less than 30
56 or more
Outdoor fan speed
6th speed
More than 30
but 56 or less
5th speed
4th speed
Less than 30
40 or more
6th speed
More than 30
but 40 or less
5th speed
4th speed
Cooling
Heating
Compressor speed (rps)
Less than 30
61 or more
Outdoor fan speed
6th speed
More than 30
but 61 or less
5th speed
4th speed
Less than 30
48 or more
6th speed
More than 30
but 48 or less
5th speed
4th speed
(16) Serial signal transmission error protection
(a) Purpose
(b) Detail of operation
(17) Rotor lock
(18) Outdoor fan motor protection
(19) Outdoor fan control at low outdoor temperature
Cooling
(i)
(i)
(ii)
(a)
Operating conditions
(ii) Detail of operation
(iii) Reset conditions
Outdoor air temperature > 10˚C
Outdoor air temperature <= 10˚C
Outdoor fan
Outdoor air temperature > 16˚C
Outdoor air temperature <= 16˚C
Lower limit speed
Tho-A
Tho-R
37
37
Tho-R
Tho-A
min
-1
1
2
Tho-R
3
1
2
temperature
Lower
-