7 TROUBLESHOOTING
7.2 Troubleshooting
7.2.1 When the "RUN" LED is flashing or turned off
(1) When flashing
Check item
Corrective action
Is the mode set to the offset/gain setting mode?
Reset switch 4 of the intelligent function module setting for
GPPW to the normal mode (see Section 4.5).
(2) When off
Check item
Corrective action
Is the power being supplied?
Confirm that the supply voltage for the power supply module
is within the rated range.
Is the capacity of the power supply module adequate?
Calculate the current consumption of the CPU module, I/O
module and intelligent function module mounted on the base
unit to see if the power supply capacity is adequate.
Has a watchdog timer error occurred?
Reset the PLC CPU and verify that it is lit. If the RUN LED
does not light even after doing this, the module may be
malfunctioning. Contact the nearest distributor or branch
office with a description of the problem.
Is the module correctly mounted on the base unit?
Check the mounting condition of the module.
7.2.2 When the "ERROR" LED is on or flashing
(1) When on
Check item
Corrective action
Is an error being generated?
Confirm the error code and take corrective action described
in Section 7.1.
(2) When flashing
Check item
Corrective action
Is intelligent function module setting switch 5 set to "other
than 0"?
Using GPPW parameter setting, set intelligent function
module setting switch 5 to "0" (see Section 4.5).
Summary of Contents for Q64AD
Page 11: ...1 2 MELSEC Q 1 OVERVIEW MEMO...
Page 13: ...2 2 MELSEC Q 2 SYSTEM CONFIGURATION MEMO...
Page 31: ...3 18 MELSEC Q 3 SPECIFICATIONS MEMO...
Page 43: ...4 12 MELSEC Q 4 SETUP AND PROCEDURES BEFORE OPERATION MEMO...
Page 61: ...5 18 MELSEC Q 5 UTILITY PACKAGE SW0D5C QADU E MEMO...
Page 67: ...6 6 MELSEC Q 6 PROGRAMMING MEMO...
Page 76: ...Index 3 MEMO...