3.1.3 Accuracy
Accuracy is expressed as a full-scale value.
For example, the accuracy is ± 0.1% ( ± 4 for digital output value) when the module is
used in an ambient temperature of 25 ± 5 °C, and ± 0.3% (± 12 for digital output value)
in an ambient temperature of 0 to 55 °C with temperature drift compensation function.
4000
–4000
Di
g
it
a
l out
p
u
t
va
lu
e
–10 V
0 V
10 V
Analog input value
Range of fluctuation with
respect to the ambient
temperature
Figure 3.3 Accuracy