5.3.3 Memory capacities of files
When using the program memory or standard ROM, calculate the rough size of each file
according to Table5.4.
* : 134 is the default value (It can be increased or decreased by parameter setting.)
Table5.4 Memory capacity calculation for files
Function
Rough file capacity (unit: byte)
Drive heading
70
Parameter
Default: 316 (increases depending on the parameter setting)
Reference
• Boot setting 100
• CC-Link IE controller network setting made Max. 326 increased
• MELSECNET/H setting made Max. 226 increased
• Ethernet setting made Max. 896 increased
• CC-Link setting made 22 + 606
(number of modules of CC-Link Safety) + 76
(number
of safety remote stations) + 4
(number of safety remote station parameter settings)
• Remote password setting made 70 + 20 + (number of target modules 10), Max. 170
increased
Sequence program
134
*
+ (4
(
(number of steps) + (number of allocate memory for online change)))
Device comment
80 + (sum of comment data sizes of devices)
• Comment data size of one device = 10 + 10210
a + 40
b
• a : Quotient of ((device points)/256)
• b : Remainder of ((device points)/256)
Multi-block online
program change
Value set at formatting (0/1.25k/2.5k)