6
- 36
6.8 Recording the operation contents and self-diagnostics error occurrence contents (operation/error history
function)
6
FUNCTIONS
(b) Self-diagnostics error
The contents of the self-diagnostics error detected by the CPU module are stored.
For details on self-diagnostics errors, refer to the following manual.
QSCPU User’s Manual (Hardware Design · Maintenance and Inspection)
(3) Operation · history capacity
The contents of 3000 operations and errors can be stored in the operation/error
history of the CPU module.
When the total number of operations and errors exceeds 3000, the oldest content is
overwritten with the latest one in order.
Table6.13 Operations stored in the operation/error history
Classification
Operation code
Operation message
Operation description
System
OP001
SYSTEM INITIALIZE OPERATION
MODE
Because the safety CPU operation mode is
not retained correctly, the CPU module
initialized the safety CPU operation mode
in TEST MODE.
OP002
SYSTEM INITIALIZE PROGRAM
MEMORY
Because the program memory contents
are not retained correctly, the CPU module
formatted the program memory.
OP003
SYSTEM INITIALIZE OPE./ERROR
LOG
Because the operation/error history
contents are not retained correctly, the
operation/error history was initialized into 0
incidents.
OP004
SYSTEM INITIALIZE SYSTEM CLOCK
Because the system clock data is not
correct, the CPU module initialized the
system clock data.
OP005
SYSTEM INITIALIZE PLC MEMORY
The CPU module executed the PLC
memory initialization function.
OP006
SYSTEM INITIALIZE ROM WRITE INF.
Because the write to ROM information is
not retained correctly, the CPU module
initialized the ROM information.
System (CPU
operation status)
OP010
SYSTEM SWITCH TO RUN
The CPU operation status of the CPU
module switched to the RUN state.
OP011
SYSTEM SWITCH TO STOP
The CPU operation status of the CPU
module switched to the STOP state.
Power supply
operation
OP100
POWER ON
The PLC was power-on.Or the CPU
module reset was canceled.
Drive operation
OP144
WRITE PRGRAM MEMORY TO ROM
The write to ROM of program memory data
standard ROM was executed.
Remote
operation
OP160
SWITCH TO RUN REMOTELY
The remote RUN operation was executed.
OP161
SWITCH TO STOP REMOTELY
The remote STOP operation was
executed.
Safety CPU
operation mode
operation
OP180
SWITCH SAFETY PC OPERATION
MODE
The safety CPU operation mode was
switched.
History operation
OP200
CLEAR OPERATION/ERROR LOG
The operation/error history in the CPU
module was cleared.
Clock operation
OP210
ADJUST SYSTEM CLOCK
The CPU module clock was set.
CPUaccess
password
operation
OP220
MODIFY ACCESS PASSWORD
In the CPU module, the CPU access pass-
word was set.
Summary of Contents for MELSEC QS Series
Page 1: ......
Page 2: ......
Page 24: ...A 22 Memo ...
Page 258: ...Index 3 Memo ...
Page 263: ......
Page 264: ......