9.2 Internal User Devices
9.2.6 Link relay (B)
(3) Using link relays in the network system
In order to use link relays in the network system, a network parameter setting is
required.
Link relays in the range where network parameters have not been set (not used by the
CC-Link IE controller network or MELSECNET/H) can be used as internal relays.
POINT
The number of device points for link relays is 16384 in the CC-Link IE controller
network module and MELSECNET/H module, but 2048 in the CPU module by
default.
To use link relays exceeding the device point range described above, change the
number of device points for link relays on the Device setting tab of PLC parameter
in GX Developer.
Remark
For the network parameters, refer to the following manuals.
CC-Link IE Controller Network Reference Manual
Q Corresponding MELSECNET/H Network System Reference Manual
(PLC to PLC network)