6
- 48
6.12 Remote Operation
6.12.1 Remote RUN/STOP
6
FUNCTIONS
6.12 Remote Operation
Remote operation changes the operating status of the CPU module by the operation
performed from outside (e.g. GX Developer, remote contact).
The following two options are available for remote operations:
• Remote RUN/STOP
:
• Remote RESET
:
6.12.1 Remote RUN/STOP
(1) Definition of Remote RUN/STOP
The remote RUN/STOP performs RUN/STOP of the CPU module externally with the
CPU module RUN/STOP/RESET switch at RUN.
(2) Applications of remote RUN/STOP
Using remote RUN/STOP for the following remote operations are useful:
• When the CPU module is at a position out of reach
• When performing RUN/STOP of the control board CPU module externally
(3) Calculations during Remote RUN/STOP
The program calculation that performs remote RUN/STOP is as follows:
(a) Remote STOP
Executes the program to the END instruction and enters the STOP status.
(b) Remote RUN
When remote RUN is performed while in the STOP status using remote STOP, the
status changes to RUN and executes the program from step 0.
Summary of Contents for MELSEC QS Series
Page 1: ......
Page 2: ......
Page 24: ...A 22 Memo ...
Page 258: ...Index 3 Memo ...
Page 263: ......
Page 264: ......