94
3.8
Input Response Time Setting
This function changes the input response time for each input module. Input modules obtain external inputs within the
set response time.
For the input response time setting by the built-in I/O function, refer to the following.
MELSEC-L CPU Module User's Manual (Built-In I/O Function)
(1) Setting procedure
1.
Select "Input" under "Type" in the I/O Assignment tab, and click the
button.
Project Window
[Parameter]
[PLC Parameter]
[I/O Assignment]
2.
Select any of the following values for "I/O Response Time". (Default: 10ms)
1ms, 5ms, 10ms, 20ms, 70ms
The shorter the input response time is, the more the CPU module is susceptible to noise. Consider the operating
environment when setting input response time values.
OFF
OFF
ON
ON
External input
Input module
Input response time