146
(4) CPU module operation at error detection
When an error is detected by the self-diagnostic function, the CPU module operates according to the specified
operation mode.
• Mode that stops CPU module operation ("Stop"):
• Mode that continues CPU module operation ("Continue"):
When an error is detected, the CPU module executes programs other than the one (instruction) where an
error occurred.
(a) Errors selectable in the PLC RAS tab
Set the operation mode for the case of an error.
Project window
[Parameter]
[PLC Parameter]
[PLC RAS]
(b) Errors selectable in the I/O Assignment tab
• Intelligent function module error (
Project window
[Parameter]
[PLC Parameter]
[I/O Assignment]
[Detailed Setting]
(5) Error check options
Whether to check the following errors can be selected. (All the items are selected by default.)
Project window
[Parameter]
[PLC Parameter]
[PLC RAS]
• Carry Out Battery Check
• Check Device Range at Indexing
The output mode setting in the detailed setting
(from the "I/O Assignment" tab)
CPU module operation
Clear
When an error is detected, the CPU module stops an operation and turns off all
external outputs of the module.
(Outputs (Y) of the device memory are held.)
Hold
When an error is detected, the CPU module stops an operation and holds external
outputs of the module.
(Outputs (Y) of the device memory are held.)
• Computation Error (including SFC program)
• Intelligent Module Program Execution Error
• File Access Error
• Memory Card Operation Error
Select the operation mode.
Summary of Contents for L02CPU
Page 1: ......
Page 2: ......
Page 13: ...11 Memo ...
Page 78: ...76 Memo ...
Page 226: ...224 Memo ...
Page 318: ...316 To the next page ...
Page 320: ...318 To the next page ...
Page 322: ...320 To the next page ...
Page 324: ...322 To the next page ...
Page 326: ...324 To the next page ...
Page 335: ...333 Memo ...
Page 339: ......