148
: Self-diagnostics is performed. ×: Self-diagnostics is not performed.
(To the next page)
Diagnostics
Error
message
Diagnostic timing
CPU
module
status
LED status
L02CPU
L26CPU
-BT
RUN
ERR.
Handling
error
Module verification
UNIT BAD
CONNECT
• Execution of the END
instruction
Stop
Off/On
Flashing/
On
Intelligent function module
assignment error
SP.UNIT LAY
ERR.
• Power-on/reset
• Switching from STOP to RUN
Stop
Off
Flashing
Intelligent module program
execution error
*1
SP.UNIT ERROR
• Execution of the FROM/TO
instructions
Stop/
Continue
Off/On
Flashing/
On
Intelligent function module
version error
SP.UNIT
VER.ERR
• Power-on/reset
Stop
Off
Flashing
END cover is not attached
NO END COVER
• Power-on/reset
• Execution of the END
instruction
Stop
Off
Flashing
Execution of the END
instruction
SYSTEM LAY
ERR
• Power-on/reset
Stop
Off
Flashing
No parameter
MISSING PARA.
• Power-on/reset
• Switching from STOP to RUN
Stop
Off
Flashing
Boot error
BOOT ERROR
• Power-on/reset
Stop
Off
Flashing
Backup error
RESTORE
ERROR
• Power-on/reset
Stop
Off
Flashing
Memory card operation
error
*1
ICM.OPE.
ERROR
• Insertion/removal of the
memory card
Stop/
Continue
Off/On
Flashing/
On
×
×
File setting error
FILE SET
ERROR
• Power-on/reset
• Writing to programmable
controller
Stop
Off
Flashing
File access error
*1
FILE OPE.
ERROR
• Instruction execution
Stop/
Continue
Off/On
Flashing/
On
Instruction execution
disabled
CAN'T EXE.PRG.
• Power-on/reset
• Switching from STOP to RUN
Stop
Off
Flashing
Parameter
error
Parameter setting check
PARAMETER
ERROR
• Power-on/reset
• Switching from STOP to RUN
• Writing to programmable
controller
Stop
Off
Flashing
SFC parameter error
SFC
PARA.ERROR
• Switching from STOP to RUN
• Writing to programmable
controller
Stop
Off
Flashing
Intelligent function module
parameter error
SP.PARA.
ERROR
• Power-on/reset
Stop
Off
Flashing
Password error
REMOTE
PASS.ERR
• Power-on/reset
• Switching from STOP to RUN
Stop
Off
Flashing
Instruction code check
INSTRUCT.
CODE ERR
• Power-on/reset
• Switching from STOP to RUN
• Instruction execution
Stop
Off
Flashing
No END instruction
MISSING END
INS.
• Power-on/reset
• Switching from STOP to RUN
Stop
Off
Flashing
Pointer setting error
CAN'T SET(P)
• Power-on/reset
• Switching from STOP to RUN
Stop
Off
Flashing
CAN'T SET(I)
• Power-on/reset
• Switching from STOP to RUN
Stop
Off
Flashing
Summary of Contents for L02CPU
Page 1: ......
Page 2: ......
Page 13: ...11 Memo ...
Page 78: ...76 Memo ...
Page 226: ...224 Memo ...
Page 318: ...316 To the next page ...
Page 320: ...318 To the next page ...
Page 322: ...320 To the next page ...
Page 324: ...322 To the next page ...
Page 326: ...324 To the next page ...
Page 335: ...333 Memo ...
Page 339: ......