Appendix 1.3
Network Parameter Setting
For the network parameters of CC-Link, refer to the following.
MELSEC-L CC-Link System Master/Local Module User's Manual
Appendix 1.4
Remote Password setting
This section provides the remote password setting screens and details of the setting items.
After setting a remote password, store the parameters in the parameter-valid drive.
Item
Description
Setting range
Password Setting
Enter a remote password.
Up to four characters (alphanumeric
characters, special symbols)
Password
Active
Module
Setting
Model Name
Select a model name of the CPU module.
• LCPU
• LJ71C24
Start X/Y
Set the start address of the module.
0000
H
to 0FE0
H
Condition (detailed setting)
When selecting the L02CPU or L26CPU-BT, detailed
settings are required.
⎯
User Connection No.
Select a user connection number(s).
Connection 1 to Connection 16
System Connection
Select a port(s) where the remote password is
enabled.
• MELSOFT Transmission Port (TCP/IP)
• MELSOFT Transmission Port (UDP/IP)
• FTP Transmission port (TCP/IP)
• Direct Connection of MELSOFT
Regard as Error when Remote
Pasword Mismatch Count Reaches
Upper Limit
Set whether to generate an error when the number
of mismatches on remote password reaches to the
upper limit.
Deselected
Upper Limit of
Mismatch
Set the upper limit of the number of remote
password mismatches.
1 to 65535 (default: 10 (Count))
Summary of Contents for L02CPU
Page 1: ......
Page 2: ......
Page 13: ...11 Memo ...
Page 78: ...76 Memo ...
Page 226: ...224 Memo ...
Page 318: ...316 To the next page ...
Page 320: ...318 To the next page ...
Page 322: ...320 To the next page ...
Page 324: ...322 To the next page ...
Page 326: ...324 To the next page ...
Page 335: ...333 Memo ...
Page 339: ......