(7) Time taken to collect module errors
Use the following formula to calculate the increase in scan time when the module error collection function is used.
[Increase in the scan time]
KM1 + (N1 × KM2) + (N2 × KM3) [µs]
• N1: FNumber of errors collected per scan by the built-in CC-Link or external modules
• N2: FNumber of errors collected by the built-in I/O
(8) Data logging function
For the increase in scan time when using the data logging function, refer to the following.
MELSEC-L CPU Module User's Manual (Data Logging Function)
CPU module
KM1
KM2
KM3
L02CPU
28
80
60
L26CPU-BT
21
70
50