157
CHAPTER 3 CPU MODULE FUNCTIONS
3
3.
26
M
odule E
rror
Collect
io
n F
unct
ion
(5) Monitoring module errors
To check the collected errors, open the "Error History" dialog box.
[Diagnostics]
[System Monitor...]
[System Error History]
* 1
For details on error codes, refer to the following.
Manual for the intelligent function module used
*2
If an error occurred during initial processing, its occurrence time may be stored as "0000/00/00 00:00:00" in the module
error collection file. Such errors are not displayed in the order of occurrence.
●
The Error History dialog box can be displayed by selecting a module figure in the "Main block" area and clicking the
button in the System Monitor dialog box. In this case, only the errors of the selected module are
displayed.
GX Works2 Version1 Operating Manual (Common)
●
Errors are not displayed for modules that do not support the module error collection function.
●
Errors may not be displayed when they occur frequently and successively.
Item
Description
Remarks
Error Code
*1
Displays error code numbers.
⎯
Date and Time
*2
Displays the year, month, day, hour, minute, and second when an error
occurred.
The year can be displayed within the range of
1980 to 2079.
Model Name
Displays a module model name. For the built-in I/O and built-in CC-Link, the
model name is displayed as follows.
• Built-in I/O: CPU module model name (IO) (example: L02CPU(IO) or
L26CPU-BT(IO))
• Built-in CC-Link: CPU module model name (BT) (example: L26CPU-
BT(BT)
⎯
Start I/O
Displays the start I/O number of a module in error.
⎯
Summary of Contents for L02CPU
Page 1: ......
Page 2: ......
Page 13: ...11 Memo ...
Page 78: ...76 Memo ...
Page 226: ...224 Memo ...
Page 318: ...316 To the next page ...
Page 320: ...318 To the next page ...
Page 322: ...320 To the next page ...
Page 324: ...322 To the next page ...
Page 326: ...324 To the next page ...
Page 335: ...333 Memo ...
Page 339: ......