7. CAPACITY TABLES
7-9. Correction by Refrigerant Piping Length
CITY MULTI systems can have extended piping lengths if certain limitations are followed, but cooling/heating capacity could be
reduced. Using following correction factor by equivalent piping length shown at 6-2-1 and 6-2-2, capacity can be found. 6-2-3
shows how to obtain the equivalent piping length.
7-9-1. Cooling Capacity Correction
2 - 471
6. CAPACITY TABLES
DATA U10
OUTDOOR UNITS
H
2i
R
2
6-2. Correction by refrigerant piping length
CITY MULTI systems can have extended piping lengths if certain limitations are followed, but cooling/heating capacity could be
reduced. Using following correction factor by equivalent piping length shown at 6-2-1 and 6-2-2, capacity can be found. 6-2-3
shows how to obtain the equivalent piping length.
6-2-1. Cooling capacity correction
6-2-2. Heating capacity correction
0
100
200
300
400
500
600 ft.
Piping equivalent length
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Cooling capacity correction factor
0
31
61
92
122
153
183 m
PURY-HP72TKMU/YKMU
72
108
54
36
Total capacity of indoor unit
0
100
200
300
400
500
600 ft.
Piping equivalent length
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Cooling capacity correction factor
0
31
61
92
122
153
183 m
PURY-HP144TSKMU/YSKMU
Total capacity of indoor unit
72
108
144
216
0
100
200
300
400
500
600 ft.
Piping equivalent length
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Cooling capacity correction factor
0
31
61
92
122
153
183 m
PURY-HP96TKMU/YKMU
Total capacity of indoor unit
48
72
96
144
0
100
200
300
400
500
600 ft.
0
31
61
92
122
153
183 m
Piping equivalent length
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
Cooling capacity correction factor
PURY-HP192TSKMU/YSKMU
Total capacity of indoor unit
96
144
192
288
0.80
50
0
100 150 200 250 300 350 400 450 500 550 600
Heating capacity correction factor
0.85
0.90
0.95
1.00
ft.
Piping equivalent length
15
0
31 46 61 76 92 107 122 137 153 168 183 m
PURY-HP72TKMU/YKMU
0.80
50
0
100 150 200 250 300 350 400 450 500 550 600
Heating capacity correction factor
0.85
0.90
0.95
1.00
ft.
Piping equivalent length
15
0
31 46 61 76 92 107 122 137 153 168 183 m
PURY-HP144,192TSKMU/YSKMU
0.80
50
0
100 150 200 250 300 350 400 450 500 550 600
Heating capacity correction factor
0.85
0.90
0.95
1.00
ft.
Piping equivalent length
15
0
31 46 61 76 92 107 122 137 153 168 183 m
PURY-HP96TKMU/YKMU