FX2N-64CL-M CC-Link/LT Master Block
Outline 1
1-4
•
Factory default, DIP switches are set OFF.
•
The Test mode is selected when both the CONFIG and TEST modes are set ON
simultaneously.
•
For each setting, the status at the time of power ON is valid.
(If a setting is changed after the power is set ON, such a change is invalid.)
•
In the CONFIG mode, the L ERR. indicator lights or flickers when the detailed information
on the remote station actually connected at the time of power ON do not match the detailed
remote station information within the master.
(When BFM #32 (20h) to #95 (5Fh) are edited, the station numbers are checked.)
If the remote station information is not edited, the L ERR. does not light or flicker when
turning ON the all disconnected remote station, or when removing the remote station after
power ON.
DIP
s
w
itc
h
f
o
r op
e
ra
tion
s
e
tt
in
g
1
B RATE
Communication speed setting
2
3 16pts/4pts
Point mode setting
(Select the number of I/O points per station.)
OFF:4-point mode (4 input points and 4 output points in each station)
ON :16-point mode (16 input points and 16 output points in each station)
4
--
Setting is disabled. (Make sure that it is OFF during operation.)
5
--
Setting is disabled. (Make sure that it is OFF during operation.)
6 CONFIG/ONLINE
CONFIG mode
OFF: ONLINE mode (normal operation)
ON : CONFIG mode (The information on the connected stations is saved to
the EEPROM.)
7 TEST/ONLINE
TEST mode
OFF: ONLINE mode (normal operation)
ON : TEST mode (Self-loop back Test)
8
--
Setting is disabled. (Make sure that it is OFF during operation.)
Name
Description
Communication speed
SW1
SW2
156 kbps
OFF
OFF
625 kbps
ON
OFF
2.5 Mbps
OFF
ON
Setting disabled
ON
ON
Summary of Contents for FX2N-64CL-M
Page 1: ...USER S MANUAL Detailed Volume FX2N 64CL M CC Link LT Master Block ...
Page 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Page 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Page 12: ...FX2N 64CL M CC Link LT Master Block x ...
Page 26: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 ...
Page 50: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 ...
Page 74: ...FX2N 64CL M CC Link LT Master Block Model Assignment of Buffer Memory 10 10 14 ...
Page 93: ......