FX2N-64CL-M CC-Link/LT Master Block
Specifications 2
2-2
2.1
General specifications
*1 Do not use the PLC under pressure higher than the atmospheric pressure. Doing so may damage the PLC.
2.2
Network wiring specifications
Item
Specification
Operating temperature
0 to 55
°
C (32 to 131
°
F)
Storage temperature
-20 to 70
°
C (-4 to 158
°
F)
Operating humidity
35 to 85%RH (Dew condensation should not be allowed.)
Vibration resistance
Direct mounting
Number of sweep times
Frequency
Acceleration
Half amplitude
10 times in each of the X, Y and Z
directions (for 80 min)
10 to 57Hz
--
0.075mm
57 to 150Hz
9.8m/s
2
--
DIN rail mounting
Frequency
Acceleration
Half amplitude
10 to 57Hz
--
0.035mm
57 to 150Hz
4.9m/s
2
--
Shock resistance
147 m/s
2
, working time: 11 ms, half sine wave, three times in each of X, Y and Z
directions
Noise immunity
By noise simulator of noise voltage = 1,000 Vp-p, noise width = 1
µ
s, rising = 1 ns,
cycle = 30 to 100 Hz
Dielectric withstand
voltage
500V AC for 1 min
In conformance to JEM-1021
Between case and PLC grounding terminal
Isolation resistance
5 M
Ω
or more by 500V DC
megger
Operating ambience
Do not use in a corrosive gas, flammable gas or conductive dust environment.
Working altitude
<2000m
*1
Grounding
Class D grounding
(Common grounding with a heavy electrical system is not allowed.)
Item
Specification
Remarks
Communication speed
2.5Mbps
625kbps
156kbps
--
Distance between stations
No restriction
--
Maximum number of
modules connected in 1
drop line
8 units
Maximum number of
remote modules
connected per branch in
a drop line
Maximum trunk length
35m (114' 9")
100m (328' 1")
500m (1640' 5")
Cable length between
terminating resistors
T-branch interval
No restriction
--
Maximum drop length
4m (13' 1")
16m (52' 5")
60m (196' 10")
Cable length per branch
Cumulative drop line
length
15m (49' 2")
50m (164' 0")
200m (656' 2")
Sum of all drop lines
Summary of Contents for FX2N-64CL-M
Page 1: ...USER S MANUAL Detailed Volume FX2N 64CL M CC Link LT Master Block ...
Page 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Page 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Page 12: ...FX2N 64CL M CC Link LT Master Block x ...
Page 26: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 ...
Page 50: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 ...
Page 74: ...FX2N 64CL M CC Link LT Master Block Model Assignment of Buffer Memory 10 10 14 ...
Page 93: ......