FX2N-64CL-M CC-Link/LT Master Block
Assignment of I/O numbers 8
8-6
Configuration of detailed remote station information
Bit
Function
1(ON)
0(OFF)
b0
Number of I/O points
00001:1point
00101:5points
01001: 9points
01101:13points
00010:2points
00110:6points
01010:10points
01110:14points
00011:3points
00111:7points
01011:11points
01111:15points
00100:4points
01000:8points
01100:12points
10000:16points
The bits above are in the order "b4, b3, b2, b1, b0".
b1
b2
b3
b4
b5 to b7
(Setting prohibited)
Set these bits to 0.
b8
Input flag
Input is given.
Input is not given.
b9
Output flag
Output is given.
Output is not given.
b10
RD station flag
RD station.
Not RD station.
b11
Head station flag
Head station.
Not a head station.
b12
Input filter setting
High-speed input
General-purpose input
b13
Output hold/clear setting
HOLD
CLEAR
b14
(Setting prohibited)
Set these bits to 0.
b15
Reserved station flag
Reserved station.
Not a reserved station.