117
O
ffline aut
o t
u
ning
458
Second motor constant
(R1)
0.001
Ω
9999
0 to 50
Ω
Tuning data of the second motor
(The value measured by offline auto tuning is
automatically set.)
9999
Use the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU (1500r/min series)) constants
459
Second motor constant
(R2)
0.001
Ω
9999
0 to 50
Ω
Tuning data of the second motor
(The value measured by offline auto tuning is
automatically set.)
9999
Use the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU (1500r/min series)) constants
460
Second motor constant (L1)
0.001
Ω
(0.1mH)
9999
0 to 50
Ω
(0
to 1000mH)
Tuning data of the second motor
(The value measured by offline auto tuning is
automatically set.)
9999
Use the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU (1500r/min series)) constants
461
Second motor constant (L2)
0.001
Ω
(0.1mH)
9999
0 to 50
Ω
(0
to 1000mH)
Tuning data of the second motor
(The value measured by offline auto tuning is
automatically set.)
9999
Use the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU (1500r/min series)) constants
462
Second motor constant (X)
0.01
Ω
(0.1%)
9999
0 to 500
Ω
(0 to 100%)
Tuning data of the second motor
(The value measured by offline auto tuning is
automatically set.)
9999
Use the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU (1500r/min series)) constants
463
Second motor auto tuning
setting/status
1
0
0, 1, 101
Set the tuning mode of the second motor. (same as
Pr. 96
)
684
Tuning data unit switchover
1
0
0
Internal data converter value
1
Displayed in "A,
Ω
, mH, %".
859
Torque current
0.01A
9999
0 to 500A
Tuning data
(The value measured by offline auto tuning is
automatically set.)
9999
Use the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU (1500r/min series)) constants
860
Second motor torque
current
0.01A
9999
0 to 500A
Tuning data of the second motor
(The value measured by offline auto tuning is
automatically set.)
9999
Use the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU (1500r/min series)) constants
—
89
Refer to
Pr. 81
.
90 to 94
Refer to
Pr. 82
to
Pr. 84
.
O
n
line aut
o t
uning
95
Online auto tuning selection
1
0
0
Online auto tuning is not performed
1
Start-time tuning (at start-up)
2
Magnetic flux observer (normal)
574
Second motor online auto
tuning
1
0
0, 1
Select the second motor online auto tuning. (same as
Pr. 95
)
—
96
Refer to
Pr. 82
to
Pr. 84
.
Func
tio
n
Parameter
Name
Incre
ments
Initial
Value
Range
Description
Re
la
te
d
p
ara
m
e
te
rs
Magnetic fluxM
a
g
n
e
ti
c
f
lu
x
Magnetic flux
SensorlessS
e
n
s
o
rl
e
s
s
Sensorless
VectorV
e
c
to
r
Vector
Magnetic fluxM
a
g
n
e
ti
c
f
lu
x
Magnetic flux
SensorlessS
e
n
s
o
rl
e
s
s
Sensorless
VectorV
e
c
to
r
Vector