116
O
ffl
ine aut
o
t
uni
ng
82
Motor excitation current
0.01A
9999
0 to 500A
Tuning data
(The value measured by offline auto tuning is
automatically set.)
9999
Use the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU (1500r/min series)) constants
83
Rated motor voltage
0.1V
200/
400V *
0 to 1000V
Set the rated motor voltage(V).
* The initial values differ according to the voltage level.
(200V/400V)
84
Rated motor frequency
0.01Hz
60Hz
10 to 120Hz Set the rated motor frequency (Hz).
90
Motor constant (R1)
0.001
Ω
9999
0 to 50
Ω
Tuning data
(The value measured by offline auto tuning is
automatically set.)
9999
Use the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU (1500r/min series)) constants
91
Motor constant (R2)
0.001
Ω
9999
0 to 50
Ω
Tuning data
(The value measured by offline auto tuning is
automatically set.)
9999
Use the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU (1500r/min series)) constants
92
Motor constant (L1)
0.001
Ω
(0.1mH)
9999
0 to 50
Ω
(0
to 1000mH)
Tuning data
(The value measured by offline auto tuning is
automatically set.)
9999
Use the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU (1500r/min series)) constants
93
Motor constant (L2)
0.001
Ω
(0.1mH)
9999
0 to 50
Ω
(0
to 1000mH)
Tuning data
(The value measured by offline auto tuning is
automatically set.)
9999
Use the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU (1500r/min series)) constants
94
Motor constant (X)
0.01
Ω
(0.1%)
9999
0 to 500
Ω
(0 to 100%)
Tuning data
(The value measured by offline auto tuning is
automatically set.)
9999
Use the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU (1500r/min series)) constants
96
Auto tuning setting/status
1
0
0
Auto tuning is not performed
1
Tuning performed without motor running
101
Tuning performed with motor running
455
Second motor excitation
current
0.01A
9999
0 to 500A
Tuning data of the second motor
(The value measured by offline auto tuning is
automatically set.)
9999
Use the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA,
SF-HRCA, SF-V5RU (1500r/min series)) constants
456
Rated second motor
voltage
0.1V
200/
400V *
0 to 1000V
Set the rated voltage (V) of the second motor.
* The initial values differ according to the voltage level.
(200V/400V)
457
Rated second motor
frequency
0.01Hz
60Hz
10 to 120Hz Set the rated frequency (Hz) of the second motor.
Func
tio
n
Parameter
Name
Incre
ments
Initial
Value
Range
Description
Re
la
te
d
p
ara
m
e
te
rs
Magnetic fluxM
a
g
n
e
ti
c
f
lu
x
Magnetic flux
SensorlessS
e
n
s
o
rl
e
s
s
Sensorless
VectorV
e
c
to
r
Vector