91
Start/stop from the operation panel (PU
REMARKS
Pr. 184 AU terminal function selection
must be set to "4" (AU signal) (initial value).
(Refer to Chapter 4 of
the Instruction Manual
(Applied).)
Change the frequency (60Hz) at the maximum value of potentiometer (at 20mA, initial value)
Adjust the frequency in
Pr. 126 Terminal 4 frequency setting gain frequency. (Refer to page 99.)
Change the frequency (0Hz) at the minimum value of potentiometer (at 4mA, initial value)
Adjust the frequency in
calibration parameter C5 Terminal 4 frequency setting bias frequency. (Refer to
Chapter 4 of
the Instruction Manual (Applied).)
Stop
Flickering
Display
Operation
10.
Deceleration
Input 4mA or less.
The frequency on the display decreases
in
Pr. 8 Deceleration time
, and the motor stops
rotating with " " (0.00Hz) displayed.
[FWD] indicator or [EXT] indicator flickers.
11.
Stop
Press .
[FWD] indicator or [REV] indicator turns OFF.
Current signal
source
(20mADC)
Current signal
source
(4mADC)
9.
Acceleration
→
constant speed
Perform 20mA input.
The frequency on the display increases in
Pr. 7
Acceleration time
and " " (60.00Hz)
appears.