5 - 7
MELSEC-A
5 PROGRAMMING
*1 When remote device station initialization procedure registration is to be made
to multiple modules, correct the program part enclosed by the dotted line 1) as
shown below.
RX(m+1)B/RX(n+1)B indicates remote READY, and RX(m+1)8/RX(n+1)8
indicates an initial data processing request flag. The device number changes
depending on the station number. Insert the remote READY and initial data
processing request flags for all stations where remote device station
initialization procedure registration has been set.
SB5F
RX(m+1)B RX(n+1)B
RX(m+1)8
RX(n+1)8
*2 The program part enclosed by the dotted line 2) is request only when the initial
setting is changed.