3 - 7
MELSEC-A
3 SPECIFICATION
(2) Accuracy of current output
For current output, accuracy is relative to 20mA.
Analog output is provided at the accuracy of within ±0.2% (±40µA) when the
operating ambient temperature is 25±5°C, or within ±0.4% (±80µA) when the
operating ambient temperature is 0 to 55°C.
0mA
0
4000
Digital input value
20mA
A
nal
og o
u
tput
val
u
e
Varies within the range of
0.2% ( 40 A) at operating
ambient temperature of 25 5 .
Varies within the range of
0.4% ( 80 A) at operating
ambient temperature of 0 to 55 .
Fig. 3.4 Current Output Accuracy
3.3.5 Conversion speed
Conversion speed indicates time required to read the digital output value written to the
buffer memory, perform D/A conversion, and then output the specified analog value.
Conversion speed per channel of the AJ65SBT-62DA is 1ms.
Due to the data link processing time of the CC-Link system, there is a transmission
delay until the D/A conversion value is read actually.
For the data link processing time, refer to the user's manual of the master module
used.
Example) Data link processing time taken in the asynchronous mode when the master
module is the QJ61BT11 (normal value)
[Calculation expression]
SM+LS×1+remote device station processing time
SM: Scan time of master station sequence program
LS : Link scan time
Remote device station processing time: (Number of channels used+1*) × 1ms
*: Internal processing time of AJ65SBT-62DA
Summary of Contents for AJ65SBT-62DA
Page 2: ......
Page 12: ...A 10 MEMO...
Page 14: ...1 2 MELSEC A 1 OVERVIEW MEMO...
Page 42: ...4 10 MELSEC A 4 SETUP AND PREPARATION BEFORE OPERAATION MEMO...
Page 48: ...5 6 MELSEC A 5 PROGRAMMING 3 Program example...
Page 62: ...6 6 MELSEC A 6 TROUBLESHOOTING MEMO...
Page 69: ...Index 3 MEMO...
Page 71: ......