3 - 15
MELSEC-A
3 SPECIFICATION
3.6.4 Output range/HOLD/CLEAR setting (Address RWwm+3)
(1) Make output range setting using the 8 upper bits (b8 to b15) of address RWwm+3.
Make HOLD/CLEAR setting using the 8 lower bits (b0 to b7) of address
RWwm+3.
(2) The default settings are -10 to +10V and CLEAR.
b15
b12
b11
b8
b7
b4
b3
b0
Output range setting
HOLD/CLEAR setting
0
H
: -10 to +10V
1
H
: 0 to 5V
2
H
: 1 to 5V
3
H
: 0 to 20mA
4
H
: 4 to 20mA
5
H
: User range setting 1 (-10 to +10V)
6
H
: User range setting 2 (0 to 5V)
7
H
: User range setting 3 (0 to 20mA)
0
H
1 to F
H
: HOLD
: CLEAR
to
CH.2
to
CH.1
to
CH.2
to
CH.1
Example
Set 5101H when setting channel 1 to "0 to 5V" and "HOLD" and channel 2 to "User range setting
1" and "CLEAR".
b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
5101
H
0
1
0
0
0
1
0
0
0
0
0
0
0
1
1
0
1
0
1
5
CH.2
CH.1
CH.2
CH.1
Summary of Contents for AJ65SBT-62DA
Page 2: ......
Page 12: ...A 10 MEMO...
Page 14: ...1 2 MELSEC A 1 OVERVIEW MEMO...
Page 42: ...4 10 MELSEC A 4 SETUP AND PREPARATION BEFORE OPERAATION MEMO...
Page 48: ...5 6 MELSEC A 5 PROGRAMMING 3 Program example...
Page 62: ...6 6 MELSEC A 6 TROUBLESHOOTING MEMO...
Page 69: ...Index 3 MEMO...
Page 71: ......