![Mitsubishi AJ65SBT-62DA User Manual Download Page 21](http://html1.mh-extra.com/html/mitsubishi/aj65sbt-62da/aj65sbt-62da_user-manual_1809306021.webp)
3 - 5
MELSEC-A
3 SPECIFICATION
3.3.2 Current output characteristics
The current output characteristic graph is shown below.
A
nal
o
g
out
p
u
t va
lue (
m
A
)
Digital input value
1
2
4095
4000
0
0
5
10
15
20
P
ract
ic
a
l anal
o
g
out
put
sc
o
p
e
2000
4
Number
Analog Output Range Setting
Offset Value
Gain Value
Digital Input Value
Maximum Resolution
1)
0 to 20mA
0mA
20mA
5µA
2)
4 to 20mA
4mA
20mA
—
User range setting 3
(0 to 20mA)
0mA
20mA
0 to 4000
4µA
Fig. 3.2 Current Output Characteristic
POINT
(1) Within the digital input and analog output scopes of each output range, the
maximum resolution and accuracy are within the performance specification
range. Outside those scopes, however, they may not fall within the performance
specification range. (Avoid using the dotted line part in Fig. 3.2.)
(2) Set the offset and gain values of the user range setting within the range
satisfying the following conditions.
(a) Setting range when user range setting 3 is selected: 0 to 20mA
(b) (Gain value) > (Offset value)
If you attempt to make setting outside the setting range of (a), the "RUN" LED
flickers at 0.5s intervals.
Set the values within the setting range.
If you attempt to make setting outside the setting range of (b), the "RUN" LED
flickers at 0.5s intervals.
Make setting again.
Summary of Contents for AJ65SBT-62DA
Page 2: ......
Page 12: ...A 10 MEMO...
Page 14: ...1 2 MELSEC A 1 OVERVIEW MEMO...
Page 42: ...4 10 MELSEC A 4 SETUP AND PREPARATION BEFORE OPERAATION MEMO...
Page 48: ...5 6 MELSEC A 5 PROGRAMMING 3 Program example...
Page 62: ...6 6 MELSEC A 6 TROUBLESHOOTING MEMO...
Page 69: ...Index 3 MEMO...
Page 71: ......