4 - 9
MELSEC-A
4 SETUP AND PREPARATION BEFORE OPERAATION
4.8.2 Wiring of module with external equipment
(1) For voltage output
V+
COM
CH1
V+
COM
CH2
2k
1M
to
GND
Motor drive unit or like
*1
*2
GND
Motor drive unit or like
D/A
conversion
2k
1M
to
*1 .....Use a two-core twist shielded line for the wiring.
*2 .....If noise or ripples occur in the external wiring, connect a 0.1 to 0.47µF
capacitor (25V or higher voltage-resistant product) to the input
terminals of the external device.
(2) For current output
I+
COM
CH1
I+
COM
CH2
0
600
to
GND
Motor drive unit or like
*1
*2
GND
Motor drive unit or like
D/A
conversion
0
600
to
*1 .....Use a two-core twist shielded line for the wiring.
*2 .....If noise or ripples occur in the external wiring, connect a 0.1 to 0.47µF
capacitor (25V or higher voltage-resistant product) to the input
terminals of the external device.
POINT
D/A conversion values are fluctuated by self-heating within approx. 30 minutes after
power is turned ON.
4.9 Maintenance and Inspection
There are no special inspection items for the AJ65SBT-62DA module, but follow the
inspections items describes in the PLC CPU User's Manual so that the system can
always be used in the best condition.
Summary of Contents for AJ65SBT-62DA
Page 2: ......
Page 12: ...A 10 MEMO...
Page 14: ...1 2 MELSEC A 1 OVERVIEW MEMO...
Page 42: ...4 10 MELSEC A 4 SETUP AND PREPARATION BEFORE OPERAATION MEMO...
Page 48: ...5 6 MELSEC A 5 PROGRAMMING 3 Program example...
Page 62: ...6 6 MELSEC A 6 TROUBLESHOOTING MEMO...
Page 69: ...Index 3 MEMO...
Page 71: ......