Speed in standby mode (only used if "auto" has been selected
for "Operating mode") means the charge pump operates at the
set speed during the time when there is neither a need for
compressor operation nor additional heat.
5.12 - country
Select here where the product was installed. This allows access
to country specifi c settings in your product.
Language settings can be made regardless of this selection.
NOTE
This option locks after 24 hours, restart of display or
program updating.
Menu 5.11 - heat pump settings
Settings for installed heat pump can be made in the submenus.
Menu 5.11.1 - EB101 - EB108
Make settings specifically for the installed heat pump and
charge pump here.
For RC-HY40, it is possible to connect up to 8 heat pumps.
Menu 5.11.1.1 - heat pump
Make settings for the installed heat pump here. To see what
settings you can make, see installation manual for the heat
pump.
Menu 5.11.1.2 - charge pump (GP12)
op. mode
Heating/cooling
Setting range: auto / intermittent
Default value: auto
Set the operating mode for the charge pump here.
auto:
The charge pump runs according to the current operating
mode for SMO 20.
intermittent:
The charge pump starts and stops 20 seconds
before and after the compressor in the heat pump.
speed during operation heating, hot water,
cooling
Setting range: auto / manual
Default value: auto
Manual setting
Setting range: 1 – 100 %
Default values: 70 %
speed in wait mode
Setting range: 1 – 100 %
Default values: 30 %
max. allowed speed
Setting range: 80 – 100 %
Default values: 100 %
Set the speed at which the charge pump is to operate in the
present operating mode. Select "auto" if the speed of the charge
pump is to be regulated automatically (factory setting) for
optimal operation.
If "auto" is activated for heating operation, you can also make
the setting "max. allowed speed" which restricts the charge
pump and does not allow it to run at a higher speed than the set
value.
For manual operation of the charge pump deactivate "auto" for
the current operating mode and set the value to between 1 and
100 % (the previously set value for "max. allowed speed" no
longer applies).
Summary of Contents for HMK60
Page 2: ...1 2 ...
Page 87: ...85 Technical data Electrical circuit diagram HSB60 ...
Page 88: ...86 Technical data HMK60 RC HY FDCW60VNX A FDCW60VNX A 2 FDCW60VNX A 3 ...
Page 89: ...87 Technical data FDCW60VNX A 2 FDCW60VNX A 3 RC HY RC HY RC HY ...
Page 90: ...88 Technical data RC HY RC HY RC HY ...
Page 93: ...91 Technical data sheet 3 ...
Page 94: ...92 Technical data sheet 4 ...
Page 97: ...95 Technical data sheet 3 ...
Page 98: ...96 Technical data sheet 4 ...
Page 99: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 100: ...98 Technical data sheet 6 ...
Page 101: ......
Page 104: ...1 2 FDCW71VNX FDCW100VNX LEK LEK ...
Page 189: ...85 Technical data Electrical circuit diagram HSB100 ...
Page 190: ...86 Technical data HMK100 RC HY FDCW FDCW FDCW ...
Page 191: ...87 Technical data FDCW FDCW RC HY RC HY RC HY ...
Page 192: ...88 Technical data RC HY RC HY RC HY ...
Page 195: ...91 Technical data sheet 3 ...
Page 196: ...92 Technical data sheet 4 ...
Page 199: ...95 Technical data sheet 3 ...
Page 200: ...96 Technical data sheet 4 ...
Page 201: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 202: ...98 Technical data sheet 6 ...
Page 203: ......
Page 206: ......
Page 277: ...71 Technical data Electrical circuit diagram HSB140 ...
Page 280: ...74 Technical data sheet 3 ...
Page 281: ...75 Technical data sheet 4 ...
Page 284: ...78 Technical data sheet 3 ...
Page 285: ...79 Technical data sheet 4 ...
Page 286: ...80 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 287: ...81 Technical data sheet 6 ...