79
Disturbance in comfort
■ External switch for changing the room heating activ- ated.
– Check any external switches.
■ Air in the climate system.
– Vent the climate system.
■ Closed valves to the climate system.
– Open the valves.
■ Incorrectly adjusted fl ow across the heat pump.
– Check whether alarm high condenser in (163) or high
condenser out (162) is in the alarm log. Follow the
instructions for adjusting charge fl ow.
High room temperature
■ Too high set value on the automatic heating control.
– Enter menu 1.1 (temperature) and reduce the offset
heating curve. If the room temperature is only high in
cold weather the curve slope in menu 1.9.1 "heating
curve" needs adjusting down.
■ External switch for changing the room heating activated.
– Check any external switches.
Low system pressure
■ Not enough water in the climate system.
– Top up the water in the climate system.
The compressor does not start
■ There is no heating requirement.
– The heat pump does not call on heating nor hot water.
■ Temperature conditions tripped.
– Wait until the temperature condition has been re- set.
■ Minimum time between compressor starts has not been
reached.
– Wait 30 minutes and check if the compressor has started.
■ Alarm tripped.
– Follow the display instructions.
Additional heating only
If you are unsuccessful in rectifying the fault and are unable to
heat the house, you can, whilst waiting for assistance, continue
running the heat pump in ”add. heat only”. This means that
additional heating only is used to heat the house.
Set the installation to additional heat
mode
1. Go to menu 4.2 op. mode.
2. Mark ”add. heat only” using the control knob and then press
OK button.
Return to the main menus by pressing the Back button.
CAUTION
When commissioning without MTH air/water heat pump an
alarm communication error may appear in the display.
The alarm is reset if the relevant heat pump is deactivated
in menu 5.2.2 ("installed heat pump").
Summary of Contents for HMK60
Page 2: ...1 2 ...
Page 87: ...85 Technical data Electrical circuit diagram HSB60 ...
Page 88: ...86 Technical data HMK60 RC HY FDCW60VNX A FDCW60VNX A 2 FDCW60VNX A 3 ...
Page 89: ...87 Technical data FDCW60VNX A 2 FDCW60VNX A 3 RC HY RC HY RC HY ...
Page 90: ...88 Technical data RC HY RC HY RC HY ...
Page 93: ...91 Technical data sheet 3 ...
Page 94: ...92 Technical data sheet 4 ...
Page 97: ...95 Technical data sheet 3 ...
Page 98: ...96 Technical data sheet 4 ...
Page 99: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 100: ...98 Technical data sheet 6 ...
Page 101: ......
Page 104: ...1 2 FDCW71VNX FDCW100VNX LEK LEK ...
Page 189: ...85 Technical data Electrical circuit diagram HSB100 ...
Page 190: ...86 Technical data HMK100 RC HY FDCW FDCW FDCW ...
Page 191: ...87 Technical data FDCW FDCW RC HY RC HY RC HY ...
Page 192: ...88 Technical data RC HY RC HY RC HY ...
Page 195: ...91 Technical data sheet 3 ...
Page 196: ...92 Technical data sheet 4 ...
Page 199: ...95 Technical data sheet 3 ...
Page 200: ...96 Technical data sheet 4 ...
Page 201: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 202: ...98 Technical data sheet 6 ...
Page 203: ......
Page 206: ......
Page 277: ...71 Technical data Electrical circuit diagram HSB140 ...
Page 280: ...74 Technical data sheet 3 ...
Page 281: ...75 Technical data sheet 4 ...
Page 284: ...78 Technical data sheet 3 ...
Page 285: ...79 Technical data sheet 4 ...
Page 286: ...80 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 287: ...81 Technical data sheet 6 ...