Control
Menu 5.1.3 - max diff flow line temp.
max diff compressor
Setting range: 1 – 25 °C
Default value: 10 °C
max diff addition
Setting range: 1 – 24 °C
Default value: 7 °C
Here you set the maximum permitted difference between the
calculated and actual supply temperature during compressor
mode and add. heat mode. Max diff . additional heat can never
exceed max diff . compressor
max diff compressor
When the current supply temperature
deviates
from the set
value compared to that calculated, the heat pump is forced to
stop irrespective of the degreeminute value.
If the current supply temperature exceeds the calculated fl ow
temperature plus the set value, the degree minute value is set to
0. The compressor in the heat pump stops when there is only a
heating demand.
max diff addition
If "addition” is selected and activated in menu 4.2 and the
present supply temp
exceeds
the calculated temperature plus
the set value, the additional heat is forced to stop.
Menu 5.1.4 - alarm actions
Select how to control the heat pump in the event of an alarm.
You can choose to stop producing hot water and/or reduce the
room temperature.
CAUTION
If no alarm action is selected, it can result in
higher energy consumption in the event of an
alarm.
Menu 5.1.12 - addition
add type: step controlled
max step
Setting range (binary stepping deactivated): 0 – 3
Setting range (binary stepping activated): 0 – 7
Default value: 3
fuse size
Setting range: 1 – 200 A
Factory setting: 16 A
You can set the maximum number of permitted additional
heat steps, if there is internal additional heat in the tank (only
accessible if the additional heat is positioned after QN10),
whether binary stepping is to be used and the size of the
fuse.
<Add. Type: shurt controlled (RC-HY40 only)>
prioritised additional heat
Setting range: on/off
Factory setting: off
minimum running time
Setting range: 0 – 48 h
Default value: 12 h
min temp.
Setting range: 5 – 90 °C
Default value: 55 °C
mixing valve amplifier
Setting range: 0.1 –10.0
Default value: 1.0
mixing valve step delay
Setting range: 10 – 300 s
Default values: 30 s
fuse size
Setting range: 1 – 200 A
Factory setting: 16 A
transformation ratio
Setting range: 300 – 3000
Factory setting: 300
Select this option if shunt controlled additional heat is
connected.
Set when the addition is to start, the minimum run time and the
minimum temperature for external addition with shunt here.
External addition with shunt is for example a wood/oil/gas/
pellet boiler.
You can set shunt valve amplifi cation and shunt valve waiting
time.
Selecting "prioritised additional heat" uses the heat from the
external additional heat instead of the heat pump.
The shunt valve is regulated as long as heat is available,
otherwise the shunt valve is closed.
TIP
See the accessory installation instructions for function
description.
Menu 5.1.14 - flow set. climate system
presettings
Setting range: radiator, fl oor heat., rad. + fl oor heat.
Default value: radiator
Setting range DOT: -40.0 – 20.0 °C
The factory setting of DOT value depends on the country
that has been given for the product's location.
The example below refers to Sweden.
Factory setting DOT: -20.0 °C
own setting
Setting range dT at DOT: 0.0 – 25.0
Summary of Contents for HMK60
Page 2: ...1 2 ...
Page 87: ...85 Technical data Electrical circuit diagram HSB60 ...
Page 88: ...86 Technical data HMK60 RC HY FDCW60VNX A FDCW60VNX A 2 FDCW60VNX A 3 ...
Page 89: ...87 Technical data FDCW60VNX A 2 FDCW60VNX A 3 RC HY RC HY RC HY ...
Page 90: ...88 Technical data RC HY RC HY RC HY ...
Page 93: ...91 Technical data sheet 3 ...
Page 94: ...92 Technical data sheet 4 ...
Page 97: ...95 Technical data sheet 3 ...
Page 98: ...96 Technical data sheet 4 ...
Page 99: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 100: ...98 Technical data sheet 6 ...
Page 101: ......
Page 104: ...1 2 FDCW71VNX FDCW100VNX LEK LEK ...
Page 189: ...85 Technical data Electrical circuit diagram HSB100 ...
Page 190: ...86 Technical data HMK100 RC HY FDCW FDCW FDCW ...
Page 191: ...87 Technical data FDCW FDCW RC HY RC HY RC HY ...
Page 192: ...88 Technical data RC HY RC HY RC HY ...
Page 195: ...91 Technical data sheet 3 ...
Page 196: ...92 Technical data sheet 4 ...
Page 199: ...95 Technical data sheet 3 ...
Page 200: ...96 Technical data sheet 4 ...
Page 201: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 202: ...98 Technical data sheet 6 ...
Page 203: ......
Page 206: ......
Page 277: ...71 Technical data Electrical circuit diagram HSB140 ...
Page 280: ...74 Technical data sheet 3 ...
Page 281: ...75 Technical data sheet 4 ...
Page 284: ...78 Technical data sheet 3 ...
Page 285: ...79 Technical data sheet 4 ...
Page 286: ...80 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 287: ...81 Technical data sheet 6 ...