32
Electrical installation
Connection between controller and 3-way valve
(QN10/QN12)
3-way valve is used for switching heating / hot water
production (QN10), or switching heating / cooling (QN12).
Install appropriate valves according to the system structure on
site.
HSB140
HSB140 is not equipped with 3-way valve. Install the valves
on right position according to the diagram and connect wires
on appropriate port according to the type of controller.
<HSB140 with RC-HY20>
• 3-way valve for Heating / Hot water (QN10)
Connect the N, Control and L wire on 3-way valve to the port
2, 3 and 4 on X4 terminal on AA2 board on RC-HY20/40
respectively as shown below.
1
2
3
4
5
6
SMO
Externt
L
N
External
RC-HY20/40
AA2-X4
QN10
LEK
L N
1
1
0
2 3 4
PE
AA2-X4
RC-HY20/40
• 3-way valve for Heating / Cooling (QN12)
QN12 can be controlled with potential free variable relay.
Connect L and Control wire on 3-way valve to the port 15 and
16 on X4 terminal on AA2 board on RC-HY20 respectively.
Also, connect L and N wire to power supply as shown below.
Additional setting is necessary in menu 5.4. See Menu system
for details.
4
1
5
1
6
1
7
1
SMO
Externt
L
L
N
N
External
RC-HY 20
AA2-X4
LEK
L N
1
1
0
2 3 4
PE
AA2-X4
RC-HY20
QN12
CAUTION
The relay outputs can have a max load of 2 A
at resistive load (230V AC).
<HSB140 with RC-HY40>
Connect the port 5, 6 and 7 on X4 terminal on AA2 board on
RC-HY40 to the port PE, N and L on circulation pump
(EB101-GP12) respectively. Control signal cable is connected
between the port 7 and 8 on X4 terminal on AA3 board on RC-
HY40 and GND and PWM on circulation pump respectively as
shown below.
SMO
E
xternt
PE
L
N
External
RC-HY 40
AA2-X4
EB101-GP12
L N
1
1
0
2 3 4
PE
1 2 3
4
LEK
1 2 3
4
AA2-X4
4
5
6
7
8
9
RC-HY40
0
1
9
8
7
6 5
SMO
E
xternt
External
RC-HY 40
AA3-X4
EB101-GP12
PWM
GND
RC-HY40
AA3-X4
RC-HY40 can connect and control up to two pumps. Connect
the port 12, 13 and 15 on X4 terminal on AA2 board on RC-
HY40 to the port PE, N and L on second circulation pump
(EB102-GP12) respectively. Control cable is connected
between the port 5 and 6 on X4 terminal on AA3 board on RC-
HY40 and GND and PWM on circulation pump respectively as
shown below.
AA2-X4
1
1
2
1
3
1
4
1
5
1
6
1
SMO
E
xternt
PE
L
N
External
RC-HY 40
EB102-GP12
L N
1
1
0
2 3 4
PE
1 2 3
4
LEK
1 2 3
4
AA2-X4
RC-HY40
3
4
5
6
7
8
SMO
E
xternt
External
RC-HY 40
AA3-X4
EB102-GP12
PWM
GND
RC-HY40
AA3-X4
Summary of Contents for HMK60
Page 2: ...1 2 ...
Page 87: ...85 Technical data Electrical circuit diagram HSB60 ...
Page 88: ...86 Technical data HMK60 RC HY FDCW60VNX A FDCW60VNX A 2 FDCW60VNX A 3 ...
Page 89: ...87 Technical data FDCW60VNX A 2 FDCW60VNX A 3 RC HY RC HY RC HY ...
Page 90: ...88 Technical data RC HY RC HY RC HY ...
Page 93: ...91 Technical data sheet 3 ...
Page 94: ...92 Technical data sheet 4 ...
Page 97: ...95 Technical data sheet 3 ...
Page 98: ...96 Technical data sheet 4 ...
Page 99: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 100: ...98 Technical data sheet 6 ...
Page 101: ......
Page 104: ...1 2 FDCW71VNX FDCW100VNX LEK LEK ...
Page 189: ...85 Technical data Electrical circuit diagram HSB100 ...
Page 190: ...86 Technical data HMK100 RC HY FDCW FDCW FDCW ...
Page 191: ...87 Technical data FDCW FDCW RC HY RC HY RC HY ...
Page 192: ...88 Technical data RC HY RC HY RC HY ...
Page 195: ...91 Technical data sheet 3 ...
Page 196: ...92 Technical data sheet 4 ...
Page 199: ...95 Technical data sheet 3 ...
Page 200: ...96 Technical data sheet 4 ...
Page 201: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 202: ...98 Technical data sheet 6 ...
Page 203: ......
Page 206: ......
Page 277: ...71 Technical data Electrical circuit diagram HSB140 ...
Page 280: ...74 Technical data sheet 3 ...
Page 281: ...75 Technical data sheet 4 ...
Page 284: ...78 Technical data sheet 3 ...
Page 285: ...79 Technical data sheet 4 ...
Page 286: ...80 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 287: ...81 Technical data sheet 6 ...