Control
Menu 5.9 - floor drying function
length of period 1 – 7
Setting range: 0 – 30 days
Factory setting, period 1 – 3, 5 – 7: 2 days
Factory setting, period 4: 3 days
temp. period 1 – 7
Setting range: 15 – 70 °C
Default value:
temp. period 1
20 °C
temp. period 2
30 °C
temp. period 3
40 °C
temp. period 4
45 C
temp. period 5
40 °C
temp. period 6
30 °C
temp. period 7
20 °C
Set the function for under fl oor drying here.
You can set up to seven period times with diff erent calculated
fl ow temperatures. If less than seven periods
are to be used, set the remaining period times to 0 days.
Mark the active window to activate the underfloor drying
function. A counter at the bottom shows the number of days the
function has been active.
TIP
If operating mode "add. heat only" is to be used, select it in
menu 4.2.
Menu 5.10 - change log
Read off any previous changes to the control system here.
The date, time and ID no. (unique to certain settings) and the
new set value is shown for every change.
NOTE
The change log is saved at restart and remains unchanged
after factory setting.
Menu 5.4 – soft in/outputs
You can set the function of in/output for each terminal (AUX1-
6 and output).
Position of the terminal depends on the type of controller.
RC-HY20: port 11-18 on X2 terminal (AUX1-6), X4 terminal
on AA2 board (output)
RC-HY40: port 9-14 on terminal X6 and port 1-4 on X2
terminal on AA3 board (AUX1-6), X7 terminal on AA3 board
(output)
Menu 5.5 - factory setting service
All settings can be reset (including settings available to the
user) to default values here.
NOTE
When resetting, the start guide is displayed the next time
the control module is restarted.
Menu 5.6 - forced control
You can force control the diff erent components in the control
module and any connected accessories here.
Menu 5.7 - start guide
When the control module is started for the fi rst time the start
guide starts automatically. Start it manually here.
See page 25 for more information about the start guide.
Menu 5.8 - quick start
It is possible to start the compressor from here.
CAUTION
There must be a heating or hot water demand to start the
compressor.
CAUTION
Do not quick start the compressor too many times over a
short period of time as this may damage the compressor
and its surrounding equipment.
Summary of Contents for HMK60
Page 2: ...1 2 ...
Page 87: ...85 Technical data Electrical circuit diagram HSB60 ...
Page 88: ...86 Technical data HMK60 RC HY FDCW60VNX A FDCW60VNX A 2 FDCW60VNX A 3 ...
Page 89: ...87 Technical data FDCW60VNX A 2 FDCW60VNX A 3 RC HY RC HY RC HY ...
Page 90: ...88 Technical data RC HY RC HY RC HY ...
Page 93: ...91 Technical data sheet 3 ...
Page 94: ...92 Technical data sheet 4 ...
Page 97: ...95 Technical data sheet 3 ...
Page 98: ...96 Technical data sheet 4 ...
Page 99: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 100: ...98 Technical data sheet 6 ...
Page 101: ......
Page 104: ...1 2 FDCW71VNX FDCW100VNX LEK LEK ...
Page 189: ...85 Technical data Electrical circuit diagram HSB100 ...
Page 190: ...86 Technical data HMK100 RC HY FDCW FDCW FDCW ...
Page 191: ...87 Technical data FDCW FDCW RC HY RC HY RC HY ...
Page 192: ...88 Technical data RC HY RC HY RC HY ...
Page 195: ...91 Technical data sheet 3 ...
Page 196: ...92 Technical data sheet 4 ...
Page 199: ...95 Technical data sheet 3 ...
Page 200: ...96 Technical data sheet 4 ...
Page 201: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 202: ...98 Technical data sheet 6 ...
Page 203: ......
Page 206: ......
Page 277: ...71 Technical data Electrical circuit diagram HSB140 ...
Page 280: ...74 Technical data sheet 3 ...
Page 281: ...75 Technical data sheet 4 ...
Page 284: ...78 Technical data sheet 3 ...
Page 285: ...79 Technical data sheet 4 ...
Page 286: ...80 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 287: ...81 Technical data sheet 6 ...