12
Dimensioning expansion vessel
The expansion vessel volume must be at least 5% of total water
volume in the circulation system.
Initial pressure and max height difference
Recommended maximum height diff erence between expansion
vessel and the highest point in the system is 5m.
The initial pressure of the pressure expansion vessel must be
dimensioned according to the maximum height (H) between
the vessel and the highest positioned radiator, see figure. An
initial pressure of 0.5 bar (5 mvp) means a maximum permitted
height diff erence of 5 m.
If the standard initial pressure in the pressure vessel is not high
enough it can be increased by filling via the valve in the
expansion vessel. The expansion vessel’s standard initial
pressure must be entered in the check list on User’s manua1.
Any change in the initial pressure affects the ability of the
expansion vessel to handle the expansion of the water.
Consult local distributor in case height diff erence exceeds 5m.
H
Recommended installation order
1. Hang indoor unit and control unit to appropriate position
and connect indoor unit and tank unit.
2. Connect indoor unit to climate system, cold and hot water
lines as well as any external heat sources. See page 14.
Also see docking descriptions on page 23-24 and further
on.
3. Install refrigerant pipes according to the description on the
Installation manual for outdoor unit.
4. Connect current limiter, any centralised load control and
external contacts as well as the cable between indoor unit
and outdoor unit.
5. Connect incoming electricity to indoor unit and/or outdoor
unit. See page 29.
6. Follow the commissioning instructions on page 30-41.
General information for the installer
Summary of Contents for HMK60
Page 2: ...1 2 ...
Page 87: ...85 Technical data Electrical circuit diagram HSB60 ...
Page 88: ...86 Technical data HMK60 RC HY FDCW60VNX A FDCW60VNX A 2 FDCW60VNX A 3 ...
Page 89: ...87 Technical data FDCW60VNX A 2 FDCW60VNX A 3 RC HY RC HY RC HY ...
Page 90: ...88 Technical data RC HY RC HY RC HY ...
Page 93: ...91 Technical data sheet 3 ...
Page 94: ...92 Technical data sheet 4 ...
Page 97: ...95 Technical data sheet 3 ...
Page 98: ...96 Technical data sheet 4 ...
Page 99: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 100: ...98 Technical data sheet 6 ...
Page 101: ......
Page 104: ...1 2 FDCW71VNX FDCW100VNX LEK LEK ...
Page 189: ...85 Technical data Electrical circuit diagram HSB100 ...
Page 190: ...86 Technical data HMK100 RC HY FDCW FDCW FDCW ...
Page 191: ...87 Technical data FDCW FDCW RC HY RC HY RC HY ...
Page 192: ...88 Technical data RC HY RC HY RC HY ...
Page 195: ...91 Technical data sheet 3 ...
Page 196: ...92 Technical data sheet 4 ...
Page 199: ...95 Technical data sheet 3 ...
Page 200: ...96 Technical data sheet 4 ...
Page 201: ...97 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 202: ...98 Technical data sheet 6 ...
Page 203: ......
Page 206: ......
Page 277: ...71 Technical data Electrical circuit diagram HSB140 ...
Page 280: ...74 Technical data sheet 3 ...
Page 281: ...75 Technical data sheet 4 ...
Page 284: ...78 Technical data sheet 3 ...
Page 285: ...79 Technical data sheet 4 ...
Page 286: ...80 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 287: ...81 Technical data sheet 6 ...