Service
-
-
E49 - LP alarm
YES
YES
YES
Correct it.
NO
NO
NO
YES
NO
YES
NO
Is the low pressure sensor
correctly connected?
Check the value on the low
pressure sensor, via indoor
unit, in: (1) stationary
compressor, (2) compressor
operation.
Is the value around 0 MPa, without
significant change, both in states
(1) and (2)?
Check the insulation resistance on
the low pressure sensor.
Is the resistance greater than 100
ohm at DC 500 V?
Connect a pressure gauge to the
low pressure pipe and measure in
state (1). Compare with the value
shown on the indoor unit.
Replace the low pressure
sensor.
Is the difference less than 0.2 MPa?
Advance to checking the refrigerant
circuit on the next page.
Connect a new low pressure
sensor to the control PCB and
position it open in the atmosphere.
Is the pressure 0 MPa in the indoor
unit?
Replace the control PCB.
Replace the low pressure
sensor.
Troubleshooting guide
Summary of Contents for FDCW100VNX
Page 7: ...For Home Owners 6 For Home Owners ...
Page 20: ...Installation 19 Installation ...
Page 42: ...Control 41 Control ...
Page 66: ...System description 65 System description ...
Page 81: ...Service 80 Service ...
Page 148: ...Components 147 Components ...
Page 155: ...Technical data 154 Technical data ...
Page 156: ...Technical data Electrical circuit diagram 155 Electrical circuit diagram HM270V ...
Page 157: ...Technical data Electrical circuit diagram 156 ...
Page 158: ...Technical data Electrical circuit diagram 157 ...
Page 159: ...Technical data Electrical circuit diagram 158 ...
Page 160: ...Technical data Electrical circuit diagram 159 ...