31 - S. fault HP
NO
NO
Is the saturated temperature of
balanced pressure same or similar
to the outdoor air temperature
when the outdoor unit is stopping.
YES
YES
Is the service valve on the refrigerant
line open?
Is the service valve on the water
line open?
Is the valve(s) (QM31 or QN11)
functioning properly?
Is the operation signal of the
valves outputted correctly?
Is there clogging on the strainer
on the water line?
NO
Is the circulation pump setting (2.2.5)
done properly?
Set the appropriate value
to obtain enough water flow.
If the phenomenon persists,
Is the operation signal of the pump
outputted correctly?
Replace the refrigerant.
Connect it correctly
Replace the pump.
Open it.
Clean-up the strainer.
Is air-bleed done properly?
Open it.
Bleed the air in the water line.
Is the pressure sensor (BP4)
correctly connected?
YES
Does the pressure (external meter)
correspond with the value
displayed in the indoor unit?
NO
Replace the pressure sensor.
YES
YES
YES
YES
YES
NO
NO
NO
Replace the indoor unit relay board AA6.
NO
Replace the valve(s).
Replace the indoor unit relay board AA6.
NO
YES
YES
YES
NO
NO
Troubleshooting guide
Summary of Contents for FDCW100VNX
Page 7: ...For Home Owners 6 For Home Owners ...
Page 20: ...Installation 19 Installation ...
Page 42: ...Control 41 Control ...
Page 66: ...System description 65 System description ...
Page 81: ...Service 80 Service ...
Page 148: ...Components 147 Components ...
Page 155: ...Technical data 154 Technical data ...
Page 156: ...Technical data Electrical circuit diagram 155 Electrical circuit diagram HM270V ...
Page 157: ...Technical data Electrical circuit diagram 156 ...
Page 158: ...Technical data Electrical circuit diagram 157 ...
Page 159: ...Technical data Electrical circuit diagram 158 ...
Page 160: ...Technical data Electrical circuit diagram 159 ...