E59 - Inverter error
YES
NO
Disconnect the outdoor fan motor
connector and try to startup
Check power supply.
NO
Is power supply voltage OK?
YES
YES
NO
Is the insulation resistance and coil
resistance of compressor OK?
'HIHFWLYHFRPSUHVVRUĺUHSODFH
Try to startup several times.
Is power transistor module OK?
NO
'HIHFWLYHLQYHUWHU3&%ĺUHSODFH
YES
YES
Is the inverter output OK?
NO
'HIHFWLYHLQYHUWHU3&%ĺUHSODFH
Note: Several times restarting trial may
make a recovery from startup failure,
because liquid refrigerant migrated in the
compressor could be discharged during
several trial.
Can start?
NO
'HIHFWLYHFRPSUHVVRUĺUHSODFH
Is the pressure balance at starting
OK?
NO
Check refrigerant amount and
refrigerant circuit.
Does compressor startup?
'HIHFWLYHIDQPRWRUĺUHSODFH