Components
HM270V
- 149 -
Troubleshooting
Action
Cause
Indicator lamp
Off
1 × short + 1 × long
3 × short + 1 × long
5 × short + 1 × long
The pump is not connected or is incorrectly
connected.
Low voltage.
Temperature too high.
Pump blocked.
- Check the connection.
- Power failure. Check power supply and fuses.
- The pump restarts automatically.*
- Check max. system temperature.
- Check supply voltage.
- Open and clean the pump.
* The pump reduces the voltage automatically (the speed) at 105 °C, to stop completely at 125 °C. When the pump has cooled to 115 °C
again, it restarts automatically.
Other faults:
Action
Cause
Problem
Noise from pump.
Air in the system.
Dirt in the pump.
Worn bearings.
- Vent the system.
- Open and clean the pump.
- Replace the pump.
Technical specifications
Connection
Length
Voltage
Frequency
Output
Circulation pump
Max pressure height
Max volume flow
Min/max temperature
Max system pressure
6 m
3000
ℓ
/h
-10 °C* to +95 °C
6 bar
G1” Accessories
130 mm
200-240 V
50/60 Hz
9–63 W
* Not frozen or condensed
0
10
20
30
40
50
60
0
0.05
0.11
0.16 0.22
0.28
0.33
0.39 0.44
0.5 0.55
kPa
Available pressure
Flow
ℓ
/s
Summary of Contents for FDCW100VNX
Page 7: ...For Home Owners 6 For Home Owners ...
Page 20: ...Installation 19 Installation ...
Page 42: ...Control 41 Control ...
Page 66: ...System description 65 System description ...
Page 81: ...Service 80 Service ...
Page 148: ...Components 147 Components ...
Page 155: ...Technical data 154 Technical data ...
Page 156: ...Technical data Electrical circuit diagram 155 Electrical circuit diagram HM270V ...
Page 157: ...Technical data Electrical circuit diagram 156 ...
Page 158: ...Technical data Electrical circuit diagram 157 ...
Page 159: ...Technical data Electrical circuit diagram 158 ...
Page 160: ...Technical data Electrical circuit diagram 159 ...