Installation
- 21 -
Outdoor unit installation
CAUTION
Do not apply force beyond proper fastening
torque in tightening the flare nut.
Fix both liquid and gas service valves at the valve
main bodies as illustrated on the right, and then
fasten them, applying appropriate fastening torque.
Tightening angle
(
°
)
Tightening torque
(N-m)
Ǿ
6.35 (1/4")
Ǿ
9.52 (3/8")
Ǿ
12.7 (1/2")
Ǿ
15.88 (5/8")
14
〜
18
34
〜
42
49
〜
61
68
〜
82
45
〜
60
30
〜
45
30
〜
45
15
〜
20
150
200
250
300
●
Tighten a flare joint securely with a double spanner.
Use a torque wrench. If a torque wrench is not available,
fasten the flare nut manually first and then tighten it
further, using the left table as a guide.
Recommended length
of a tool handle (mm)
Operation valve size
(mm)
Do not hold the valve cap area with a spanner.
2. REFRIGERANT PIPING WORK
3) Refrigerant pipe wall thickness and material
●
Select refrigerant pipes of the table shown on the right wall thickness and material as
specified for each pipe size.
Pipe diameter [mm]
Minimum pipe wall thickness [mm]
Pipe material*
How to remove the service panel
9.52
0.8
O-type pipe
15.88
1.0
O-type pipe
NOTE
*Phosphorus deoxidized seamless copper pipe C1220T, JIS
H
3300
Catch
< Single type >
L
H
Outdoor unit
Indoor unit
1) Restrictions on unit installation and use
●
Check the following points in light of the indoor unit specifications and the installation site.
●
Observe the following restrictions on unit installation and use.
Improper installation can result in a compressor failure or performance degradation.
2) Determination of pipe size
●
Determine refrigerant pipe size pursuant to the following guidelines based on the indoor unit specifications.
One-way pipe length of refrigerant piping
Restrictions
Dimensional
restrictions
Marks appearing in the drawing on the right
L
H
H
Outdoor unit connected
Indoor unit connected
Connected indoor unit model
Refrigerant piping
Ǿ
15.88
Ǿ
15.88
φ
15.88
Flare
Elevation difference between
indoor and outdoor units
FDCW100VNX
HM270VS
Gas pipe
Liquid pipe
First remove the five screws (
mark) of the service panel and push it down into the
direction of the arrow mark and then remove it by pulling it toward you.
When the outdoor unit is positioned higher,
When the outdoor unit is positioned lower,
Single type
●
Take care so that installed pipes may not touch components within a unit. If touching with
an internal component, it will generate abnormal sounds and/or vibrations.
●
The pipe can be laid in any of the following directions: side right, front, rear and downward.
●
Remove a knock-out plate provided on the pipe penetration to open a minimum necessary area and attach an
edging material supplied as an accessory by cutting it to an appropriate length before laying a pipe.
●
Carry out the on site piping work with the operation valve fully closed.
●
Give sufficient protection to a pipe end (compressed and blazed, or with an adhesive tape) so that water or foreign
matters may not enter the piping.
●
Bend a pipe to a radius as large as practical.(R100
〜
R150)
Do not bend a pipe repeatedly to correct its form.
●
Flare connection is used between the unit and refrigerant pipe.
Flare a pipe after engaging a flare nut onto it.
Flare dimensions for R410A are different from those for conventional R407C.
Although we recommend the use
of flaring tools designed specifically for R410A, conventional flaring tools can also be used by adjusting the
measurement of protrusion B with a protrusion control gauge.
4) On-site piping work
IMPORTANT
A
B
Flared pipe end: A (mm)
Ǿ
6.35
Ǿ
9.52
Ǿ
12.7
Ǿ
15.88
Copper
pipe outer
diameter
0
ー
0
.
4
A
9
.
1
13
.
2
16.6
19.7
Copper pipe protrusion for flaring: B (mm)
Ǿ
6.35
Ǿ
9.52
Ǿ
12.7
Ǿ
15.88
Copper
pipe outer
diameter
In the case of a rigid (clutch) type
With an R410A tool
With a conventional tool
0
〜
0.5
0.7
〜
1.3
For downward connection
For side right connection
For front connection
For rear connection
●
Select pipes having a wall thickness larger
than the specified minimum pipe thickness.
12m or less
7m or less
7m or less
Ǿ
9.52
Flare
Ǿ
9.52
Ǿ
9.52
5) Air tightness test
①
Although outdoor and indoor units themselves have been tested for air tightness at the factory, check the connecting pipes after the installation work for air tightness from the operation
valve’s check joint equipped on the outdoor unit side. While conducting a test, keep the operation valve shut all the time.
a) Raise the pressure to 0.5 MPa, and then stop. Leave it for five minutes to see if the pressure drops.
b) Then raise the pressure to 1.5 MPa, and stop. Leave it for five more minutes to see if the pressure drops.
c) Then raise the pressure to the specified level (4.15 MPa), and record the ambient temperature and the pressure.
d) If no pressure drop is observed with an installation pressurized to the specified level and left for about one day, it is acceptable. When the ambient Temperature fall 1
℃
, the pressure also
fall approximately 0.01 MPa. The pressure, if changed, should be compensated for.
e) If a pressure drop is observed in checking e) and a) – d), a leak exists somewhere. Find a leak by applying bubble test liquid to welded parts and flare joints and repair it. After repair,
conduct an air-tightness test again.
②
In conducting an air-tightness test, use nitrogen gas and pressurize the system with nitrogen gas from the gas side. Do not use a medium other than nitrogen gas under any circumstances.
Gas side
operation valve
Check joint
Pressur
ize
Close
Outdoor unit
Indoor unit
<
Work flow
>
6) Evacuation
Pay attention to the following points in addition to the above for the
R410A and compatible machines.
○
To prevent a different oil from entering, assign dedicated tools, etc. to each
refrigerant type.
Under no circumstances must a gauge manifold and a charge
hose in particular be shared with other refrigerant types (R22, R407C, etc.).
○
Use a counterflow prevention adapter to prevent vacuum pump oil from
entering the refrigerant system.
Airtighteness test completed
Fill refrigerant
Vacuum gauge check
Vacuuming completed
Vacuuming begins
Run the vacuum pump for at least one hour after the vacuum
gauge shows -101kPa or lower. (-755mmHg or lower)
Confirm that the vacuum gauge indicator does not rise even if
the system is left for one hour or more.
When the system has remaining moisture
inside or a leaky point, the vacuum gauge
indicator will rise.
Check the system for a leaky point and then
draw air to create a vacuum again.
Wires for connecting indoor
and outdoor units
Band
Pipe cover
Exterior tape
Gas piping
insulation
Liquid piping
8) Insulation on piping
(1) Dress refrigerant pipes (both gas and liquid pipes) for heat insulation and prevention of dew condensation.
(2) Use a heat insulating material that can withstand 120
℃
or a higher temperature. Poor heat insulating capacity can cause heat insulation problems or cable deterioration.
- Improper heat insulation/anti-dew dressing can result in a water leak or dripping causing damage to household effects, etc.
- All gas pipes must be securely heat insulated in order to prevent damage from dripping water that comes from the condensation formed on them during a cooling operation or personal injury from burns because their surface can reach quite a
high temperature due to discharged gas flowing inside during a heating operation.
- Wrap indoor units’ flare joints with heat insulating parts (pipe cover) for heat insulation (both gas and liquid pipes).
- Give heat insulation to both gas and liquid side pipes.
Bundle a heat insulating material and a pipe tightly together so that no gaps may be left between them and wrap them together with a connecting cable by a dressing tape.
-
Both gas and liquid pipes need to be dressed with 20 mm or thicker heat insulation materials above the ceiling where relative humidity exceeds 70%.
7) Refrigerant charge
(1) Since this unit contains 2.9kg refrigerant including the amount for piping of 12m, it is not necessary to charge addifional refrigerant for piping on site.
(2) Charging refrigerant
●
Since R410A refrigerant must be charged in the liquid phase, you should charge it, keeping the container cylinder upside down or using a refrigerant cylinder equipped with a siphon tube.
●
Charge refrigerant always from the liquid side service port with the operation valve shut.
When you find it difficult to charge a required amount, fully open the outdoor unit valves on both liquid and gas sides and charge refrigerant from the
gas (suction) side service port, while running the unit in the cooling mode.
In doing so, care must be taken so that refrigerant may be discharged from the cylinder in the liquid phase all the time.
When the cylinder valve is throttled down
or a dedicated conversion tool to change liquid-phase refrigerant into mist is used to protect the compressor, however, adjust charge conditions so that refrigerant will gasify upon entering the unit.
●
In charging refrigerant, always charge a calculated volume by using a scale to measure the charge volume.
●
When refrigerant is charged with the unit being run, complete a charge operation within 30 minutes.
Running the unit with an insufficient quantity of refrigerant for a long time can cause a compressor failure.
●
To charge refrigerant again to the system, recover refrigerant from the system first and then charge the same volume as initial charge.
Summary of Contents for FDCW100VNX
Page 7: ...For Home Owners 6 For Home Owners ...
Page 20: ...Installation 19 Installation ...
Page 42: ...Control 41 Control ...
Page 66: ...System description 65 System description ...
Page 81: ...Service 80 Service ...
Page 148: ...Components 147 Components ...
Page 155: ...Technical data 154 Technical data ...
Page 156: ...Technical data Electrical circuit diagram 155 Electrical circuit diagram HM270V ...
Page 157: ...Technical data Electrical circuit diagram 156 ...
Page 158: ...Technical data Electrical circuit diagram 157 ...
Page 159: ...Technical data Electrical circuit diagram 158 ...
Page 160: ...Technical data Electrical circuit diagram 159 ...