2 PARAMETER SETTINGS
2.3 Basic Settings
67
2
Network Configuration Settings
Set parameters of slave stations (the number of points and assignment of link devices) in the master station.
Setting procedure
The procedure for the network configuration settings is shown below.
1.
Select the module in "Module List" and drag it to the list of stations or the network map.
2.
Set the required items.
3.
Select [Close with Reflecting the Setting] to finish the network configuration settings.
When changing the network configuration settings after setting "Safety Communication Setting" under
"Application Settings", correct the safety communication setting.
Setting items
Item
Description
Setting range
[Detect Now] button
Automatically reads the information of slave stations.
For details, refer to the following.
iQ Sensor Solution Reference Manual
Mode Setting
The mode of the master station is displayed.
Assignment Method
Select a link device assignment method.
• Point/Start: Enter the points and start Nos. of link devices.
• Start/End: Enter the start and end Nos. of link devices.
• Point/Start
• Start/End
(Default: Start/End)
Link Scan Time
(Approx.)
The approximate link scan time is displayed.
No.
The total number of slave stations set in "Network Configuration Settings" is displayed.
Model Name
The module model name is displayed.
To set a module where the profile is not registered, select it from the "General CC IE Field
Module" list or register the profile before setting the model name. For how to register a
profile, refer to the following.
GX Works3 Operating Manual
STA#
Enter the station No. of each slave station connected to the network.
Station Nos. do not need to be set consecutively, but must be unique.
The station No. of the master station is fixed at "0".
1 to 120
(Default: Blank)
Station Type
Select the station type (excluding the master station). Select the station type same as that
of the modules connected to the network.
• Remote I/O Station
• Remote Device Station
• Intelligent Device Station
• Local Station
(Default: Varies depending on the set
module)
List of stations
Drag and drop the text.
Network map
Summary of Contents for RD77GF16
Page 1: ...MELSEC iQ R Simple Motion Module User s Manual Network RD77GF4 RD77GF8 RD77GF16 RD77GF32 ...
Page 2: ......
Page 181: ...I 179 MEMO ...
Page 185: ......