1 FUNCTIONS
1.5 IP Packet Transfer Function
47
1
Ex.
Improper setting
*1 The error of CPU module "IP communication test error" (error code: 4A28H) occurs in the IP communication test. (
MELSEC iQ-R
CPU Module User's Manual (Application))
IP communication test
This function checks whether no error occurs in the communication path within CC-Link IE Field Network when the IP packet
transfer function is used. The following can be checked using the IP communication test:
• Cables are properly connected on the communication path.
• Parameters related to the IP packet transfer function, such as an IP address and routing parameters, are correctly set on
the communication path.
• All the CPU modules and master/local modules on the communication path support the IP packet transfer function.
The following system configuration is used to explain the procedure of the IP communication test.
The IP communication test allows the communication paths in the dotted line above to be checked.
A
B
C
2
2
3
1
2
1
Because the communication route for data sending is different
from that for data receiving, an error occurs.
*1
Communication routes set using the routing parameters
Communication route automatically set (from a module that
does not have the routing parameters to the master station)
Setting for
Network No.
Relay station
Station
Setting for
Setting for
The setting is not required
because the module does not
have the routing parameters.
Network No.
Target station
Network No.
Relay station
Station
Network No.
Target station
A
B
C
Ethernet device
(request source device)
Ethernet device
(request destination device)
Local station
Master station
Network No.1
Network No.2
Network No.3
Station
No.2
Station
No.1
Station
No.0
192.168.1.1
192.168.10.1
Network No.1
Network No.10
CPU module 1: 192.168.1.10
Master station (station No.0):
192.168.2.125
CPU module 2: 192.168.10.10
Local station (station No.2):
192.168.2.2
Network No.2
Ethernet device
(request destination device)
Ethernet device
(request source device)
Simple Motion
module
Summary of Contents for RD77GF16
Page 1: ...MELSEC iQ R Simple Motion Module User s Manual Network RD77GF4 RD77GF8 RD77GF16 RD77GF32 ...
Page 2: ......
Page 181: ...I 179 MEMO ...
Page 185: ......